ACCESSORIES
DISCHARGE AIR NOZZLE KIT ASSEMBLY (2NK)
The optional discharge nozzle kits are used to direct the condi-
tioned air to a specific target area. By concentrating the airflow,
the nozzles increase the air velocity towards production lines to
cool personnel or equipment. In server rooms, the nozzles can be
used to induce airflow through the rack to remove the hot air from
the area of the equipment.
2NK-1 for model 2OAC12
, w ith (2) 4-inch diameter nozzles with
an approximate compressed length of 15 inches. The approximate
extended length is 21 inches.
2NK-2 for models 2OAC18 and 2OAC24
w ith (2) 6-inch diame-
ter nozzles with an approximate compressed length of 22 inches.
The approximate extended length is 32 inches.
2NK-3 for 2OAC36 and 2OAC60
, w ith (2) 8-inch diameter noz-
zles with an approximate compressed length of 20 inches. The
extended length is approximately 29 inches.
The nozzle kits come pre-assembles with the nozzles secured to a
mounting plate, and with edge guards. By removing the
2OAC discharge grill, one can insert the nozzle kit into the open-
ing without the use of tools.
Nozzle Kits
Kit Voltage
2DPC-1 115V
2DPC-2 208-230V
CONDENSATE PUMP KIT: 2DPC-1 and 2DPC-2
A plug-in condensate pump kit is available for applications where emptying the 5 gallon
condensate tank is not desired. The pump kit consists of a condensate pump with mount-
ing hardware and electrical connections, along with the tubing required for the drain and
discharge of the condensate water.
PARTS LIST
(1) Condensate Pump with mounting hardware
(1) 3/8-inch drain hose, 25 ft
(2) Mounting screws
(1) Drain hose — black corrugated
(2) Hose clamps
Pump Kit
The condensate pump provides for the
automatic removal of condensate water
during the cooling process. The pump is
capable of pumping against a 20 foot head,
allowing for the routing of the drain line
above the drop-ceiling to a nearby drain.
The pump is controlled by an internal float-
switch which turns the pump on and off
automatically. The pump is also equipped
with a condensate over-flow safety switch,
that will shut down the 2OAC compressor
when the pump is not working properly.
12
Содержание 20AC series
Страница 4: ...2 SPECIFICATIONS 2OAC...
Страница 9: ...7...
Страница 25: ...2OAC12 INTERIOR VIEW 23...
Страница 26: ...24...
Страница 27: ...25...
Страница 28: ...26...
Страница 29: ...27...
Страница 30: ...28...
Страница 31: ...29...
Страница 32: ...30...
Страница 33: ...31...
Страница 36: ...Form EISM 2OAC 110114 Rev 1...