![nVent SCHROFF 10130-325 Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/nvent-schroff/10130-325/10130-325_user-manual_1720877032.webp)
Date: 2021/04/07
Page
: 32 of 47
4.2.3 Settings
The cold air temperature is detected by 2 temperature sensors. The temperature sensors are
mounted
in front of the 19” plane at different heights to compensate the temperature
stratification.
As a control variable for the opening behavior of the control valve, the temperature of the
lower ("cold bottom"), the upper ("cold top") or the average value of these temperature
sensors can be used.
In addition to the control via temperature sensors, it is also possible to set the opening ratio
of the water valve manually (in % opening ratio).
Fan control variables
SET
(S1) Control fans
The following parameters are available:
Differential Pressure
Manual
In manual mode, the fan speed (20 % - 100 %) can be set. If the control is via the differential
pressure sensor, the pressure can be set from -150 Pa to +150 Pa.
Содержание 10130-325
Страница 1: ...1 nVent SCHROFF Cooling Cabinet LHX User Manual Release 1 0 07 04 2021 Doc No 61130 210...
Страница 27: ...Date 2021 04 07 Page 27 of 47...
Страница 28: ...Date 2021 04 07 Page 28 of 47 Screen Upgrade...
Страница 31: ...Date 2021 04 07 Page 31 of 47 4 2 2 Display menu...
Страница 44: ...Date 2021 04 07 Page 44 of 47 23130 662 Water hoses duct for rear panel...
Страница 46: ...Date 2021 04 07 Page 46 of 47 8 5 Air flow Air flow LHX 5 kW Air flow LHX 10 kW...
Страница 47: ...Date 2021 04 07 Page 47 of 47 8 7 Noise Level Noise level LHX 5 kW Noise level LHX 10 kW...