RJ-45 Plug Details
describes a typical compatible plug for the
J3: CAN
jack.
Table 4. CANBus RJ45 Connector Pin Assignment
Pin
Connection
Description
Connected to Device
1
CAN_P
CAN bus differential pair positive
External Equipment
2
CAN_N
CAN bus differential pair negative
External Equipment
3
COMIO
Common reference shared with GPIO
External Equipment
4
No Connect
Not Connected
No Connect
5
No Connect
Not Connected
No Connect
6
No Connect
Not Connected
No Connect
7
COMIO
Common reference shared with GPIO
External Equipment
8
No Connect
Not Connected
No Connect
3.6.5. J4: RS485 / Modbus RTU
The RS-485 connector is a standard RJ45 Cat5e rated jack. This interface provides an isolated RS-
485 (Modbus-RTU) port.
RS485 termination is not provided within the Battery Controller on stock production units.
Standard 120
Ω
termination must be installed at each end of the Modbus-RTU network.
RJ-45 Plug Details
describes a typical compatible plug for the
J4: RS485 / Modbus RTU
jack.
Table 5. RS485 / Modbus RJ45 Connector Pin Assignment
Pin
Connection
Description
Connected to Device
1
No Connect
Not Connected
No Connect
2
No Connect
Not Connected
No Connect
3
No Connect
Not Connected
No Connect
4
MODBUS_P
MODBUS differential pair positive
External Equipment
5
MODBUS_N
MODBUS differential pair negative
External Equipment
6
No Connect
Not Connected
No Connect
7
No Connect
Not Connected
No Connect
8
COMIO
Common reference shared with GPIO
External Equipment
3.6.6. J5: Control / GPIO
J5: Control / GPIO plug housing and terminal details
describes the recommended plug and crimp
terminals to be used with the
J5: Control / GPIO connector
.
Table 6. J5: Control / GPIO plug housing and terminal details
Installation Guide - 2018-10-08, Rev. 2.0
8
Содержание BMS NUV300-BC-12
Страница 21: ...Figure 7 NUV300 BC 12 Connecting 12 cells to J8 Installation Guide 2018 10 08 Rev 2 0 19 ...
Страница 24: ...Figure 9 NUV300 BC 16 Connecting 16 cells to J8 Installation Guide 2018 10 08 Rev 2 0 22 ...
Страница 25: ...Figure 10 NUV300 BC 16 Preferred method of connecting 11 cells to J8 Installation Guide 2018 10 08 Rev 2 0 23 ...