9. Preparing to install the
appliance
Before installing the indoor and outdoor units, preparatory
work needs to be carried out by qualified contractors.
9.1 Indoor unit installation location
Material damage
The indoor unit is intended to be installed only in-
side the building. It must not be installed in rooms
with high levels of humidity (permanently above
70%).
i
Information
Plan the installation sites for the outdoor and indoor
units such that the pipework carrying the refriger-
ant is as short, straight and simple as possible.
The installation location for the indoor unit must meet the
following requirements:
►
A dry and frost-free room
►
Sound optimised environment
►
A horizontal, adequate load bearing floor (for weight
of indoor unit, see „Specification“ on page
►
Not situated directly below or above bedrooms
►
Max. room temperature 30°C
►
The installation room must not be subject to a risk of
explosions arising from dust, gases or vapours.
9.1.1 Keep minimum clearances
Observing the specified minimum clearances for the indoor
unit ensures:
►
Correct installation of the appliance
►
Fault-free operation
►
Ability to carry out maintenance on the appliance.
11_05_200_214_01_001
C
D
B
A
E
A
≥ 1000 mm
B
≥ 500 mm
C
≥ 500 mm
D
≥ 50 mm
E
≥ 500 mm
9.2 Outdoor unit installation location
i
Information
Plan the installation sites for the outdoor and indoor
units such that the pipework carrying the refriger-
ant is as short, straight and simple as possible.
i
Information
When laying refrigerant lines in the ground, sched-
ule the work so that the pipe liner can be laid
together with the already inserted refrigerant lines
in the trench between the outdoor and indoor units.
- If the pipe liner is laid empty, inserting the re-
frigerant lines afterwards will be difficult if not
impossible.
The outdoor unit is intended to be installed only out of
doors. Please note the following with regard to the instal-
lation location of the outdoor unit:
►
Select the outdoor unit installation location such that
the appliance is safely accessible from all sides all
year round.
►
Avoid installing it in a hollow or ditch (a “pool” of cold
air).
►
An optional snow cover is available to protect the
outdoor unit fan in case of heavy snowfall. Where
necessary, ensure that a snow cover is installed
(according to installation site and local weather
conditions).