11 | EN
SLM50 suspended vertical ladders for the maintenance of electrical function
Mounting vertical ladders up to a max storey height of 3 5 m
6 2
Mounting vertical ladders up to a max storey height of 3 5 m
Function loss in the event of fire!
At a storey height > 3.5 m, perfect functioning of the vertical ladder can-
not be guaranteed in the event of fire. Only use mounting variants at a
storey height of maximum 3.5 m.
6 2 1
Mounting the ladder rails with head plates
Fig 3:
a
Drawing on the drill holes
Note!
Distance “a” is dependent on the width of the vertical ladder used. a =
vertical ladder width – 50 mm.
1. Draw on two drill holes at spacing “a” behind the ceiling opening.
Maintain the minimum edge spacing according to the approval of the
anchor used.
2. Using a linear laser, transfer the position of the drill holes to the floor.
3. Pre-drill the drill holes. Ø according to anchor type and approval.
Fig 4:
Mounting head plates
4. Mount head plates with the open sides facing each other, using one
M12 anchor for the ceiling and one for the floor.
WARNING