7B.  Test the heating cable’s resistance.

It is possible to test the resistance of Frostex 

heating cable using a multimeter. Follow these 

steps:

•  Be sure the 9800 FlexFit plug is unplugged.
•  Push in the red reset button on the plug.
•  Connect the two lead wires on the meter to the 

two flat prongs on the plug. The meter reading 

should be between 2 and  

20,000 ohms.

If your reading is within this range, you have 

completed the installation.
If your reading is not within this range, repeat 

Step 3, “Install the 9800 FlexFit plug” and 

retest.
If your reading is still not within this range or 

you have questions, call nVent for technical 

support at (800) 545-6258.

PERIODIC INSPECTIONS

Each month

Test the 9800 FlexFit plug as described in Step 

6B.

Periodically

Each time you plug in the system, and at least 

once a year, do the following:

•  Check the entire Frostex system for signs of 

damage. Inspect any exposed portion of the 

heating cable for evidence of cuts, nicks, abra-

sions, gnawing by animals, and any other physi-

cal damage.

•  If there is damage, immediately replace the 

damaged heating cable system and thermal 

insulation. Do not attempt to repair any part of 

the heating cable system.

•  After a thorough inspection, start up the system 

and test the 9800 FlexFit plug and system as 

described in Steps 6 and 7.

TROUBLESHOOTING

Problem

: The red button pops out immediately 

when the plug is plugged in,  

or the button will not reset.

What to do

: A strand of braid may have entered 

the heating cable guide during  

Step 3B.

•  Unplug the 9800 FlexFit Plug.
•  Remove the cover (the reverse of Step 3D).
•  Unscrew the two screws of the heating cable 

guide (the reverse of Step 3C).

•  Using a flat blade screwdriver, gently pry the 

heating cable guide up until the heating cable 

can be removed.

•  Reinstall the screws completely into the heating 

cable guide before re-attaching.

•  Repeat installation steps 3A–3D, ensuring no 

braid strands enter the heating cable guide 

during Step 3B.

•  Repeat Step 6, “Start up the system.”

Note:

 If the 9800 FlexFit Plug red test 

button continues to pop out, your system 

is damaged and must be replaced.

Problem

: The signal light does not light up.

What to do

: Check to be sure the outlet has 

power. If you are not certain how to do this, 

call a professional service person.
If the outlet has no power, correct the problem, 

then follow Step 6, “Start up the system.”
If the outlet has power but the signal light 

still does not light up after you conduct the 

test described in Step 6B, “Test the plug,” the 

internal nonreplaceable fuse is blown. This 

means the Frostex system is damaged and 

must be replaced.

Problem

: The 9800 FlexFit plug does not trip 

(red button does not pop out).

What to do

: Check to be sure the outlet has 

power. If you are not certain how to do this, 

call a professional service person.
If the outlet has no power, correct the problem, 

then follow the instructions in Steps 6 and 7.
If the outlet has power but the 9800 FlexFit 

plug still fails to trip, the Frostex system is 

damaged and must be replaced.

Problem

: The heating cable fails to warm up or 

water is not warm after testing the system.

What to do

: The heating cable may not be fully 

inserted into the heating cable guide, or the 

guide may not be screwed down completely.

•  Unplug the 9800 FlexFit Plug.
•  Remove the cover (the reverse of Step 3D).
•  Unscrew the two screws of the heating cable 

guide (the reverse of Step 3C).

•  Using a flat blade screwdriver, gently pry the 

heating cable guide up until the heating cable 

can be removed.

•  Reinstall the screws completely into the heating 

cable guide before re-attaching.

•  Repeat installation steps 3A–3D, ensuring no 

braid strands enter the heating cable guide 

during Step 3B.

•  Repeat Step 6, “Start up the system.”

Содержание FROSTEX

Страница 1: ...from freezing nVent RAYCHEM Frostex Pipe Freeze Protection System Using the 9800 FlexFit Plug Kit Installation Instructions and User Guide APPROVALS G 60J9 Residential and Mobile Home Pipe Heating Cab...

Страница 2: ...cm plastic cable ties not included may be used to secure ground fault unit to pipe insulation If you have any questions after reading this guide call this toll free nVent number 800 545 6258 Save this...

Страница 3: ...ssemble at temperatures below 0 F 18 C The Frostex system can be left plugged in all year however you will save energy by unplugging the system when there is no risk of freezing Use a properly grounde...

Страница 4: ...s by your pipe length Add one extra foot 30 cm for each valve in your line Add one extra foot 30 cm for the distance to the power connection For installations in a crock add an additional 2 feet 60 cm...

Страница 5: ...the heating cable 2B Push the braid back Push the braid back 1 in 25 mm from heating cable end 1 in 25 mm 2C Remove the plastic wrap Cut and remove the clear plastic wrap Do not cut into the blue jack...

Страница 6: ...t sticking up Note The clear plastic wrap does not need to be removed 3B Insert the cable Insert the heating cable all the way into the cable guide until the cable hits the back wall Be sure no braid...

Страница 7: ...ostex 9610 application tape 1 foot spacing Figure 3 Single run method Multiple run method When two or more runs are required install the heating cable in the 4 o clock and 8 o clock positions as shown...

Страница 8: ...Step 6 Start up the system 6A Plug in the heating cable After installing the heating cable and insulation remove the clear label that covers the test and reset buttons Then plug the 9800 FlexFit plug...

Страница 9: ...can be removed Reinstall the screws completely into the heating cable guide before re attaching Repeat installation steps 3A 3D ensuring no braid strands enter the heating cable guide during Step 3B R...

Страница 10: ...glect alteration or improper installation repair or testing or such other cause outside of the responsibility of nVent under this Limited Warranty THE FOREGOING WARRANTY IS IN LIEU OF ALL OTHER REPRES...

Отзывы: