background image

nVent.com/ERICO 

|

 5

Installation and Operating Instructions

A number of different power distribution systems are employed 
in various countries around the world. It is important to 
identify the distribution system in use prior to installation of 
the SRF, and confirm that the SRF is the model recommended 
by the manufacturer for that distribution system. To identify 
the distribution system in use, consult reputable and 
knowledgeable sources such as:
•  The local power supply authority
•  Local electrical engineers
•  Applicable regulatory bodies or standards associations 

Alternatively, confirm the type of distribution system used by 
personal inspection. By visually tracing the neutral and earthing 
conductors from the load equipment or sub-distribution 
point back to the point of entry (and perhaps to the supply 
transformer), the type of distribution system should be 
identifiable with the aid of the following diagrams (figures 2-6).
These are prescribed in local regulations and describe the 
relationship between the source, exposed or conductive parts 
of the installation and earth. Amongst these, the TN-C, TN-S, 
TN-C-S and TT systems are most commonly encountered. 
Note that supplies such as those used in industry and mining 
may often use a different distribution system to that of the local 
supply authority.

4 IDENTIFY THE DISTRIBUTION SYSTEM

Regulations differ between countries. Check compliance with appropiate authorities

Figure 2. TN-C system: In this system, the neutral and protective earth conductor combine in a single conductor 

throughout. All exposed conductive parts are connected to the PEN conductor.

Содержание ERICO 5RF363N

Страница 1: ...nVent com ERICO 1 SRF N Series Surge Reduction Filters Installation and Operating Instructions...

Страница 2: ...RODUCTION 3 2 WARNING 3 3 INSTALLATION CAUTIONS 4 4 IDENTIFY THE DISTRIBUTION SYSTEM 5 5 MOUNTING THE SRF 8 6 OPTIMISING PERFORMANCE 9 7 SERVICING AND TROUBLESHOOTING 16 8 BACKPLANE MODELS 18 9 SCHEMA...

Страница 3: ...US VOLTAGES EXIST WITHIN THE SRF ENCLOSURE THIS UNIT SHOULD BE INSTALLED SERVICED ONLY BY QUALIFIED PERSONNEL AND IN ACCORDANCE WITH RELEVANT NATIONAL ELECTRICAL SAFETY CODES ALL INSTRUCTIONS MUST BE...

Страница 4: ...oltages causing problems such as excessive heat build up Because the harmonic waveforms contain higher order frequencies capacitive leakage currents may increase to above prescribed limits and shorten...

Страница 5: ...from the load equipment or sub distribution point back to the point of entry and perhaps to the supply transformer the type of distribution system should be identifiable with the aid of the following...

Страница 6: ...o this PE conductor Figure 4 TN C S system In this system a separate neutral and protective earth functions combine in a single PEN conductor This system is also known as a Multiple Earthed MEN system...

Страница 7: ...om country to country it is important to ensure that the installation complies with all regulations applicable to the location Please seek further assistance if uncertain Regulations differ between co...

Страница 8: ...abling and upstream over current protection requirements and all instructions provided in this manual should be taken into consideration before mounting the SRF To preserve the IP rating SRF units fro...

Страница 9: ...on the external side surface of the enclosure The cabling and earth wires connected to the filter input should always be run separately with a minimum clearance of 300mm between them and all other cab...

Страница 10: ...lock 25 to 120 mm2 19 N m Backplane Stud 1 x M8 8 5 N m 500A Stud Terminal Block 1 x M10 30 N m Backplane Stud 1 x M10 17 N m 800A Stud Terminal Block 2 x M10 30 N m Backplane Stud 1 x M10 17 N m SING...

Страница 11: ...nVent com ERICO 11 SRF163N SRF3500N 2X CABLE TIE HOLES ON BACK PLANE TO FASTEN EARTH CABLE IN POSITION OUTPUT INPUT 6 2 CABLING Figure 9 Typical earth cabling Installation and Operating Instructions...

Страница 12: ...one A similar scenario exists where the output of the SRF is fed to an electrically noisy load Any transients developed by this load may also be fed to other equipment connected to the same supply Ele...

Страница 13: ...by the earthing system to which it is connected A low impedance route to the earth is required less than 10 This can be achieved by ensuring that the earth electrode system at the site presents a low...

Страница 14: ...away from the input circuit and any other current carrying conductors Alarm contact ratings 5A 250VAC 54 30 VDC 4kV Isolation See section 7 Servicing and Trouble Shooting for further information Unde...

Страница 15: ...provide a separate earth electrode for the SRF subject to compliance with relevant wiring regulations particularly where the filter is to be installed on a sub circuit some distance from the existing...

Страница 16: ...fuse should be obtained from nVent as soon as possible Note that the N E Spark Gap does not have an LED SECONDARY UNITS The Secondary Units are blue in colour and contain the secondary shunt diverter...

Страница 17: ...UNIT PHASE 1 SRFSUAC UNIT SRF3500N SECONDARY UNIT FUSES N E SPARK GAP PHASE 1 SPARK GAP SECONDARY UNIT FUSE SRF163N GREEN STATUS INDICATING LED DIVERTER MODULE STATUS INDICATING FLAG ALARM CONTACTS O...

Страница 18: ...model number These units are supplied without the proprietary enclosure and are intended to be mounted in a customer s provided switchboard SINGLE PHASE SRF MODELS FUSE SECONDARY UNIT SG PRIMARY DIVE...

Страница 19: ...the top surface and the outputs on the bottom surface See Section 6 2 Cabling SRF Model Enclosure Size mm Mounting mm W H D X1 X2 Y1 Y2 Fastener Diameter Weight Kg SRF163N 400 300 200 360 470 260 370...

Страница 20: ...ctive Lightning Protection System nVent ERICO SYSTEM 2000 Conventional Lightning Protection System 6 Protect Low Voltage Data Telecommunications Circuits 1 4 2 5 3 6 Capture the Lightning Strike Prote...

Отзывы: