3.3 Protecting the floor

•  any combustible floor beneath a fireplace must have a floor protector that extends 300mm beyond the 

diameter of the firebox in all directions. 

•  if installed directly on combustible material, the floor protector must be made of a minimum 6mm  

thick cement sheet. non-combustible finishes can be applied to the floor protector (tiles, steel sheet,  
light concrete, etc).

•  if the combustible floor is installed on concrete, you can replace the combustible material with non-

combustible material laid directly onto the concrete. 

Joist

Insulative board (6mm)

+ non combustible finish

Non combustible finish

(eg.tiles)

Concrete

Floor protector

Combustible 
floor (eg. timber)

Joist

Insulative board (6mm)

+ non combustible finish

Combustible 
floor (eg. timber)

Combustible 
floor (eg. timber)

140mm

140mm

80mm

80mm

1200mm

1180mm

Combustible floor
(eg: Timber)

Cement Sheet 6mm thickness

floor Protector laId on tImber floor

3. InStallatIon 

(contInued)

Joist

Insulative board (6mm)

+ non combustible finish

Non combustible finish

(eg.tiles)

Concrete

Floor protector

Combustible 
floor (eg. timber)

Joist

Insulative board (6mm)

+ non combustible finish

Combustible 
floor (eg. timber)

Combustible 
floor (eg. timber)

140mm

140mm

80mm

80mm

1200mm

1180mm

Combustible floor
(eg: Timber)

Cement Sheet 6mm thickness

floor Protector laId on JoISt

Содержание Skantherm Turn

Страница 1: ...Skantherm Turn Installation and User Manual 1 Technical Data 2 2 PRE Installation 3 3 Installation 5 4 Operation 9 5 TestING 10 Keep for future use Oblica 200 Argyle St Fitzroy VIC 3065 03 9416 0400...

Страница 2: ...and User Manual 1 Technical Data Determined under test conditions Nominal thermal output 5kW Efficiency 78 4 Weight and dimensions Dimensions W1150 x H852 x D382mm Firebox weight 213kg Flue kit Stand...

Страница 3: ...flue and engage the firebox Ensure the floor has adequate protection Caution Using components or parts other than those provided by the manufacturer or modifying the specification of components may re...

Страница 4: ...eat shielding please contact our office on 03 9416 0400 or email info oblica com au IMPORTANT Frames must also be considered Timber window frames must be treated as combustible surfaces see 2 3 Alumin...

Страница 5: ...3 1 Typical flue kit installation Cowl Chinaman Hat 8 Outer Case 10 Outer Case 8 Outer Case Crimped end up on dec outer case 8 Outer decorative casing 8 Outer decorative casing FIREBOX 10 Outer Case 6...

Страница 6: ...stalled as per Australian standards see diagrams below The top of the flue must be 400mm higher than the highest point of the roof Alternatively there must be a minimum distance of 8 meters from any h...

Страница 7: ...is installed on concrete you can replace the combustible material with non combustible material laid directly onto the concrete Joist Insulative board 6mm non combustible finish Concrete Combustible...

Страница 8: ...le finish Combustible floor eg timber 140mm 80mm 80mm 1200mm 1180mm Combustible floor eg Timber Cement S mm inish Non combustible finish eg tiles Concrete Floor protector mm inish Combustible floor eg...

Страница 9: ...s to start or rekindle the fire Do not use flammable liquids or aerosols in the vicinity of the fireplace when operating Do not store fuel within prescribed installation clearance distances The use of...

Страница 10: ...determination of Power Output and Efficiency and AS NZS 4013 1999 for Flue Gas Emission using hardwood fuel Test Dates 29 10 2013 to 18 11 2013 INVESTIGATING OFFICERS Christian Schmidt Rebecca Searcy...

Отзывы: