3.6.9. J8: Cell Voltage / Temperature
This interface is used to connect the battery cell voltage sense wires as well as up to eight 10k
Ω
NTC thermistors to the Battery Controller module.
Table 12. J8: Cell Voltage / Temperature plug housing and terminal details
Samtec IPD1-20-D
Manufacturer
Samtec Inc
Housing
IPD1-20-D
Housing material
Nylon (Zytel® PA66)
UL94V-2
Circuits
40
Crimp terminal
CC79R-2024-01-L
Wire gauge range
AWG20-24 stranded
Battery Cell Connections
The following two models of the Battery Controller are available, supporting a variety of cell counts
and voltage ranges:
NUV300-BC-12
: Connected cells are monitored internally by a single functional block. This
functional block requires a minimum stack voltage of 11V to operate and measure its input
voltages. The total voltage across the stack can be up to 60V. Unused cell tap wires should be
connected to the last cell in the stack. See
NUV300-BC-12: Connecting 12 cells to J8
and
NUV300-
BC-12: Connecting 8 cells to J8
for examples of how to connect cells to the NUV300-BC-12.
NUV300-BC-16
: Connected cells are monitored internally by two functional blocks, each
measuring eight cells (C0 to C8 and C8 to C16). Each functional block requires a minimum of 11V
across it to operate and measure its input voltages. The total voltage across the stack can be up
to 60V. See
NUV300-BC-16: Connecting 16 cells to J8
,
NUV300-BC-16: Preferred method of
connecting 11 cells to J8
and
NUV300-BC-16: Less optimal method of connecting 11 cells to J8
for
examples of how to connect cells to the NUV300-BC-12.
Groups do not need to contain the same number of cells but the maximum and minimum voltage
limits must be met, as stated in
Battery Controller supported cell connections
.
Table 13. Battery Controller supported cell connections
Battery Controller
Cell
groups
Max cell
inputs per
group
Max cell
voltage
per input
Max total
voltage
across
group
Max total
voltage
across all
groups
Min
voltage
per group
NUV300-BC-12
1
12
5V
60V
60V
11V
Installation Guide - 2018-10-08, Rev. 2.0
16