Modify the value of the unlocked parameter by pressing buttons and . The setting
is confirmed by pressing the button . By pressing buttons , you can move to
another parameter and repeat the procedure.
exit parameter settings by pressing the button .
Warning: Change of service and functional parameters must be carried out only by
a properly qualified expert.
35
Service parameters
12.3
Basic parameters:
Para-
Function
Parameter description
Setting
Default
meter
range
value
S1.1
S1.2
S1.4
S1.5
S1.9
S1.17
S1.18
HYDRAULIC SCHEME
Selection of hydraulic scheme.
01 - 04
01
CODE FOR
UNLOCKING THE
SERVICE SETTINGS
This setting enables the change of code
which is necessary to unlock the service
settings.
WARNING! Keep new code on a safe
place. Without this code is impossible
to change service settings.
0000 ÷ 9999
0001
ACTUATOR
OPENING DIRECTION
Setting of actuator turning direction -
valve opening.
0- RIGHT
1- LEFT
0
ANTI-BLOCK
FUNCTION FOR
PUMP AND VALVE
All outputs that haven’t been activated
in the last week are activated on Friday
at 20:00 for 60 seconds.
0- OFF
1- ON
0
DISPLAY ORIENTATION
Setting of display orientation.
0 - REGULAR 0°
1 - ROTATED
180°
0
SENSOR T1
CALIBRATION
Correction of displayed measured tem-
perature for sensor T1.
-5 ÷ 5 K
0
SENSOR T2
CALIBRATION
Correction of displayed measured tem-
perature for sensor T2.
-5 ÷ 5 K
0
Constant temperature controller
GB