background image

16 

|

  nVent.com/ERICO

7 SERVICING AND TROUBLESHOOTING

HAZARDOUS VOLTAGES EXIST WITHIN THE SRF ENCLOSURE. 
THE SRF SHOULD ONLY BE SERVICED BY QUALIFIED 
PERSONNEL, IN ACCORDANCE WITH RELEVANT NATIONAL 
ELECTRICAL & SAFETY CODES.

Do not disconnect upstream earth or neutral connections 
supplying the SRF while power is applied to the unit, as this  
may damage the SRF or load.
Only replace the primary spark gaps or secondary TDS surge 
diverters with an identical type.
Voltage-free alarm contacts are activated should the secondary 
protection status fall below a pre-determined level.
The SRFs are essentially maintenance free, although periodic 
inspection is recommended to ensure that the ventilation 
louvres (where fitted) do not become clogged with dust.

INITIAL POWER CHECK 

All indicators, alarms and surge counters (where fitted) should 
be checked on a regular basis. 
Should any of the display indicators fail to illuminate, check for 
the following conditions:
•  Is power available to the SRF?
•  Check the input voltage by measuring the voltage between 

active and neutral

•  Has the upstream circuit breaker or fuse tripped?

INDICATORS 

If power is being supplied to the SRF and the indicators still 
fail to all correctly illuminate, then it is possible that either the 
primary Spark Gap or secondary TDS devices have exhausted 
their surge capacity. In such circumstances, the particular 
devices should be replaced as a matter of urgency as they are 
no longer providing optimum protection.

PRIMARY SPARK GAPS

With power correctly supplied, the Phase Spark Gaps should have 
their green LEDs illuminated. Note that in the 250A to 800A SRFs, 
these Spark Gaps are supplied via Spark Gap Fuses. If power is 
correctly applied, and a Phase Spark Gap does not have its LED 
illuminated, check the adjacent fuse. If the fuse has operated 

(blown) it needs to be replaced. If the fuse is still in good order, the 
Spark Gap needs to be replaced. Blown fuses may be temporarily 
replaced with a 125A 22mm x 58mm gG Fuse. Note that this fuse 
will not allow the full rated surge current to be diverted by the 
associated Spark Gap. The correct replacement fuse should be 
obtained from nVent as soon as possible.
Note that the N-E Spark Gap does not have an LED.

SECONDARY UNITS

The Secondary Units are blue in colour and contain the 
secondary shunt diverter module and the filter capacitance  

(see Figure yy). They are fed from individual 20A fuses. The 
Phase 1 Secondary Unit is fitted with the Alarm Contacts, and it 
is marked as SRFSUAC. On three phase units, the Phase 2 and 
Phase 3 Secondary Units are marked as SRFSU. The status of 
each SRFSUAC and SRFSU unit is indicated by the green LED 
included on each. A correctly powered and operating SRF will 
have all Secondary Unit LEDs illuminated green.
A Secondary Unit LED that is not illuminated indicates one of  
the following:
•  A blown Secondary Unit Fuse (replace Fuse)
•  A failed Diverter Module (replace Module)
•  An SRFSU or SRFSUAC internal failure (replace SRFSU or 

SRFSUAC unit)

Troubleshooting proceeds in the order indicated here:
1) Check fuses for continuity, and replace blown fuses with 20A 
10mm x 38mm gG fuses.
2) Check Diverter Module indicator flags. These should appear 
as the textured window, with a faint grey/red tinge. Any window 
showing a bright red colour should be replaced. Modules may  
be gripped with the fingers and pulled straight out, away from 
the Secondary Unit. Replace with an identical module obtained 
from nVent.
3) Where all fuses and modules have been checked as OK,  
then the affected Secondary Unit itself needs replacing  

(ie the SRFSUAC or SRFSU unit).

Phase 1 

SRFSUAC 

LED Status

Phase 2 

SRFSU LED 

status

Phase 3 

SRFSU LED 

Status

 Diagnosis

Green

Green

Green

All OK

Extinguished Green

Green

Replace Phase 1 

SRFSUAC unit

Extinguished Extinguished Green

Replace Phase 2* 

SRFSU unit

Extinguished Green

Extinguished Replace Phase 3* 

SRFSU unit

*It is possible that both the Phase 1 SRFSU and Phase 2  

(or 3) SRFSU units are faulty in this circumstance, but the  
above diagnosis is more likely.
Obtain the correct model Secondary Unit (SRFSUAC or SRFSU) 
from nVent and wire in to replace the faulty unit. Exercise care 
when replacing the wiring to ensure the resulting wiring is 
correct. It may be useful to take a photograph before removing 
the faulty unit.

FRONT DOOR LED INDICATOR

This indicator will be illuminated green if all Secondary Units  
are indicating correctly.

Installation and Operating Instructions

Содержание ERICO 5RF363N

Страница 1: ...nVent com ERICO 1 SRF N Series Surge Reduction Filters Installation and Operating Instructions...

Страница 2: ...RODUCTION 3 2 WARNING 3 3 INSTALLATION CAUTIONS 4 4 IDENTIFY THE DISTRIBUTION SYSTEM 5 5 MOUNTING THE SRF 8 6 OPTIMISING PERFORMANCE 9 7 SERVICING AND TROUBLESHOOTING 16 8 BACKPLANE MODELS 18 9 SCHEMA...

Страница 3: ...US VOLTAGES EXIST WITHIN THE SRF ENCLOSURE THIS UNIT SHOULD BE INSTALLED SERVICED ONLY BY QUALIFIED PERSONNEL AND IN ACCORDANCE WITH RELEVANT NATIONAL ELECTRICAL SAFETY CODES ALL INSTRUCTIONS MUST BE...

Страница 4: ...oltages causing problems such as excessive heat build up Because the harmonic waveforms contain higher order frequencies capacitive leakage currents may increase to above prescribed limits and shorten...

Страница 5: ...from the load equipment or sub distribution point back to the point of entry and perhaps to the supply transformer the type of distribution system should be identifiable with the aid of the following...

Страница 6: ...o this PE conductor Figure 4 TN C S system In this system a separate neutral and protective earth functions combine in a single PEN conductor This system is also known as a Multiple Earthed MEN system...

Страница 7: ...om country to country it is important to ensure that the installation complies with all regulations applicable to the location Please seek further assistance if uncertain Regulations differ between co...

Страница 8: ...abling and upstream over current protection requirements and all instructions provided in this manual should be taken into consideration before mounting the SRF To preserve the IP rating SRF units fro...

Страница 9: ...on the external side surface of the enclosure The cabling and earth wires connected to the filter input should always be run separately with a minimum clearance of 300mm between them and all other cab...

Страница 10: ...lock 25 to 120 mm2 19 N m Backplane Stud 1 x M8 8 5 N m 500A Stud Terminal Block 1 x M10 30 N m Backplane Stud 1 x M10 17 N m 800A Stud Terminal Block 2 x M10 30 N m Backplane Stud 1 x M10 17 N m SING...

Страница 11: ...nVent com ERICO 11 SRF163N SRF3500N 2X CABLE TIE HOLES ON BACK PLANE TO FASTEN EARTH CABLE IN POSITION OUTPUT INPUT 6 2 CABLING Figure 9 Typical earth cabling Installation and Operating Instructions...

Страница 12: ...one A similar scenario exists where the output of the SRF is fed to an electrically noisy load Any transients developed by this load may also be fed to other equipment connected to the same supply Ele...

Страница 13: ...by the earthing system to which it is connected A low impedance route to the earth is required less than 10 This can be achieved by ensuring that the earth electrode system at the site presents a low...

Страница 14: ...away from the input circuit and any other current carrying conductors Alarm contact ratings 5A 250VAC 54 30 VDC 4kV Isolation See section 7 Servicing and Trouble Shooting for further information Unde...

Страница 15: ...provide a separate earth electrode for the SRF subject to compliance with relevant wiring regulations particularly where the filter is to be installed on a sub circuit some distance from the existing...

Страница 16: ...fuse should be obtained from nVent as soon as possible Note that the N E Spark Gap does not have an LED SECONDARY UNITS The Secondary Units are blue in colour and contain the secondary shunt diverter...

Страница 17: ...UNIT PHASE 1 SRFSUAC UNIT SRF3500N SECONDARY UNIT FUSES N E SPARK GAP PHASE 1 SPARK GAP SECONDARY UNIT FUSE SRF163N GREEN STATUS INDICATING LED DIVERTER MODULE STATUS INDICATING FLAG ALARM CONTACTS O...

Страница 18: ...model number These units are supplied without the proprietary enclosure and are intended to be mounted in a customer s provided switchboard SINGLE PHASE SRF MODELS FUSE SECONDARY UNIT SG PRIMARY DIVE...

Страница 19: ...the top surface and the outputs on the bottom surface See Section 6 2 Cabling SRF Model Enclosure Size mm Mounting mm W H D X1 X2 Y1 Y2 Fastener Diameter Weight Kg SRF163N 400 300 200 360 470 260 370...

Страница 20: ...ctive Lightning Protection System nVent ERICO SYSTEM 2000 Conventional Lightning Protection System 6 Protect Low Voltage Data Telecommunications Circuits 1 4 2 5 3 6 Capture the Lightning Strike Prote...

Отзывы: