INSTALLATION | Specification
48
www.ochsner.com | 982001-TERRA-M2-M4-EN04.1
14.2 Heat pumps for single phase alternating
current
14.2.1 Data table
TERRA 6 HPLB
TERRA 8 HPLB
TERRA 11 HPLB
TERRA 14 HPLB
INDOOR UNIT:
Hydraulic variant
M2-1/M2-2/M2-3/M2-4 M2-1/M2-2/M2-3/M2-4 M2-1/M2-2/M2-3/M2-4 M2-1/M2-2/M2-3/M2-4
Dimensions HxWxD
[mm]
1286x600x680
1286x600x680
1286x600x680
1286x600x680
Hydraulic connection
DN 32 (1 1/4”) male
DN 32 (1 1/4”) male
DN 32 (1 1/4”) male
DN 32 (1 1/4”) male
Weight
[kg]
200
210
220
230
Casing colour
Tiger white 29/11289/
grey RAL 7016
Tiger white 29/11289/
grey RAL 7016
Tiger white 29/11289/
grey RAL 7016
Tiger white 29/11289/
grey RAL 7016
HEATING MODE PERFORMANCE FIGURES:
Operating point B0/W35
Heating output
[kW]
5,8
7,5
10,3
13,2
Total power consumption
[kW]
1,2
1,55
2,05
2,75
Coefficient of performance
EN 14511/EN 255
4.8/-
4.8/5.0
5.0/5.2
4.8/5.0
Operating current
[A]
5,8
7,5
9,7
13,6
Operating point B0/W50
Heating output
[kW]
5,3
6,8
9,3
12,1
Total power consumption
[kW]
1,7
2,3
3,1
3,9
Coefficient of performance
EN 14511/EN 255
3.1/-
3.0/3.2
3.0/3.2
3.1/3.3
Operating current
[A]
8,2
11,1
14,7
19,3
Operating point S0/W60
Heating output
[kW]
5,0
6,2
8,8
11,8
Total power consumption
[kW]
2,0
2,5
3,7
4,4
Coefficient of performance
EN 14511/EN 255
2.5/-
2.5/2.7
2.4/2.6
2.7/2.9
Operating current
[A]
9,7
12,1
17,5
21,7
SPECIFICATION:
Phases/nominal voltage/frequency [~]/[V]/[Hz]
1/230/50
1/230/50
1/230/50
1/230/50
Output factor cos ϕ
0.90
0.90
0,92
0,88
Fuse protection
C16A
C25A
C25A
C32A
Max. operating current
[A]
12,8
17,1
22,8
27,9
Max. starting current
[A]
30
41,5
54
65
Sound power/sound pressure level
(at 1 m distance)
[dBA]
43 / 35
44 / 36
48 / 40
50 / 42
ELECTRIC BOOSTER HEATER (M4-1, M4-3):
Phases/nominal voltage/frequency [~]/[V]/[Hz]
1/230/50
1/230/50
1/230/50
1/230/50
Max. output
[kW]
8.8 (2.9 / 2.9 / 2.9)
8.8 (2.9 / 2.9 / 2.9)
8.8 (2.9 / 2.9 / 2.9)
8.8 (2.9 / 2.9 / 2.9)
Max. operating current
[A]
38,3
38,3
38,3
38,3
CONDENSER (HEAT SINK SYSTEM):
Type
Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger
Material
Stainless steel 1.4301 Stainless steel 1.4301 Stainless steel 1.4301 Stainless steel 1.4301
Number
[pce]
1
1
1
1
Max. refrigerant operating pres-
sure
[bar]
45
45
45
45
Max. heat transfer medium operat-
ing pressure
[bar]
6
6
6
6
Heat transfer medium temperature
differential
[K]
5
5
5
5
Application range
[°C]
65
65
65
65
Heat transfer medium
Water
Water
Water
Water
Test pressure
[bar]
54
54
54
54
Heat transfer medium flow rate
[m³/h]
1,0
1,29
1,77
2,27
Internal pressure differential
[mbar]
113
264
279
414
Flow meter, heat sink
built-in
built-in
built-in
built-in
Heat sink circulation pump (heat
generator pump)
internal
Yonos Para 25/7.5
Yonos Para 25/7.5
Yonos Para 25/7.5
Yonos Para 25/7.5
Residual head I M4-1
[mbar]
656
496
351
63
REFRIGERANT CIRCUIT:
Содержание TERRA 6
Страница 2: ......
Страница 80: ...80 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity...
Страница 81: ...982001 TERRA M2 M4 EN04 1 www ochsner com 81 INSTALLATION Declaration of conformity...
Страница 82: ...82 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity...
Страница 90: ...90 www ochsner com 982001 TERRA M2 M4 EN04 1...
Страница 91: ...982001 TERRA M2 M4 EN04 1 www ochsner com 91...