End Seal Installation for HWAT Heating Cables
1"
• Score down and around outer jacket 1 inch from the end.
• Remove the outer jacket.
• Do not cut or damage inner jacket.
• Using wire cutters, cut away aluminum wrap close to
braid and outer jacket.
• Remove exposed braid.
• Push end seal completely onto heating cable.
• Wipe off excess gel that may ooze out after you insert the
heating cable.
Note: The end seal can be installed only once; it cannot be
removed from the heating cable.
1
2
3
4
5
6
0