Ocean Breeze OBZ-09NPH Скачать руководство пользователя страница 22

Note: When one of the above malfunctions occurs, turn off the unit 

and check for any obstructions. Restart the Unit. If the malfunction 

persists, turn off the unit and unplug the power cord. Contact the 

manufacturer or its service agents or a similarly qualified person for 

service.

- Press the "MODE" button until the "COOL" indicator light comes on.

- Press the Up (+) and Down (-) buttons to select your desired room temperature.

  The temperature can be set within a range of 17°C~30°C/62°F~86°F.

- Press the "FAN" button from the remote control to choose the fan speed.

- Press the "MODE" button until the "DRY" indicator light comes on.

- Under this mode, you cannot select a fan speed or adjust the temperature. The fan

  motor operates at LOW speed.

- Keep windows and doors closed for the best dehumidifying effect.

- Do not connect the exhaust hose to a window.

- In cool mode, this unit is made to self-evaporate. This means if you keep the rubber 

  stoppers closed on the back of the unit, the water will evaporate and you will not 

  have to drain.

- In cases of extreme humidity, you may have some water accumulation that the unit

  is unable to evaporate. In this case, the unit will beep 8 times, switch to fan mode, 

and read P1 on the LED display (it will stay like this until the unit is drained). If 

this happens, you should drain the water from the lower drain (located at the 

bottom of the unit).

- This feature can be activated from the remote control ONLY.

- When you set the air conditioner in AUTO mode, it will automatically select cooling or 

  fan only operation depending on what temperature you have selected and the current 

  room temperature.

- The air conditioner will control room temperature automatically according to the 

   temperature point set by you.

- Under AUTO mode, you cannot select the fan speed.

- Press the "MODE" button until the "FAN" indicator light comes on.

- Press the "FAN" button from the remote control to choose the fan speed. The temperature 

  cannot be adjusted.

- Do not connect the exhaust hose to a window.

- In COOL or DRY mode, press the "MODE" button for 3 seconds to turn on or off the 

  constant fan function. When the function is turned on, the constant fan light will illuminate, 

  identifying that the fan will continuously run for cooling.

AUTO operation

Constant Fan operation

see Troubleshooting Tips.

21

Содержание OBZ-09NPH

Страница 1: ...OBZ 09NPH Read this owner s manual thoroughly before operating the appliance and keep it handy for reference at all times WWW OCEANBREEZECOMFORT COM ...

Страница 2: ...t deal of time and money over the life of your air conditioner You ll find many answers to common problems in the troubleshooting tips you should be able to fix most of them quickly before calling service These instructions may not cover every possible condition of use so common sense and attention to safety is required when installing operating and maintaining this product 1 2 3 15 16 20 23 24 ...

Страница 3: ...ontrol lever adjust manually Panel Caster Bottom tray drain outlet Air filter Upper air intake air outlet Lower air intake Drain outlet Design Notice In order to ensure the optimal performance of our products the design specifications of the unit and remote control are subject to change without prior notice 2 ...

Страница 4: ...o combustible gas as this could cause a fire The unit has wheels to facilitate movement Make sure not to use the wheels on thick carpet or to roll over objects as this could cause the unit to fall DO NOT operate the unit that has been dropped or damaged DO NOT allow children to play with the air conditioner Children must be supervised around the unit at all times During a thunderstorm the power mu...

Страница 5: ...not pierce or burn Be aware that the refrigerants may not contain an odor Compliance with national gas regulations shall be observed Keep ventilation openings clear of obstruction The appliance shall be stored so as to prevent mechanical damage from occurring A warning that the appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specified for ope...

Страница 6: ...e Refrigerant R32 is used within air conditioner When maintaining or disposing the air conditioner the refrigerant R32 or R290 shall be recovered properly shall not discharge to air directly No open fire or device like switch which may generate spark arcing shall be around air conditioner to avoid causing ignition of the flammable refrigerant used Please follow the instruction carefully to store o...

Страница 7: ...ide the package will not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations 6 Information on servicing 1 Checks to the area Prior to beginning work on systems containing flammable refrigerants safety checks are necessary to ensure that the risk of ignition is minimised For repair to the refrigerat...

Страница 8: ...ly safe 5 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts appropriate fire extinguishing equipment shall be available on hand Have a dry powder or CO2 fire extinguisher adjacent to the charging area 6 No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work tha...

Страница 9: ...plied to installations using flammable refrigerants The charge size is in accordance with the room size within which the refrigerant containing parts are installed The ventilation machinery and outlets are operating adequately and are not obstructed If an indirect refrigerating circuit is being used the secondary circuit shall be checked for the presence of refrigerant Marking to the equipment con...

Страница 10: ...electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation 2 Particular attention shall be paid to the follo...

Страница 11: ...o wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans 10 Detection of flammable refrigerants Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks A halide torch...

Страница 12: ...system with OFN and continuing to fill until the working pressure is achieved then venting to atmosphere and finally pulling down to a vacuum This process shall be repeated until no refrigerant is within the system When the final OFN charge is used the system shall be vented down to atmospheric pressure to enable work to take place This operation is absolutely vital if brazing operations on the pi...

Страница 13: ...ng the site 14 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its detail It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essen...

Страница 14: ... cylinders are evacuated and if possible cooled before recovery occurs The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants cylinders conform to the appropriate standards d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so tha...

Страница 15: ...rigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant Waste Transfer Note arranged Do not mix refrigerants in recovery units and especially not in cylinders If compressors or compressor oils are to be removed ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant ...

Страница 16: ... or similar coverings Do not route cord under furniture or appliances Arrange the cord away from the traffic area and where it will not be tripped over Never attempt to operate this appliance if it is damaged malfunctioning partially disassembled or has missing or broken parts including a damaged cord or plug To reduce the risk of fire or electric shock do not use this unit with any solid state sp...

Страница 17: ...it as this could cause damage to the unit Note About Fluorinated Gasses This air conditioning unit is a hermetically sealed unit that contains fluorinated gasses For specific information on the type of gas and the amount please refer to the relevant label on the unit itself Service maintenance or repair of this unit must be performed by a certified technician Product uninstallation and recycling m...

Страница 18: ...window sliders use the bolt to fasten the window sliders once they are adjusted to the proper length Press the exhaust hose into the window slider adaptor and the unit adaptor Each adaptor will snap into the exhaust hose automatically with plastic clips Step One Preparing the exhaust hose assembly Medium Phillips screwdriver Suggested Tools Accessories Installation Kit Tape measure or ruler Knife ...

Страница 19: ...ly Insert the window slider assembly on the left or right sides of the sash channel Use care when installing the window slider assembly which will now fit very tightly in the opening Close the sash tightly against the other side of the window slider assembly Foam seal A Long adhesive foam seal for top and bottom sides Foam seal A Long adhesive foam seal for right and left sides Foam seal B Short a...

Страница 20: ... Note This air conditioner exhausts hot air from the back of the unit While operating in cool mode the exhaust hose will become warm to the touch this is normal Having the exhaust hose overextended can cause radiant heat into the room causing ineffective operation The exhaust hose and adaptors must be installed according to the installation instructions so the warm air from the exhaust is vented o...

Страница 21: ...he selected mode Used to adjust increasing decreasing temperature settings in 1 C 1 F increments in a range of 17 C 62 F to 30 C 86 F Up and Down buttons Power button Power switch on off NOTE The control is capable of displaying temperature in degrees Fahrenheit or degrees Celsius To convert from one to the other press and hold the Up and Down buttons at the same time for 3 seconds 20 ...

Страница 22: ...idity you may have some water accumulation that the unit is unable to evaporate In this case the unit will beep 8 times switch to fan mode and read P1 on the LED display it will stay like this until the unit is drained If this happens you should drain the water from the lower drain located at the bottom of the unit This feature can be activated from the remote control ONLY When you set the air con...

Страница 23: ...on manually Do not place any heavy objects or other loads on the louver doing so will cause damage to the unit Keep the louver fully opened during operation Remove the drain plug Continuous drain hose WATER DRAINAGE When the water level of the bottom tray reaches a predetermined level the unit beeps 8 times the digital display area shows P1 At this time the air conditioning dehumidification proces...

Страница 24: ...e lifespan of the unit Air filter take out down the grille Gently wash the air filter using water and or diluted liquid dishwashing detergent Rinse thoroughly and gently shake excess water from the filters Make sure the filters are dry before reinstalling NOTE You may use a vacuum cleaner to remove dust 23 ...

Страница 25: ...hooting Tips Before calling for service review this list It may save you time and expense This list includes common problems that may not be the result of defective workmanship or materials in this appliance 24 ...

Страница 26: ...upper and lower drain plugs to let air get into the unit 4 Put the unit in the FAN mode and run it in this mode for 5 6 hours This will allow the machine to dry out and will hopefully dry out the internal sensors that are throwing the P1 code 5 After you run the machine in the FAN mode for several hours then put the drain plugs back in the top and bottom of the machine and unplug the unit from the...

Страница 27: ......

Страница 28: ......

Отзывы: