8
UNI-STRUT INSTALLATION
USE (4) 5/16-18 x 1” BOLTS AND
WASHERS TO
SECURE UNIT TO UNIT-STRUT
USE (4) 5/16-18 x 1” BOLTS AND
WASHERS TO
SECURE UNIT TO UNIT-STRUT
CAUTION
- When hanging or permanently connecting the CAC, all
applicable local/state/federal building codes must be followed. The structural
beam(s) must be capable of properly supporting the weight of the unit (130 lbs.)
WHEN INSTALLED—UNIT IS TO BE PLUMB AND LEVEL
The CAC may be suspended above a space, or installed
above a drop ceiling. The unit can be hung from a
building’s structural beam by one of three means:
Using 5/16” -18 threaded rods secured into the top of
the unit at the 4 corners. Make sure there is a
minimum of 1/2” thread engagement into panel nuts.
Rods are to be secured to upper structure by means of
washers and nuts.
Using 12 ga. Uni-Strut (P1000 Series or equivalent)
secured to the top of the unit by 5/16-18 bolts
Using 12 ga. Uni-Strut (P1000 Series or equivalent)
secured beneath the unit by 5/16-18 bolts
When hanging or permanently installing the CAC,
remove the unit casters and handles prior to
installation.
INSTALL (4) 5/16-18
THREADED RODS INTO
TOP PANEL OF UNIT
UNI-STRUT
UNI-STRUT
INSTALLATION—HANGING APPLICATION