ACCESSORIES 
 
CONDENSER RETURN AIR PLENUM, 2DCP 

 

Condenser return air plenums are available for installations where it is required to duct air 
to the inlet of the condenser.  The plenum easily attaches with one screw to the back of 
the unit, and is provided with flange(s) for connecting 12-inch flexible ducting.  A conden-
ser return air plenums can substantially reduce air noise and allows the unit to operate 
without drawing condenser air from the conditioned space.  Refer to the table below for 
configuration and application information. 
 

NOTE — When installing the condenser return air plenum with the ceiling panel 
kits, allow for a minimum separation distance of 2 feet between the unit discharge 
duct and the return air duct(s).  It is also recommended to direct the condenser 
discharge air away from the condenser return air ducts. 

Plenum                Duct 
   Kit                    Flange 

2OAC12

 

2OAC18

 

2OAC24

 

2OAC36

 

2OAC60

 

2DCP-1              12-inch 

ü 

 

 

 

 

2DCP-2              12-inch 

 

ü 

ü 

 

 

DCP-5                16-Inch 

 

 

 

ü 

ü 

Maximum Approximate 

Equivalent Feet 

 

25 

50 

50 

50 

100 

Estimated External Stat-

ic Pressure

 

(.20) 

(.25) 

(.25) 

(.25) 

(.50) 

2DCP-1 ,2DCP-2 and DCP-5 

To estimate the “equivalent feet” of condenser duct, add the length of the 
condenser intake duct run and the length of the condenser discharge duct run, 
and add 6 equivalent feet per bend in the duct. Make sure that you do not exceed 
the rated E.S.P. to avoid shut down due to the high pressure cut-out

 

13 

Содержание 20AC series

Страница 1: ...ENGINEERING INSTALLATION AND SERVICE MANUAL 2OAC series Deluxe Portable Air Cooled Spot Cooler Form EISM 2OAC 110114 Rev 1...

Страница 2: ...tallation and operation of the Oceanaire 2OAC spot cooler It is recommend ed to read and fully understand the instructions outlined within this manual before operating the 2OAC unit As with all commer...

Страница 3: ...from the top of the unit The 2OAC models range in cooling capacities from 12 000 BTU HR to 60 000 BTU HR to satisfy most space cooling requirements The 2OAC is a self contained unit with the entire c...

Страница 4: ...2 SPECIFICATIONS 2OAC...

Страница 5: ...speed CONDENSATE RESERVOIR PUMP 2OAC units come equipped with a means for handling the condensate generated during the cooling process All models except the 2OAC60 models come equipped with a Con den...

Страница 6: ...enclosed the condenser hot air exhaust duct directs condenser air out of the area allowing the evaporator air to cool the specific space ROOM AIR CONDITIONER When ducted the OceanAire 2OAC can be used...

Страница 7: ...to the chart below for plug and receptacle details for all 2OAC models A DAMAGED LCDI POWER SUPPLY CORD MUST BE REPLACED WITH A NEW POWER SUPPLY CORD AND NOT REPAIRED UNIT MODEL PLUG CONFIGURATION RE...

Страница 8: ...AN EXTENSION CORD CAN BE USED PROVIDED IT IS RATED AT LEAST 50 AMPS 250 VOLTS WITH GROUNDING TYPE ATTACH MENT PLUG AND GROUNDING TYPE CONNECTOR LOAD FITTING FOR MODELS 2OAC3632 AND 2OAC6032 AN EXTENSI...

Страница 9: ...7...

Страница 10: ...ill continue to run circulating air TANK LEVEL ADJUSTMENT INSTRUCTIONS An adjustment screw is provided to vary the cut off of the tank full switch If a lighter less weight level of water is desired tu...

Страница 11: ...9 CK 12PL CK 16 CK 12 CK 16 2DDA 6 2DDA 10 2DDA 16 2NK 1 2NK 2 2NK 3 DEP 10 2DEP 12 DEP 16 2DCP 1 2DCP 2 DCP 5 2OAC UNIT ACCESSORIES...

