3.7 Initial operation
The cabinet is equipped with door contact switches. When the doors are
open, the fans are disabled and the control valve is closed.
To ensure proper function and cooling performance, the front 19" plane must
be sealed off from the rear part of the cabinet by suitable air baffle plates and
seals.
Make sure that power and water supply are connected and the doors are closed.
The cooling in the cabinet starts with the default settings.
Default settings:
Cold air temperature: 24 °C
Temperature sensor: Average outlet temperature
Fan speed: 70 % manual control
The default settings can be changed via the remote display or after log-in to the web
interface of the controller.