4. INSTALLATION SAFETY
In order to reach the level of safety required by current regulations, read the following prescriptions carefully.
1) Make all the connections in the terminal block after carefully reading the instructions given in this manual and observing the general
rules and technical standards governing electrical systems.
2) Upstream from the installation,
fi
t an omnipole miniature circuit breaker with a contact gap of at least 3 mm.
3) If there isn’t one already, install a residual current device with a threshold of 30 mA.
4) Check the effectiveness of the grounding system and connect to it all the parts of the automation
fi
tted with a terminal or grounding
cable.
5) Fit at least one external warning device, such as a traf
fi
c light or
fl
ashing light, along with a warning or danger sign.
6) Fit all the safety devices required by the type of installation, taking into consideration the risks it can cause.
7) Separate the power lines (min. sect. 1.5 mm
2
) from the low-voltage signal lines (min. sect. 0,5 mm
2
) in the ducts.
LINE
230V
230V 50/60Hz power supply with mov internal protection and 6,3A fuse (5x20).
Connect the phase and neutral as shown on the screen printing. Use a cable type H07RN-F 2x1.5+E min.
Connect the yellow/green wire of the power supply mains to the earth terminal of the appliance.
5. INPUT AND OUTPUT FUNCTIONALITY AND CONNECTIONS
OUT24
Output 24Vac, 1A MAX
OUT1
(bar lights)
Self-powered triac output. 24Vac, 100mA max
OUT2
Programmable volt-free relay output, max. 500mA 24 Vac/dc (parameter
- level 2)
OUT3
Programmable volt-free relay output, max. 500mA 24 Vac/dc (parameter
- level 2)
OUT4
Programmable volt-free relay output, max. 500mA 24 Vac/dc (parameter
- level 2)
2nd CH RX
N.O. output of the 2nd radio receiver channel, integrated and plugged in
5.3
J4
OUTPUTS/ACCESSORIES TERMINAL BLOCK
5.1
J1
POWER TERMINAL BLOCK
5.2
J2
POWER TERMINAL BLOCK
L N E
= FLASHING LIGHT:
230Vac; 40W max.
OUT2
OUT2
OUT3
OUT3
OUT4
OUT4
2nd
CH
RX
24 V
ac
OUT1
24 Vac
Active only in the
CSB-BR
NOT ACTIVE