Страница 12: ...AC12 2DDA 10 10 Inch Round 2OAC18 24 DDA 16 16 Inch Round 2OAC36 60 CONDENSATE PUMP KIT 2DPC 1 115V Models 2DPC 2 230V Models Not Required for 2OAC60 s CEILING PANEL KIT CK 12 2OAC12 18 24 CK 16 2OAC3...

Страница 13: ...flexible duct Note Drop ceiling spaces should be vented or large enough to handle the warm condenser air Check local codes to assure compliance If longer runs of duct are required table below lists ma...

Страница 14: ...and with edge guards By removing the 2OAC discharge grill one can insert the nozzle kit into the open ing without the use of tools Nozzle Kits Kit Voltage 2DPC 1 115V 2DPC 2 208 230V CONDENSATE PUMP K...

Страница 15: ...r plenum with the ceiling panel kits allow for a minimum separation distance of 2 feet between the unit discharge duct and the return air duct s It is also recommended to direct the condenser discharg...

Страница 16: ...gid to the return air intake to reduce air noise and increase the number of options for solving difficult cooling problems The plenum attaches to the front of the unit replacing the return air grill R...

Страница 17: ...r discharge to a 6 inch diameter round duct 2DDA 10 for 2OAC18 and 2OAC24 converts the evaporator to a 10 inch diameter round duct 2DDA 16 for 2OAC36 and 2OAC60 converts the evaporator discharge to a...

Страница 18: ...ed on the back of the unit to make certain that the proper power is available for the unit Refer to Specifications section for voltage and amperage requirements For proper NEMA receptacles refer to El...

Страница 19: ...COOL The system will operate in cooling mode only MOISTURE CONTROL The system operates in the cooling mode to reduce humidity within the conditioned space Every 4 hours the fan is started circulating...

Страница 20: ...freeze ups P4 Adjust the P4 setting to match the actual INSIDE room temperature if needed P10 Use this parameter to display temperatures in the desired units P13 To cycle the evaporator fan with the c...

Страница 21: ...ours 03 and 486 3486 hours 01 and 59 1059 hours TOTAL HOURS REPRESENTS COMPRESSOR RUN TIME MODEL CODE SETTINGS 2OAC12 P1 85 P2 35 2OAC18 P1 80 P2 50 2OAC24 P1 70 P2 50 2OAC36 P1 85 P2 40 2OAC60 P1 85...

Страница 22: ...left side panel from front Locate the two nuts securing the display to the front panel Unplug the display cable and remove display Install new display and secure Plug in display cable 2 To remove the...

Страница 23: ...PORATOR FAN RUNS BUT COMPRESSOR AND CONDENSER FAN DO NOT START CAUSE SET POINT setting may be too high for cooling or too low for heating REMEDY Make sure set point is adjusted accordingly You should...

Страница 24: ...acing them in a dishwasher or soaking them in a solution of warm water and detergent for 10 minutes Then rinsing them clean with hot water and shaking excess moisture from filter CONDENSATE PUMP Conde...

Страница 25: ...2OAC12 INTERIOR VIEW 23...

Страница 26: ...24...

Страница 27: ...25...

Страница 28: ...26...

Страница 29: ...27...

Страница 30: ...28...

Страница 31: ...29...

Страница 32: ...30...

Страница 33: ...31...

Страница 34: ...d or operated in accordance with the furnished written instructions or has been altered or modified in any way b to any expenses including labor or material incurred during removal or reinstallation o...

Страница 35: ...LLED BY DATE INSTALLED For Technical Support or to locate a distributor for service parts contact Oceanaire at 847 583 0311 or 1 866 GETAIRE 438 2473 Please indicate the Model Number and Serial Number...

Страница 36: ...Form EISM 2OAC 110114 Rev 1...

Отзывы: