OEG 150 Скачать руководство пользователя страница 30

30

Fresh-water, Combined and Buffer Storage Tanks

GB

Drinking water 
connection

3.2

Mixed installation

3.3

According to technical rules, an appropriate electrical separation of the conductive 
connection between the different materials has to be provided for mixed installations.

Pressure shocks / 
water hammers

3.4

When installing fast-closing shut-off and water-tapping valves (solenoid valves, ball 
valves, single-lever mixers), it might come to short-term pressure shocks in drinking 
water installations becoming noticable in the form of disturbing noises and eventually 
leading to wear and break of pipes and storage tanks. When using such components, 
appropriate water hammer dampers are to be provided. We assume no liability for 
damages caused by pressure shocks and water hammers.

1.) Absperrventil
2.) Prüfvorrichtung für Rückflussverhinderer
3.) Rückflussverhinderer
4.) Manometeranschlussstutzen
5.) Absperrventil
6.) Sicherheitsventil mit Abblasleitung und Trichtersiphon
7.) Membranausdehnungsgefäß

1

2

3

4

5

6

7

1.) Shut-off valve
2.) Tester for non-return valve
3.) Non-return valve
4.) Pressure gauge connection
5.) Shut-off valve
6.) Safety valve with drain line and funnel siphon
7.) Diaphragm expansion tank

up to 300 liter

more than 400 liter

The valid standards and regulations have to be complied with. The cold water connection has
to comply with DIN 1988 / DIN EN 1717 and DIN 4753, Part 1. 

In areas with a water hardness of over 20° dH we recommend the use of softening units or
the installation of flush taps in combination with fresh-water storage tanks in order to 
facilitate the cleaning of the domestic hot water heat exchanger.

Содержание 150

Страница 1: ...icher D Installation and Operating Instructions Fresh water combined and buffer storage tanks GB Notice de montage et d emploi Ballons d eau fra che instantan e ballons combin s et ballons tampons FR...

Страница 2: ...her 2250 5000 Pufferspeicher 10000 Frischwasserspeicher 150 500 Frischwasserspeicher 800 1500 Frischwasserspeicher 2250 5000 Unterstellfrischwasserspeicher stehend 80 200 Liegend und Unterstellpuffers...

Страница 3: ...sserspeicher 150 500 Liter Seite 15 800 1500 Liter Seite 16 2250 5000 Liter Seite 17 Liegendspeicher und Unterstellspeicher Liegend und Unterstellpufferspeicher 120 500 Liter Seite 19 Liegend und Unte...

Страница 4: ...ser Montageanleitung in Widerspruch zu den l nderspezifisch g lti gen Vorschriften stehen so sind die l nderspezifisch g ltigen Vorschriften vorzuziehen Arbeiten am Speicher 2 3 Installationen und Inb...

Страница 5: ...izier tes Fachpersonal und nach Installationsanleitung des Herstellers erfolgen F r Tauchheiz k rper gelten die Gew hrleistungsbestimmungen des Herstellers Installation Inbetriebnahme 3 Alle Speicher...

Страница 6: ...icht unter die Gew hrleistung Die g ltigen Normen und Vorschriften m ssen eingehalten werden Der Kaltwasseranschluss hat nach DIN 1988 DIN EN 1717 und DIN 4753 1 zu erfolgen WICHTIG In Gebieten mit ho...

Страница 7: ...le Wartung und Reinigung 4 WICHTIG Die Entleerung bei Frischwasser und Kombispeichern erfolgt in umgekehrter Rei henfolge zur Inbetriebnahme Bei Wartung der Trinkwasserseite ist zuerst die Heizwasser...

Страница 8: ...ionsanleitung des Herstellers erfolgen F r Fremdstromanoden gelten die Gew hrleistungsbedingungen des Herstellers Frischwasserspeicher sind trinkwasserseitig mit einem Edelstahlwellrohr 1 4404 ausge s...

Страница 9: ...bei Speichern mit emaillierten Trinkwasserbeh ltern durch die Flansch ffnung Die emaillierte Innenfl che verhindert eine Kalksteinbildung weitestge hend und erm glicht ein schnelles Reinigen von lose...

Страница 10: ...se j hrliche Reinigung bei einer H rte des Trinkwassers von ber 20 dH j hrliche Kontrolle der Magnesium Schutzanode und Austausch alle zwei Jahre bei Speichern mit emailliertem Trinkwasserbeh lter Ent...

Страница 11: ...l che Volumen m l 0 63 4 2 0 63 4 2 0 77 5 1 73 11 3 1 74 11 4 Glattrohrw rmetauscher pmax tmax bar C 10 130 10 130 10 130 10 130 10 130 R cklauf W rmeerzeuger R 1 A mm 132 132 132 130 137 R cklauf Gl...

Страница 12: ...5 29 7 Glattrohrw rmetauscher oben Fl che Volumen m l 2 2 14 2 2 6 17 2 8 18 6 Glattrohrw rmetauscher pmax tmax bar C 10 130 10 130 10 130 R cklauf W rmeerzeuger Rp 1 A mm 255 255 312 R cklauf Glattr...

Страница 13: ...39 5 5 36 6 8 44 7 8 51 Glattrohrw rmetauscher oben Fl che Volumen m l 2 5 16 4 6 30 5 5 36 6 8 44 7 8 51 Glattrohrw rmetauscher pmax tmax bar C 10 130 10 130 10 130 10 130 10 130 R cklauf W rmeerzeu...

Страница 14: ...3 95 R cklauf W rmeerzeuger Rp 2 A mm 571 Frei verf gbar Flansch DN150 PN6 B mm 626 Frei verf gbar Rp 2 C mm 1381 Frei verf gbar Rp 2 D mm 2191 Frei verf gbar Flansch DN150 PN6 E mm 2946 Vorlauf W rme...

Страница 15: ...n Fl che Volumen m l 0 77 5 1 15 7 5 1 15 7 5 1 88 12 3 1 88 12 4 Glattrohrw rmetauscher mitte Fl che Volumen m l 1 15 7 5 Glattrohrw rmetauscher oben Fl che Volumen m l 0 63 4 2 0 63 4 2 0 77 5 1 73...

Страница 16: ...x tmax bar C 6 95 6 95 6 95 Glattrohrw rmetauscher unten Fl che Volumen m l 2 6 17 3 3 21 3 4 5 29 7 Glattrohrw rmetauscher oben Fl che Volumen m l 2 2 14 2 2 6 17 2 8 18 6 Glattrohrw rmetauscher pmax...

Страница 17: ...39 5 Trinkwasserw rmetauscher pmax tmax bar C 6 95 6 95 6 95 6 95 6 95 Glattrohrw rmetauscher unten Fl che Volumen m l 4 9 32 5 9 39 5 5 36 6 8 44 7 8 51 Glattrohrw rmetauscher oben Fl che Volumen m l...

Страница 18: ...rmhalteverlust nach EN 12897 W 23 26 28 31 Sch ttleistung 45 C Speicher 65 C Kaltwasser 10 C kein Nachheizen l 50 68 85 115 Leistungskennzahl NL in Anlehnung an DIN 4708 0 6 0 8 1 1 2 Speicher pmax tm...

Страница 19: ...nung Nr 812 2013 A A A A A A Warmhalteverlust nach EN 12897 W 26 29 31 36 41 43 Speicher pmax tmax bar C 3 95 3 95 3 95 3 95 3 95 3 95 R cklauf W rmeerzeuger R 1 A mm Frei verf gbar R 1 B mm Frei verf...

Страница 20: ...3 95 3 95 3 95 3 95 3 95 3 95 Trinkwasserw rmetauscher Fl che Volumen m l 1 52 6 92 2 1 9 6 2 5 11 2 5 11 5 1 23 5 1 23 Trinkwasserw rmetauscher pmax tmax bar C 6 95 6 95 6 95 6 95 6 95 6 95 Zusatzw...

Страница 21: ...max tmax bar C 10 95 Glattrohrw rmetauscher unten Fl che Volumen m l 2 13 Glattrohrw rmetauscher pmax tmax bar C 10 130 R cklauf W rmeerzeuger Rp 1 A mm 221 R cklauf Glattrohrw rmetauscher unten Rp 1...

Страница 22: ...unten Fl che Volumen m l 2 6 17 3 3 21 3 4 5 29 7 Glattrohrw rmetauscher pmax tmax bar C 10 130 10 130 10 130 R cklauf W rmeerzeuger Rp 1 A mm 255 255 312 R cklauf Glattrohrw rmetauscher unten Rp 1 B...

Страница 23: ...16 Glattrohrw rmetauscher pmax tmax bar C 10 130 10 130 10 130 Frei verf gbar R 1 A mm 137 137 137 F hlerh lse 6 mm B mm 227 227 227 Frei verf gbar R 1 C mm 317 317 317 Kaltwasseranschluss R 1 D mm 53...

Страница 24: ...F r Ihre Notizen...

Страница 25: ...F r Ihre Notizen...

Страница 26: ...10 000 Fresh water storage tanks 150 500 Fresh water storage tanks 800 1 500 Fresh water storage tanks 2 250 5 000 Built under fresh water storage tanks vertical 80 200 Horizontal and built under buf...

Страница 27: ...tanks 150 500 litres page 38 800 1 500 litres page 39 2 250 5 000 litres page 40 Horizontal and built under fresh water storage tanks Horizontal and built under buffer storage tanks 120 500 litres pag...

Страница 28: ...water installations must absolutely be adhered to If any specifications in this manual are in contradiction to the country specific provisions the latter are preferable Work on the storage tank 2 3 I...

Страница 29: ...mmersion heaters are subject to the warranty conditions of the manufacturer The cold water connection of the storage tank is connected with the drinking water network the hot water connection is conne...

Страница 30: ...e no liability for damages caused by pressure shocks and water hammers 1 Absperrventil 2 Pr fvorrichtung f r R ckflussverhinderer 3 R ckflussverhinderer 4 Manometeranschlussstutzen 5 Absperrventil 6 S...

Страница 31: ...side Commissioning 3 5 Control maintenance and cleaning 4 IMPORTANT Draining of fresh water and combined storage tanks is performed in reverse order to commisssioning When maintaining the drinking wa...

Страница 32: ...d by qualified personnel and according to the installation instructions of the manufacturer The impressed current anodes are subject to the warranty conditions of the manufacturer Fresh water tanks ar...

Страница 33: ...ss of over 20 dH a yearly cleaning interval is a requirement for asserting any warranty claims The cleaning is done through the flange aperture The enamelled internal surface prevents limestone format...

Страница 34: ...of the storage tank and all its connections and its flange yearly control of the magnesium anode and its replacement every two years cleaning every two years incl replacement of the flange seal for co...

Страница 35: ...1 042 I mm 682 878 1 347 1 265 1 317 J mm 752 982 1 487 1 465 1 482 K mm 1 565 1 587 L mm 1 019 1 264 1 749 1 695 1 731 M mm 792 1 032 1 517 1 485 1 508 N mm 682 910 1 423 1 265 1 279 O mm 500 689 1...

Страница 36: ...5 29 7 Smooth pipe heat exchanger top surface volume m l 2 2 14 2 2 6 17 2 8 18 6 Smooth pipe heat exchanger pmax tmax bar C 10 130 10 130 10 130 Return heat generator Rp 1 A mm 255 255 312 Return smo...

Страница 37: ...1 665 G mm 1 033 769 1 109 1 095 1 070 H mm 1 348 1 519 1 341 1 745 1 720 I mm 1 348 1 439 1 254 1 745 1 720 J mm 1 348 1 519 1 341 1 745 1 720 K mm 1 733 2 019 1 809 2 375 2 350 L mm 1 648 1 989 177...

Страница 38: ...tmax bar C 3 95 Return heat generator Rp 2 A mm 571 Freely available flange DN150 PN6 B mm 626 Freely available Rp 2 C mm 1 381 Freely available Rp 2 D mm 2 191 Freely available flange DN150 PN6 E mm...

Страница 39: ...mm 1 019 1 264 1 749 1 695 1 731 O mm 792 1 032 1 517 1 485 1 508 P mm 682 910 1 423 1 265 1 279 Q mm 500 689 1 145 895 910 R mm 242 242 242 245 252 Real volume according to EN 12897 Fire protection...

Страница 40: ...max bar C 6 95 6 95 6 95 Smooth pipe heat exchanger bottom surface volume m l 2 6 17 3 3 21 3 4 5 29 7 Smooth pipe heat exchanger top surface volume m l 2 2 14 2 2 6 17 2 8 18 6 Smooth pipe heat excha...

Страница 41: ...mm 1 348 1 519 1 341 1 745 1 720 I mm 1 348 1 439 1 254 1 745 1 720 J mm 1 348 1 519 1 341 1 745 1 720 K mm 1 733 2 019 1 809 2 375 2 350 L mm 1 648 1 989 1 774 2 375 2 350 M mm 1 750 2 024 1 809 2 39...

Страница 42: ...tion no 812 2013 A A A A Heat retaining loss according to EN 12897 W 23 26 28 31 Output capacity 45 C storage tanks 65 C cold water 10 C no reheating l 50 68 85 115 Performance factor NL following DIN...

Страница 43: ...regulation no 812 2013 A A A A A A Heat retaining loss according to EN 12897 W 26 29 31 36 41 43 Storage tank pmax tmax bar C 3 95 3 95 3 95 3 95 3 95 3 95 Return heat generator R 1 A mm Freely availa...

Страница 44: ...age tank pmax tmax bar C 3 95 3 95 3 95 3 95 3 95 3 95 DHW heat exchanger surface volume m l 1 52 6 92 2 1 9 6 2 5 11 2 5 11 5 1 23 5 1 23 DHW heat exchanger pmax tmax bar C 6 95 6 95 6 95 6 95 6 95 6...

Страница 45: ...max bar C 10 95 Smooth pipe heat exchanger bottom surface volume m l 2 13 Smooth pipe heat exchanger pmax tmax bar C 10 130 Return heat generator Rp 1 A mm 221 Return smooth pipe heat exchanger bottom...

Страница 46: ...e volume m l 2 6 17 3 3 21 3 4 5 29 7 Smooth pipe heat exchanger pmax tmax bar C 10 130 10 130 10 130 Return heat generator Rp 1 A mm 255 255 312 Return smooth pipe heat exchanger bottom Rp 1 B mm 413...

Страница 47: ...changer pmax tmax bar C 10 130 10 130 10 130 Freely available R 1 A mm 137 137 137 Sensor sleeve 6 mm B mm 227 227 227 Freely available R 1 C mm 317 317 317 Cold water connection R 1 D mm 531 531 531...

Страница 48: ...Notes...

Страница 49: ...Notes...

Страница 50: ...he instantan e 800 1500 Ballons d eau fra che instantan e 2250 5000 Ballons d eau fra che instantan e install s sous le plan de travail verticaux 80 200 Ballons tampons horizontaux et ballons tampons...

Страница 51: ...itres page 63 800 1500 litres page 64 2250 5000 litres page 65 Ballons horizontaux et ballons install s sous le plan de travail Ballons tampons horizontaux et ballons tampons install s sous le plan de...

Страница 52: ...iques un pays suivre les r glementations sp cifiques du pays en vigueur Travaux sur le ballon 2 3 L installation la mise en service l entretien ainsi que les r parations doivent tre effectu s par du p...

Страница 53: ...fectu s par du personnel qualifi et selon les instructions d installation du fabricant Pour les corps de chauffe visser les conditions de garantie du fabricant sont applicables Installation Mise en se...

Страница 54: ...en vigueur doivent tre respect es Le raccordement d eau froide doit tre effectu conform ment aux normes DIN 1988 DIN EN 1717 et DIN 4753 IMPORTANT Pour les r gions pr sentant une duret d eau lev e de...

Страница 55: ...5 Contr le entretien et nettoyage 4 IMPORTANT le vidange des ballons d eau fra che instantan e et des ballons combin s a lieu dans l ordre contraire celui lors de la mise en service Lors de la mainte...

Страница 56: ...selon les instructions d installation du fabricant Pour les anodes courant impos les conditions de garantie du fabricant sont applicables Les ballons d eau fra che instantan e sont quip s du c t eau s...

Страница 57: ...oir d eau chaude sanitaire maill le nettoyage s effectue par l ouverture de bride La surface int rieure maill e emp che largement la formation de calcaire et permet un nettoyage rapide des r sidus de...

Страница 58: ...nuel en cas de duret de l eau sanitaire de plus de 20 dH V rification annuelle de l anode magn sium et remplacement de celle ci tous les deux ans pour les ballons avec r servoir d eau chaude sanitaire...

Страница 59: ...5 1482 K mm 1565 1587 L mm 1019 1264 1749 1695 1731 M mm 792 1032 1517 1485 1508 N mm 682 910 1423 1265 1279 O mm 500 689 1145 895 910 P mm 242 242 242 245 252 Capacit r elle selon EN 12897 Classe de...

Страница 60: ...contenance m l 2 2 14 2 2 6 17 2 8 18 6 Pression max Temp rature max de l changeur thermique tube lisse bar C 10 130 10 130 10 130 Retour g n rateur de chaleur Rp 1 A mm 255 255 312 Retour changeur th...

Страница 61: ...350 L mm 1648 1989 1774 2375 2350 M mm 1750 2024 2390 2365 N mm 1733 2019 1809 2375 2350 O mm 2112 2391 2245 2840 2828 P mm diverses hauteurs diverses hauteurs diverses hauteurs diverses hauteurs dive...

Страница 62: ...PN6 B mm 626 Librement disponible Rp 2 C mm 1381 Librement disponible Rp 2 D mm 2191 Librement disponible bride DN150 PN6 E mm 2946 D part changeur thermique Rp2 F mm 3001 Purge Rp 1 G mm 3655 Libreme...

Страница 63: ...ude sanitaire pmax tmax bar C 6 95 6 95 6 95 6 95 6 95 Echangeur thermique tube lisse en bas surface contenance m l 0 77 5 1 15 7 5 1 15 7 5 1 88 12 3 1 88 12 4 Echangeur thermique tube lisse au milie...

Страница 64: ...thermique eau chaude sanitaire m l 8 34 8 34 8 34 Pression max Temp rature max de l changeur thermique eau chaude sanitaire bar C 6 95 6 95 6 95 Echangeur thermique tube lisse en bas surface contenanc...

Страница 65: ...1733 2019 1809 2375 2350 O mm 2112 2391 2245 2840 2828 P mm diverses hauteurs diverses hauteurs diverses hauteurs diverses hauteurs diverses hauteurs Capacit r elle selon EN 12897 Classe de r sistance...

Страница 66: ...45 C ballon 65 C eau froide 10 C pas de r chauffement n cessaire l 50 68 85 115 Coefficient de performance NL selon DIN 4708 0 6 0 8 1 1 2 Pression max Temp rature max du ballon bar C 3 95 3 95 3 95 3...

Страница 67: ...A A A A A Perte de maintien au chaud selon EN 12897 W 26 29 31 36 41 43 Pression max Temp rature max du ballon bar C 3 95 3 95 3 95 3 95 3 95 3 95 Retour g n rateur de chaleur R 1 A mm Librement dispo...

Страница 68: ...taire m l 1 52 6 92 2 1 9 6 2 5 11 2 5 11 5 1 23 5 1 23 Pression max Temp rature max de l changeur thermique eau chaude sanitaire bar C 6 95 6 95 6 95 6 95 6 95 6 95 Echangeur thermique suppl mentaire...

Страница 69: ...changeur thermique tube lisse en bas surface contenance m l 2 13 Pression max Temp rature max de l changeur thermique tube lisse bar C 10 130 Retour g n rateur de chaleur Rp 1 1 2 A mm 221 Retour chan...

Страница 70: ...ax Temp rature max de l changeur thermique tube lisse bar C 10 130 10 130 10 130 Retour g n rateur de chaleur Rp 1 A mm 255 255 312 Retour changeur thermique tube lisse en bas Rp 1 B mm 413 363 470 Li...

Страница 71: ...haude sanitaire bar C 10 95 10 95 10 95 Echangeur thermique tube lisse surface en bas surface contenance m l 1 6 1 6 Echangeur thermique tube lisse surface en haut surface contenance m l 1 2 8 1 2 8 2...

Страница 72: ...Pour vos notes...

Страница 73: ...Pour vos notes...

Страница 74: ...n 2250 5000 Buffervaten 10000 Verswaterboilers 150 500 Verswaterboilers 800 1500 Verswaterboilers 2250 5000 Onderstel verswaterboilers staand 80 200 Horizontale en onderstel buffervaten 120 500 Horizo...

Страница 75: ...erboilers 150 500 liter pagina 86 800 1500 liter pagina 87 2250 5000 liter pagina 88 Horizontale en onderstelboilers Horizontale en onderstel buffervaten 120 500 liter pagina 90 Horizontale en onderst...

Страница 76: ...stallaties moeten strikt worden nageleefd Als informatie in deze montagehandleiding in tegenspraak is met de land specifieke voorschriften dan dienen de land specifieke voorschriften te worden nagelee...

Страница 77: ...iceerd personeel en volgens de installatiehandleiding van de betreffende fabrikant Voor dompelaars zijn de garantievoorwaarden van de fabrikant van toepassing verswater combinatie en bufferopslag NL I...

Страница 78: ...lep 4 Manometeraansluiting 5 Afsluiter 6 Veiligheidsklep met overstort en trechtersifon 7 Membraanexpansievat bis 300 Liter ab 400 Liter verswater combinatie en bufferopslag NL Gecombineerde installat...

Страница 79: ...opslag NL Inspectie onderhoud en reiniging 4 BELANGRIJK het legen van verswaterboilers en gecombineerde opslagvaten gebeurt in omgekeerde volgorde van inbedrijfstelling Bij het onderhoud aan de zijde...

Страница 80: ...ceerd vakpersoneel en in overeenstemming met de installatie instructies van de fabrikant Voor buitenlandse parasitaire stroomanoden zijn de garantievoorwaarden van de fabrikant van toepassing Verswate...

Страница 81: ...t voor het reinigen wegens gevaar voor beschadiging van het vat of de emaillelaag Het reinigen van de drinkwater warmtewisselaar van verswaterboilers vindt plaats door middel van een geschikt ontkalki...

Страница 82: ...rlijkse reiniging bij een waterhardheid van meer dan 20 dH Jaarlijkse controle van de magnesiumanode en vervanging om de twee jaar Bij opslagvaten met een ge mailleerd drinkwatervat Verwijdering van d...

Страница 83: ...1217 1025 1042 I mm 682 878 1347 1265 1317 J mm 752 982 1487 1465 1482 K mm 1565 1587 L mm 1019 1264 1749 1695 1731 M mm 792 1032 1517 1485 1508 N mm 682 910 1423 1265 1279 O mm 500 689 1145 895 910...

Страница 84: ...uiswarmtewisselaar boven oppervlak volume m l 2 2 14 2 2 6 17 2 8 18 6 Buiswarmtewisselaar pmax tmax bar C 10 130 10 130 10 130 Retour warmtegenerator Rp 1 A mm 255 255 312 Retour buiswarmtewisselaar...

Страница 85: ...1665 G mm 1033 769 1109 1095 1070 H mm 1348 1519 1341 1745 1720 I mm 1348 1439 1254 1745 1720 J mm 1348 1519 1341 1745 1720 K mm 1733 2019 1809 2375 2350 L mm 1648 1989 1774 2375 2350 M mm 1750 2024 2...

Страница 86: ...warmtegenerator Rp 2 A mm 571 Vrij beschikbaar flens DN150 PN6 B mm 626 Vrij beschikbaar Rp2 C mm 1381 Vrij beschikbaar Rp2 D mm 2191 Vrij beschikbaar flens DN150 PN6 E mm 2946 Voorstroom warmtegener...

Страница 87: ...Drinkwaterwarmtewisselaar pmax tmax bar C 6 95 6 95 6 95 6 95 6 95 Buiswarmtewisselaar onder oppervlak volume m l 0 77 5 1 15 7 5 1 15 7 5 1 88 12 3 1 88 12 4 Buiswarmtewisselaar midden oppervlak vol...

Страница 88: ...C 6 95 6 95 6 95 Buiswarmtewisselaar onder oppervlak volume m l 2 6 17 3 3 21 3 4 5 29 7 Buiswarmtewisselaar boven oppervlak volume m l 2 2 14 2 2 6 17 2 8 18 6 Buiswarmtewisselaar pmax tmax bar C 10...

Страница 89: ...1745 1720 I mm 1348 1439 1254 1745 1720 J mm 1348 1519 1341 1745 1720 K mm 1733 2019 1809 2375 2350 L mm 1648 1989 1774 2375 2350 M mm 1750 2024 1809 2390 2365 N mm 1733 2019 1809 2375 2350 O mm 2112...

Страница 90: ...A A Warmteverlies conform EN 12897 W 23 26 28 31 Bulkcapaciteit 45 C opslag 65 C koud water 10 C zonder naverwarming l 50 68 85 115 Vermogenskengetal NL conform DIN 4708 0 6 0 8 1 1 2 Opslag pmax tmax...

Страница 91: ...U regelgeving nr 812 2013 A A A A A A Warmteverlies conform EN 12897 W 26 29 31 36 41 43 Opslag pmax tmax bar C 3 95 3 95 3 95 3 95 3 95 3 95 Retour warmtegenerator R 1 A mm Vrij beschikbaar R 1 B mm...

Страница 92: ...3 95 3 95 3 95 3 95 Drinkwaterwarmtewisselaar oppervlak volume m l 1 52 6 92 2 1 9 6 2 5 11 2 5 11 5 1 23 5 1 23 Drinkwaterwarmtewisselaar pmax tmax bar C 6 95 6 95 6 95 6 95 6 95 6 95 Extra warmtewis...

Страница 93: ...max bar C 10 95 Buiswarmtewisselaar onder oppervlak volume m l 2 13 Buiswarmtewisselaar pmax tmax bar C 10 130 Retour warmtegenerator Rp 1 A mm 221 Retour buiswarmtewisselaar onder Rp 1 B mm 329 Vrij...

Страница 94: ...lak volume m l 2 6 17 3 3 21 3 4 5 29 7 Buiswarmtewisselaar pmax tmax bar C 10 130 10 130 10 130 Retour warmtegenerator Rp 1 A mm 255 255 312 Retour buiswarmtewisselaar onder Rp 1 B mm 413 363 470 Vri...

Страница 95: ...uiswarmtewisselaar pmax tmax bar C 10 130 10 130 10 130 Vrij beschikbaar R 1 A mm 137 137 137 Sensorhuls 6 mm B mm 227 227 227 Vrij beschikbaar R 1 C mm 317 317 317 Koud wateraansluiting R 1 D mm 531...

Страница 96: ...Voor uw aantekeningen...

Страница 97: ...Voor uw aantekeningen...

Страница 98: ...F r Ihre Notizen Notes Pour vos notes Voor uw aantekeningen...

Страница 99: ...F r Ihre Notizen Notes Pour vos notes Voor uw aantekeningen...

Страница 100: ...0800 6 343292 D Free service number Phone 00 800 63 43 66 24 Fax 00 800 63 43 29 24 GB N gratuits T l 0800 9 19109 Fax 0800 9 15408 FR NL Gratis servicenummers Tel 0800 0 226647 Fax 0800 0 225240 OEG...

Отзывы: