Code Fault code
history
Display message
Possible cause and solution
115
Er 01: DHW sensor faulty
Replace sensor
116
Er 10: Outside sensor faulty
Replace sensor
117
Er 14: Mixer sensor faulty
Replace sensor
124
Er 20: TWR sensor faulty
Replace sensor
120
Er 22: TPM or TWR shutdown sensor faulty Replace sensor
136
Er 23: TPV sensor faulty
Replace sensor
118
Er 24: Buffer sensor faulty
Replace sensor
114
Er 29: TWV sensor faulty
Replace sensor
11
11
Er 30: Phase monitor
Check power supply
134
Er 32: THG sensor faulty
Replace sensor
138
Er 33: High pressure sensor faulty
Check sensor
137
Er 34: Low pressure sensor faulty
Check sensor
5
5
Er 36: High pressure
Deficient heat distribution, faulty circulation pump, valve closed or air in the
system, check hydraulics
18
18
Er 37: Low pressure
Lack of source energy, lack of refrigerant, expansion valve, check refrigerant
circuit (by OCHSNER Customer Service)
16
16
Er 38: Hot gas
Expansion valve, lack of refrigerant, target temperature too high, check re-
frigerant circuit (by OCHSNER Customer Service)
10
10
Er 39: Compressor motor protection
Motor overload relay, phase fault/overload, source temperature too high,
check compressor in refrigerant circuit (by OCHSNER Customer Service)
8
8
Er 42: Heat sink frost protection
Deficient heat distribution, faulty circulation pump, valve closed or air in the
system, check buffer charging pump or hydraulics (brine antifreeze level)
Er 46: TSG sensor faulty
Replace sensor
9
9
Er 47: Defrost fault
Too little de-icing energy, evaporator/sensor, check refrigerant circuit (by
OCHSNER Customer Service)
129
129
Er 48: TQE sensor/Evaporator 1 is faulty
Replace sensor
130
130
Er 49: TQA sensor/Evaporator 2 is faulty
Replace sensor
12
12
Er 50: Expansion valve
Check function of electronic expansion valve (by OCHSNER)
1
1
Er 56: Heat source flow rate
Lack of source energy, heat source pump/filter, flow rate at heat source too
low
2
2
Er 57: Heat source frost protection
Lack of source energy, source temperature too low, check heat source,
check heat source pump/filter, clean water filter, submersible pump faulty
3
3
Er 58: Heat source motor protection
Check motor protection, check wiring to motor, motor protection relay, phase
fault/overload, thermal cutout
143
143
Er 59: TWV + TWR sensor break
Check sensor
144
144
Er 60: TQA + TQE sensor break
Check sensor
42
42
Er 71: Bus fault, room remote control
Check eBus wiring
30
30
Er 80: Heat generator 1 address
Check addressing
31
31
Er 81: HG 2 address
Check addressing
32
32
Er 82: HG 3 address
Check addressing
33
33
Er 83: HG 4 address
Check addressing
34
34
Er 84: HG 5 address
Check addressing
35
35
Er 85: HG 6 address
Check addressing
36
36
Er 86: HG 7 address
Check addressing
37
37
Er 87: HG 8 address
Check addressing
20
20
Er 91: Heat sink flow rate
Water pressure too low, circulation pump faulty, valve closed/air in system,
check hydraulics
21
21
Er 90: Overheating
Check refrigerant circuit (by OCHSNER Customer Service)
98
98
Er 98: Auxiliary heat generator running as
only heat generator
Check operation mode of heat pump
104
104
Er104: Sum fault, heat pump
OCHSNER Customer Service
108
108
Er108: Outdoor unit, general
Check wiring
109
109
Er109: Compressor overheating
Automatic acknowledgement
100
100
Er200: Condensation temperature too low
Check refrigerant circuit (by OCHSNER Customer Service)
102
102
Er 202: Evaporation temp. too low
Check refrigerant circuit (by OCHSNER Customer Service)
103
103
Er 203: Evaporation temp. too high
Check refrigerant circuit (by OCHSNER Customer Service)
240
240
Er240: OTE cannot recognise a Modbus
PCB
Check by OCHSNER Customer Service
241
241
Er241: Modbus communication error
Power shutdown? Check the wiring of the Modbus cable between indoor and
outdoor units. Otherwise check by OCHSNER Customer Service
242
242
Er242: CAN bus communication fault
Check wiring of CAN bus cable and Modbus cable (possible consequential
fault of Er 241), otherwise check by OCHSNER Customer Service
Содержание TERRA 6
Страница 2: ......
Страница 80: ...80 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity...
Страница 81: ...982001 TERRA M2 M4 EN04 1 www ochsner com 81 INSTALLATION Declaration of conformity...
Страница 82: ...82 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity...
Страница 90: ...90 www ochsner com 982001 TERRA M2 M4 EN04 1...
Страница 91: ...982001 TERRA M2 M4 EN04 1 www ochsner com 91...