Thermal Camera User Manual
7.
Temperature Calibration
Open the setting page, select IPCAM Web to enter the Alarm page.
There are two items to correct the Temperature:
Thermal Offset: temperature correction offset, depends on different installation site to adjust the
temperature. EX: Fill in 2 as the detection 2 degrees.
For temperature Offset, please adjust temperature with the fixed image / target / angle /
distance, otherwise the detection result will be distorted.
Thermal Denoise: The default is 2, this item is related to the algorithm, it is not recommended to
change this parameter.
If the temperature rises abnormally for a period of time, you can try to adjust it.
The parameter range is 1~10, please restarted the camera after modification.