Current terminal /
N terminal
Voltage terminals
Auxiliary
terminals
up to 65 A up to 5 A up to 65 A up to 5 A
up to 65 A up to 5 A
Terminal
dimensions
W x H (d) mm
6.9 x 7.9
3.3 x 3.0
2.7 x 3.0
2.7 x 3.0
d = 2.5
d = 2.5
Maximum
connection
diameters (mm
2
)
16
4
2.5
2.5
2.5
2.5
Maximum torques
for connection
terminals (Nm)
3.0
0.5
0.5
0.5
0.8 0.8
Table 1: Terminal dimensions, connection diameters, and torques
Note
During installation of the meter, tighten the connecting wires to the correct torque
according to EN 60999 to ensure a reliable contact. The torque depends on the type of
connecting wire and the maximum current.
To prevent damage to the meter, do not exceed the maximum permissible torque
for the connecting terminal.
2.2.1 Connection examples
Below you will find several examples of wiring diagrams. When connecting a meter,
always comply with the corresponding wiring diagram, which you will find in the terminal
cover of the meter.
Important: The neutral wire terminals 10/11 and 12 are located on the left.
2-wire model, connected directly
3-wire model, connected to current and voltage transformer
8