3.5 Bleeding the cooling module
ATTENTION
Risk of damage!
To avoid damage, the cooling module must be disconnected from the power supply during
bleeding.
Before commissioning, the device must be bleeded.
Have the refrigeration engineer/plumber open the water flow to the cabinet.
Connect a tube to the bleeding valve (1) and place it in a container with a capacity of
at least 1.5 litres.
Open the actuator (2)
manually with a 3 mm hexagonal key. (Turn it to position “1”)
Close the return valve and open the supply valve (Stopcocks in the raised floor)
Open the bleeding valve (1) carefully using a four-sided Allen key.
Allow any air to escape. When water begins to pass, close the bleeding valve.