nVent.com|3

Power Supply

Thepowersupplyconnector(TB19)isa

dualtwopinconnector.Eitherconnector

allowsforpowerin(pin#1(+),pin#2(–)

andbussingofpowertootherNGC-30-CRM

modules).

Note:

Powersupplymustbesizedcorrectly

basedonthenumberofNGC-30-CRM/-

CRMSmodules.

RS-485 Communications

ThenVentRAYCHEMRS-485connector

(TB6)isadualthreepinconnector.Either

connectorallowsforRS-485inputsignals

(pin#1(shield),pin#2(+),pin#3(–))and

bussingofRS485signaltootherNGC-30-

CRMmodules.

End of Line (EOL) Jumper

Ifthisdevice(NGC-30-CRM/-CRMS)isthe

lastdeviceintheRS-485network,theJ1

jumperneedstobemovedfromterminals2

&3toterminals1&2.

RTD Inputs  – Ordinary Area

1 2 3 4

per each NGC-30-CRM board

3wirenVentRAYCHEMRTDswithshield

maybeconnectedtoRTDCh1thruCh5

(TB1-TB5).Thetwocommonwires(usually

red,red)areconnectedtoterminals2&3,

thesource(usuallywhite)toterminal1and

thebraidtoterminal4(earthground).

Note: 

RTD'sarenotrequiredifmonitoring

current/ground-faultsonlyorifRTD'sare

connectedviaRMM2s.

RTD Inputs  – Hazardous Area

11

22

33

44

Factory wired

Factory wired

Terminal

block

Terminal

block

Hazar

dous ar

ea

Hazar

dous ar

ea

RTD

RTD

NGC-30-CRM/CRMS Board

NGC-30-CRM/CRMS Board

ForallRTDterminationsina

hazardousarea,theRTDfield

wiresmustbeterminatedona

panel-mountedterminalblock.

Relay Output Connections to 111 

Contactors or Solid State Devices (TB7)

Thisconnectorswitchesvoltagetothe

contactorcoilsorsolidstaterelays.Thepilot

relaywillswitchthesupplyvoltage(upto

277Vac)tothecontactorcoil(usinganNGC-

30-CRM)or12Vdctothesolidstatedevice

(usinganNGC-30-CRMS).
Refertosystemlayoutdiagramfordetail

wiring.

Common Alarm

Thecommonalarmterminalblock(TB12)

providesaformCdrycontact,ratedat277

Vacmax(3A).
WhentheRAYCHEMNGC-30systemis

poweredon,thecommonalarmrelaycoil

isenergizedandpin2isconnectedtopin1

(common).Thisisthe"NoAlarm"condition

fortheCRM/CRMSboard.
Ifthealarmoccurs,ortheCRM/CRMSboard

losespower,therelaycoilisde-energizedandpin1(common)

isdisconnectedfrompin2andconnectedtopin3toindicatean

alarmconditionexits.

Address Switches (SW1 & SW2)

EachNGC-30-CRM/-CRMSmusthavea

uniquecommunicationaddressselected.

Thevalidaddressswitchrangewhenusing

theNGC-UITis1-99.SW1istheonesdigit

(0–9)andSW2isthetensdigit(0or9).

Note:

WhenaddinganNGC-30-CRM/-

CRMStothesystem,youmustfirstcycle

powerontheCRM/CRMSboardandthen

performanetworkupdateattheNGC-UIT.

Optional Voltage Sensor Cable Preparation

Notes:

1. Cutoneendoffofaground-

fault/linecurrentcable.

2. Stripinsulationapprox.1

inchfromcutend.

3. Striptheredandblackwire

insulationapprox.0.20in.

4. Connectredandblackwire

tothetwopositionterminal

plug.Noneedtobe

concernedaboutpolarity.

5. Trimbrownandorangewiresfromcutend.

Optional Voltage Sensor

Theoptionalvoltagesensor

canmonitor80–290Vac.This

voltageconnectstooneofthe

fivelinecurrent/ground-fault

inputsontheNGC-30-CRM.

Note:

Byusingtheoptional

voltagesensor,youlosethe

abilitytomonitortheground-

faultandcurrentforthatcircuit.

1

2 1 2

1 2 3

1 2 3

Normal

position

End of Line

position

3

2

1

3

2

1

11

22
33

44

RTD1

RTD1

Shield

Shield

RTD connected directly to CRM board

RTD connected directly to CRM board

RTD

RTD

11

22
33

44

RTD2

RTD2

Shield

Shield

RTD

RTD

11

22
33

44

RTD3

RTD3

Shield

Shield

RTD

RTD

11

22
33

44

RTD4

RTD4

Shield

Shield

RTD

RTD

11

22
33

44

RTD5

RTD5

Shield

Shield

Chassis Ground

Chassis Ground

CRM

PCB

CRM

PCB

RTD

RTD

12-RLY4

6-RLY5

10-RLY3

8-RLY2

1 2 3 4 5 6

7 8 9 10 11 12

3-RLY1

1-COM

3

2

1

Open

Closed

CO

M

LSB

MSB

SW1

SW2

3

8

Relay “No Alarm”

Condition

1 in

0.2 in

Red and

black wires

Brown and

orange wires

Содержание Raychem NGC-30-CR

Страница 1: ...g temperature 40 F to 140 F 40 C to 60 C Ambient storage temperature 40 F to 167 F 40 C to 75 C Environment PD2 CAT III Max altitude 2000 m Humidity 0 90 non condensing Electromagnetic Compatibility I...

Страница 2: ...card rack is installed a earth bonding wire green 18 AWG min terminated with a 10 Ring terminal must be connected to the card rack using the ground screw provided Note The card rack must be installed...

Страница 3: ...Vac max 3A When the RAYCHEM NGC 30 system is powered on the common alarm relay coil is energized and pin 2 is connected to pin 1 common This is the No Alarm condition for the CRM CRMS board If the ala...

Страница 4: ...248 mm Ground Fault Line Current Cable Assembly Note A complete cable may be ordered as part number 20578010 XXX where XXX Length L in inches Each NGC 30 CTM mounts on a DIN 35 rail It should be loca...

Страница 5: ...r junction box Alarm relay output 120Vac contctor power L N NGC 30 CRM NGC 30 CTM System Layout NGC 30 CRM 12 Vdc Power Supply RTDs 120 Vac in NGC UIT Touch Screen 5 4 3 2 6 12 10 8 3 C C C C C C C C...

Страница 6: ...r Supply NGC 30 CRMS NGC 30 CTM System Layout NGC 30 CRMS 120 V ac in SSR SSR SSR SSR SSR SSR SSR SSR SSR SSR SSR AC voltage up to 277 Vac Alarm relay output Internal 12 Vdc SSR power 6 5 12 10 8 3 1...

Страница 7: ...7 00 in 9 75 in 0 625 in 2 4 in 0 188 in x4 Top of Card Rack NGC 30 CR Wall mounted hole template Note Ensure the printed template has scaled correctly...

Страница 8: ...ance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection aga...

Отзывы: