background image

|

  nVent.com/ERICO

Installation and Operating Instructions

•  Transient protection devices are usually rated to protect 

against non-repetitive pulses from sources such as direct or 
induced lightning energy.

•  They are not designed to provide protection against repeated 

cyclic anomalies such as those caused by motor speed 
control notching (variable speed controls, etc).

•  SRFs are not designed to provide protection against 

sustained over-voltage conditions where the supply voltage 
exceeds, for an extended period of time, the nominal rating of 
the protection equipment. i.e continuous over-voltages from 
poorly regulated generators or distribution systems.

•  Smaller power generation equipment does not always 

conform to the same standards of voltage regulation that 
is in place for mains power reticulation. A large number of 
smaller or cheaper generators have a voltage waveform that 
approximates 240Vrms (often poorly regulated), but more 
importantly, which often contains significant higher order 
harmonics and may exhibit a peak voltage on each half cycle 
far in excess of the normal 340V (peak). Such machines 
are usually capacitive excitation induction generators, as 
opposed to synchronous generators. The problem is usually 
increased when the generator is lightly loaded.

•  Harmonic voltages may also be present in distribution 

systems that do not feature generators. This is normally 
where non-linear loads are used, such as UPSs, rectifiers, 
switch-mode power supplies and motor speed controls. The 

harmonic voltages may have peak voltages in excess of the 
protective clamping voltages, causing problems such as 
excessive heat build up. Because the harmonic waveforms 
contain higher order frequencies, capacitive leakage currents 
may increase to above prescribed limits and shorten the 
life of the SRF. It should be noted that in sites with large 
harmonic voltage distortion, the SRF capacitance may 
dramatically affect the power factor.

•  Seek the manufacturers ' advice before installing any SRF  

into a circuit which features a total harmonic voltage ratio 
above 5%.

•  With large transients, significant energy may be passed by 

the SRF diverters back to the source or to earth. This may, 
under some circumstances, cause upstream earth leakage 
circuit breakers or residual current devices (ELCBs & RCDs) 
to nuisance trip. Where possible, these devices should be 
installed after the SRF in order to reduce this possibility.

•  Transient protection devices often have minimum 

requirements for upstream fusing to ensure proper operation. 
See section 6.1 for fusing requirements.

•  By-pass switches are not recommended to be used with 

SRFs as they compromise the protection offered. The 
connection of the by-pass switch compromises the input to 
output separation requirement by bringing the SRF input  
and output wiring into close proximity at the switch.

3 INSTALLATION CAUTIONS

Figure 1. Seek specialist advice with the above installations.

SRF

SRF

SRF

SRF

SRF

ELCB 

or 

RCD

NON PREFERRED

NON PREFERRED

 PREFERRED

AVOID UPSTREAM EARTH LEAKAGE CIRCUIT BREAKERS 

(ELCB’S) OR RESIDUAL CURRENT DEVICES (RCD’S)

BYPASS SWITCHES 

BYPASS SWITCHES COMPROMISE PROTECTION

AVOID REPETITIVE VOLTAGES IN EXCESS OF SRF RATING

AVOID HIGH HARMONIC VOLTAGES

276 Vrms 

Or 

276 Vrms 

276 Vrms 

240 Vrms 

240 Vrms 

GENERATOR

GENERATOR

GENERATOR

GENERATOR

SRF

SRF

MAINS / GENERATOR CHANGE OVER SWITCH CONNECTION

Содержание ERICO 5RF363N

Страница 1: ...nVent com ERICO 1 SRF N Series Surge Reduction Filters Installation and Operating Instructions...

Страница 2: ...RODUCTION 3 2 WARNING 3 3 INSTALLATION CAUTIONS 4 4 IDENTIFY THE DISTRIBUTION SYSTEM 5 5 MOUNTING THE SRF 8 6 OPTIMISING PERFORMANCE 9 7 SERVICING AND TROUBLESHOOTING 16 8 BACKPLANE MODELS 18 9 SCHEMA...

Страница 3: ...US VOLTAGES EXIST WITHIN THE SRF ENCLOSURE THIS UNIT SHOULD BE INSTALLED SERVICED ONLY BY QUALIFIED PERSONNEL AND IN ACCORDANCE WITH RELEVANT NATIONAL ELECTRICAL SAFETY CODES ALL INSTRUCTIONS MUST BE...

Страница 4: ...oltages causing problems such as excessive heat build up Because the harmonic waveforms contain higher order frequencies capacitive leakage currents may increase to above prescribed limits and shorten...

Страница 5: ...from the load equipment or sub distribution point back to the point of entry and perhaps to the supply transformer the type of distribution system should be identifiable with the aid of the following...

Страница 6: ...o this PE conductor Figure 4 TN C S system In this system a separate neutral and protective earth functions combine in a single PEN conductor This system is also known as a Multiple Earthed MEN system...

Страница 7: ...om country to country it is important to ensure that the installation complies with all regulations applicable to the location Please seek further assistance if uncertain Regulations differ between co...

Страница 8: ...abling and upstream over current protection requirements and all instructions provided in this manual should be taken into consideration before mounting the SRF To preserve the IP rating SRF units fro...

Страница 9: ...on the external side surface of the enclosure The cabling and earth wires connected to the filter input should always be run separately with a minimum clearance of 300mm between them and all other cab...

Страница 10: ...lock 25 to 120 mm2 19 N m Backplane Stud 1 x M8 8 5 N m 500A Stud Terminal Block 1 x M10 30 N m Backplane Stud 1 x M10 17 N m 800A Stud Terminal Block 2 x M10 30 N m Backplane Stud 1 x M10 17 N m SING...

Страница 11: ...nVent com ERICO 11 SRF163N SRF3500N 2X CABLE TIE HOLES ON BACK PLANE TO FASTEN EARTH CABLE IN POSITION OUTPUT INPUT 6 2 CABLING Figure 9 Typical earth cabling Installation and Operating Instructions...

Страница 12: ...one A similar scenario exists where the output of the SRF is fed to an electrically noisy load Any transients developed by this load may also be fed to other equipment connected to the same supply Ele...

Страница 13: ...by the earthing system to which it is connected A low impedance route to the earth is required less than 10 This can be achieved by ensuring that the earth electrode system at the site presents a low...

Страница 14: ...away from the input circuit and any other current carrying conductors Alarm contact ratings 5A 250VAC 54 30 VDC 4kV Isolation See section 7 Servicing and Trouble Shooting for further information Unde...

Страница 15: ...provide a separate earth electrode for the SRF subject to compliance with relevant wiring regulations particularly where the filter is to be installed on a sub circuit some distance from the existing...

Страница 16: ...fuse should be obtained from nVent as soon as possible Note that the N E Spark Gap does not have an LED SECONDARY UNITS The Secondary Units are blue in colour and contain the secondary shunt diverter...

Страница 17: ...UNIT PHASE 1 SRFSUAC UNIT SRF3500N SECONDARY UNIT FUSES N E SPARK GAP PHASE 1 SPARK GAP SECONDARY UNIT FUSE SRF163N GREEN STATUS INDICATING LED DIVERTER MODULE STATUS INDICATING FLAG ALARM CONTACTS O...

Страница 18: ...model number These units are supplied without the proprietary enclosure and are intended to be mounted in a customer s provided switchboard SINGLE PHASE SRF MODELS FUSE SECONDARY UNIT SG PRIMARY DIVE...

Страница 19: ...the top surface and the outputs on the bottom surface See Section 6 2 Cabling SRF Model Enclosure Size mm Mounting mm W H D X1 X2 Y1 Y2 Fastener Diameter Weight Kg SRF163N 400 300 200 360 470 260 370...

Страница 20: ...ctive Lightning Protection System nVent ERICO SYSTEM 2000 Conventional Lightning Protection System 6 Protect Low Voltage Data Telecommunications Circuits 1 4 2 5 3 6 Capture the Lightning Strike Prote...

Отзывы: