background image

NGC-30-CR   -CRM   -CRMS  -CTM   -CVM

ControlandMonitoringModulesforUsewiththenVent

RAYCHEMNGC-30InstallationInstructions

DESCRIPTION

ThenVentRAYCHEMNGC-30-CRM/-CRMSandNGC-30-

CTMprovideground-faultandlinecurrentsensing,alarming,

switchingandRTDinputsforfiveheat-tracingcircuitswhen

usedwiththeNGC-UIT.TheNGC-30-CRMisusedtocontrol

ElectromechanicalRelays(EMRs)andtheNGC-30-CRMSisused

tocontrolSolidStateRelays(SSRs).

TOOLS REQUIRED

• Wirecutters
• RJ11stripping/crimpingtool

• RJ11connectors
• Screwdriversmallblade-

standard

ADDITIONAL MATERIALS REQUIRED

• Powersupply-12Vdc@400mA-perNGC-30-CRM/-CRMSboard
• RJ114conductorcable

KIT CONTENTS

Item Qty Description

A

1

NGC-30-CRMorCRMS(cardrackmodulewithconnectors)

B

1

NGC-30-CTM(currenttransformermodule)

C

1

NGC-30-CR(cardrack)

D

1

NGC-30-CVM(voltagemonitoringmodule)-optional

APPROVALS/CERTIFICATIONS

Class I, Div. 2, Groups A,B,C,D

Ex nC IIC T5

Class I, Zone 2, AEx nC IIC T5 

Hazardous Locations

C

A

B

D

General

SupplyVoltage

12Vdc±10%

Internalpowerconsumption

<5WperNGC-30-CRM/-CRMS

Ambientoperatingtemperature –40ºFto140ºF(–40ºCto60ºC)
Ambientstoragetemperature

–40ºFto167ºF(–40ºCto75ºC)

Environment

PD2,CATIII

Max.altitude

2000m

Humidity

0–90%non-condensing

Electromagnetic Compatibility

Immunity

HeavyIndustrial

Emission

IndustrialEnvironment

Temperature Sensors

Type

100-ohmplatinumRTD,3-wire,

α

=0.00385ohms/ohm/ºC

Canbeextendedwitha3-conductor

shieldedcableof20ohmmaximumper

conductor

Quantity

Uptofivewireddirectlytoeach

NGC-30-CRM/-CRMS

Current Sensors

Mounting

DinRail–35mm

QuantityperNGC-30-CTM

Fiveforground-currentmeasurement

Fiveforlinecurrentmeasurement

Line Current Sensors

Maxcurrent

60A

Accuracy

±2%ofreading

Ground Fault Sensor

Range

10–200mA

Accuracy

±4%ofrangeat30Alinecurrent

Voltage Sensor

Range

80–290Vac50/60Hz

Accuracy

±1%ofspan

Outputs

CRMoutputrelays

FormA3-Amp@277Vacmax50/60Hz

CRMSSSRoutputs

12Vdc@30mAmaxperoutput

AlarmRelay

FormC3-Amp@277Vacmax50/60Hz

Communication to NGC-UIT

Type

2wireRS-485

Cable

Oneshieldedtwistedpair

Length

4000ft.(1200M)maximum

Quantity

Upto52*NGC-30-CRM/-CRMSmay

beconnectedtooneNGC-UIT

Connection Terminals 

Powersupply/PilotRelay/

18–12AWG(0.8-3.3mm

2

)

RTD/CommPort(RS485)
*MayrequireanRS-485repeaterifcommunicationlengthisgreaterthan4000ft.

Содержание Raychem NGC-30-CR

Страница 1: ...g temperature 40 F to 140 F 40 C to 60 C Ambient storage temperature 40 F to 167 F 40 C to 75 C Environment PD2 CAT III Max altitude 2000 m Humidity 0 90 non condensing Electromagnetic Compatibility I...

Страница 2: ...card rack is installed a earth bonding wire green 18 AWG min terminated with a 10 Ring terminal must be connected to the card rack using the ground screw provided Note The card rack must be installed...

Страница 3: ...Vac max 3A When the RAYCHEM NGC 30 system is powered on the common alarm relay coil is energized and pin 2 is connected to pin 1 common This is the No Alarm condition for the CRM CRMS board If the ala...

Страница 4: ...248 mm Ground Fault Line Current Cable Assembly Note A complete cable may be ordered as part number 20578010 XXX where XXX Length L in inches Each NGC 30 CTM mounts on a DIN 35 rail It should be loca...

Страница 5: ...r junction box Alarm relay output 120Vac contctor power L N NGC 30 CRM NGC 30 CTM System Layout NGC 30 CRM 12 Vdc Power Supply RTDs 120 Vac in NGC UIT Touch Screen 5 4 3 2 6 12 10 8 3 C C C C C C C C...

Страница 6: ...r Supply NGC 30 CRMS NGC 30 CTM System Layout NGC 30 CRMS 120 V ac in SSR SSR SSR SSR SSR SSR SSR SSR SSR SSR SSR AC voltage up to 277 Vac Alarm relay output Internal 12 Vdc SSR power 6 5 12 10 8 3 1...

Страница 7: ...7 00 in 9 75 in 0 625 in 2 4 in 0 188 in x4 Top of Card Rack NGC 30 CR Wall mounted hole template Note Ensure the printed template has scaled correctly...

Страница 8: ...ance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection aga...

Отзывы: