background image

MOUNTING THE HOUSING

NOTE: 

This unit is designed for installation between 16" OC ceiling

joists with no framing necessary. if the building structure has 24" OC
joist construction, framing will be required.
1. Position housing between ceiling joists and adjust height to

finished ceiling. Loosen two (2) hex nuts for each mounting
bracket from inside the housing and make the adjustment. Tighten
the four (4) hex nuts.

NOTE: 

There are four (4) extra mounting slots in the housing long

sides for mounting or relocating the mounting brackets.
2.

Refer to Figure 4. 

Screw housing to joists using holes in

mounting brackets and four (4) screws (furnished).

3.

Refer to Figure 2

and mounting instructions included with caps.

Install standard 3

1

4

" x 10" ductwork from damper section to

outside wall or through roof and mount appropriate wall or roof
cap (optional).

IMPORTANT: Be sure nothing obstructs the discharge of the
unit. Make sure the insulation does not get into the ductwork or
into the blower unit.

WIRING

NOTE:

All wiring connections must comply with local codes,

ordinances, and the National Electric Code and the unit must be
properly grounded.
1. Loosen screws and remove junction box.
2. Run 120vAC supply wiring with ground through switch box to

knockout in ventilator housing and secure with box connector.

3.

Refer to Figure 5. 

Connect supply wires to the unit's wires. Black

to black; white to white. Connect ground to green ground lead.

4. Replace junction box; tighten screws.
5. Connect supply wire to a listed general use wall switch in switch

box or use a listed timer suitable for the voltage and current rating
of the fan.

POWER UNIT INSTALLATION

1.

Refer to Figure 6. 

The Power Unit mounts with two hanger rods

to the mounting brackets. Insert the hanger rods through the holes
in the mounting bracket.

2. Position the power unit so that its discharge opening is in line with

the installed ductwork. Hold the power unit in position between the
mounting brackets and swing the hanger rods into the slots on the
power unit and securely tighten the wing nuts.

3. Plug the three-wire connector from the junction box into the three-

wire connector from the power unit, making sure plug is properly
aligned.

MOUNTING THE GRILLE ASSEMBLY

1. Place the reflector into the grille.
2. Insert light plug and night light plug into receptacles.
3. Using two provided screws, secure grille and reflector to housing.
4. Install 100 watt (maximum) light bulb into light socket.
5. Install 7 watt (maximum) C-7 candelabra type bulb into night light

socket.

6. Snap lens into place.

MAINTENANCE

• Disconnect the power before cleaning or performing any

maintenance on the unit.

• If the grille becomes soiled, use only a mild soap and water

solution for cleaning. Do not use solvents or abrasive cleaners.

VERTICAL DISCHARGE

3

1

4

" X 10" DAMPER

SECTION

FIGURE 3

3

1

4

" X 10"

DAMPER
SECTION

VENTILATOR
HOUSING

FIGURE 4

MOUNTING
BRACKET

LIGHT
RECEPTACLE

NIGHT LIGHT
RECEPTACLE

BLACK

WHITE

VENT
RECEPTACLE

BLACK

WHITE

BLACK

WHITE

WHITE
(COMMON)

SWITCH 
BOX

FIELD
GROUNDING
WIRE

T

O

 LIGHT SWITCH

T

O

 NIGHT

LIGHT SWITCH

T

O

 F

AN SWITCH

FIGURE 5

Содержание QuieTTest Combination Fan/Light QT140L

Страница 1: ...NING TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK OR INJURY TO PERSONS OBSERVE THE FOLLOWING A Use this unit only in the manner intended by the manufacturer If you have questions contact the manufacturer...

Страница 2: ...on box tighten screws 5 Connect supply wire to a listed general use wall switch in switch box or use a listed timer suitable for the voltage and current rating of the fan POWER UNIT INSTALLATION 1 Ref...

Страница 3: ...Stick clothes hanger through hole to help locate the area from above 2 Locate hole in attic or crawl space 3 Refer to Figure 7 In attic or crawl space mark ceiling for cutout by using the housing as...

Страница 4: ...UTONE S OBLIGATION TO REPAIR OR REPLACE AT NUTONE S OPTION SHALL BE THE PURCHASER S SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY NUTONE SHALL NOT BE LIABLE FOR INCIDENTAL CONSEQUENTIAL OR SPECIAL DAM...

Страница 5: ...red o el techo no da e el cableado el ctrico ni otros servicios escondidos D Los ventiladores entubados siempre deben estar ventilados hacia el exterior E Si la unidad se va a instalar encima de una b...

Страница 6: ...el cable de alimentaci n a un interruptor de pared certificado de uso general en la caja del interruptor o utilice un temporizador certificado apropiado para el voltaje y el tipo de corriente del ven...

Страница 7: ...ropa por el agujero para ayudarle a localizar el rea desde arriba 2 Localice el agujero en el tico o s tano de peque a altura 3 Refi rase a la Figura 7 En el tico o en el s tano de peque a altura mar...

Страница 8: ...que a Ud LA OBLIGACI N DE NUTONE DE REPARAR O REEMPLAZAR A SU OPCI N SER EL NICO Y EXCLUSIVO RECURSO QUE TENDR EL COMPRADOR BAJO ESTA GARANT A NUTONE NO SER RESPONSABLE POR DA OS INCIDENTALES CONSECUE...

Отзывы: