09. 06. 21. Document Number  671786

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

XBC75 & 85 (AS Control)

Installation Manual

7.0 ELECTRICAL INSTALLATION

Before commencing work, make sure that the unit, switched live 
and Nuaire control are electrically isolated from the mains supply.

The electrical wiring must be carried out by competent persons, in 
accordance with good industry practice and should conform to all 
governing and statutory bodies i.e. IEE, CIBSE etc.

7.1 Supply

The control is powered by a 400Vac 50Hz 3 phase supply. This must be 
isolated local to the unit and fitted with appropriate over-current and 
fault protection.

7.1.1 Electric Heater Supply

For models with electric heating, the heating circuit is powered by a 
separate, higher current, 400VAC 3ph supply. This must be isolated 
local to the unit and fitted with appropriate over-current protection. 
The main supply is still required.

Electric Heater models require two separate supplies, each with an 
appropriate overcurrent current protection device.

7.2 Volt Free Contacts

Volt free contacts are not fused. If these are used to power any external 
equipment, the installer must provide adequate fusing or other 
protections.

Volt free relay contacts are rated at 5A resistive, 0.5A inductive.

Run Connections:

   The relay is powered when the fan is running  

 

 

 

(contacts are used when an I/O damper   

 

  is 

installed). 

Fault Connections

No Fault

 - The relay is powered. 

  Fault 

- The relay is unpowered. 

Heat Demand:

  

The relay is powered when heating is selected. 

Cool Demand:

  

The relay is powered when cooling is selected.

7.3 Switched Live

Switch Live (SL) terminal 

- A signal of 100-230V AC will activate the 

switched live signal.

Switch Live 2 Boost (SL2) terminal

 - A signal of 100-230V AC will 

activate the switched live 2 (Fan Boost) signal. 

A signal from an isolating transformer will produce an unpredictable 
result and is not recommended.

Volt free versions of the switched live signals are also available at 
terminals T33-T34 & T35-T36. Link two contacts to activate the signal.

7.4 Damper Connections

A fan start delay can be imposed to allow the damper time to open and 
is adjustable via the strategy.

7.5 Network Settings

Default IP address:  

192.168.11.12 

Subnet mask:  

 

255.255.255.0

A copy of the strategy is stored in the EDoS (Engineering Data on Site) 
portion of memory.

7.6 Connection Chart

Description

TD

Short 

Name

Subsystem

Signal 

Address

Block 

Type

Signal 

Type

Unit

Min

Max

Fresh Air Temp

AHU’2Sensors’1FreshAir

1FreshAir

C

1.1

AI

R1K

°C

0

50

Supply Air Temp

AHU’2Sensors’2SupAIr

2SupAIr

C

1.2

AI

R1K

°C

-50

80

Extract Air Temp

AHU’2Sensors’3ExtAir

3ExtAir

C

1.3

AI

R1K

°C

-50

80

CO2 Sensor

AHU’2Sensors’4CO2

4CO2

C

1.4

AI

U10

ppm

0

2000

Fan Speed Cntrl

AHU’2Sensors’5FnSdCnt

5FnSdCnt

C

1.5

AI

U10

%

0

10

Alm Ctritical

AHU’3DigIns’AlmCritC1

AlmCritC1

C

1.6

BI

D20

Nml/Alm

Alm Maintenance

AHU’3DigIns’AlmFitC2

AlmFltC2

C

1.7

BI

D20

Nml/Alm

Enable Hware

AHU’3DigIns’EnaHW

EnaHW

C

1.8

BI

D20

No, Yes

Boost Ena Hware

AHU’3DigIns’BoostHW

BoostHW

C

1.9

BI

D20

No, Yes

OCC PIR Hware

AHU’3DigIns’OccPIR

OccPIR

C

1.10

BI

D20

UnOcc/Occ

SupFan AirFlo

AHU’3DigIns’SpFnDPS

SpFnDPS

C

1.11

BI

D20

NoFlo/Flow

ExtFan AirFlo

AHU’3DigIns’ExtFnDPS

ExtFnDPS

C

1.12

BI

D20

NoFlow/Flow

Extract Speed

AHU’6Outpts’4ExtFan

4ExtFan

C

4.1

AO

Y10S

%

0

100

Supply Speed

AHU’6Outpts’3SupFan

3SupFan

C

4.2

AO

Y10S

%

0

100

Heating Sig

AHU’6Outpts’7HtgSig

7HtgSig

C

4.3

AO

Y10S

%

0

100

Cooling SIg

AHU’6Outpts’91ClgSig

91ClgSig

C

4.1

AO

Y10S

%

0

100

Bypass Dmp

AHU’6Outpts’5DmpCnt

5DmpCnt

C

5.1

BO

Q250

Reclaim/Bypass

Fault Relay

AHU’6Outpts’92FltRly

92FltRly

C

5.2

BO

Q250

Off, On

Fan Enabled Rly

AHU’6Outpts’2FanEna

2FanEna

C

5.3

BO

Q250

Off, On

Chilled Dmd Relay

AHU’6Outpts’8ClgDmd

8ClgDmd

C

5.4

BO

Q250

No, Yes

Heat Dmd Relay

AHU’6Outpts’6HtgDmd

6HtgDmd

C

5.5

BO

Q250

No, Yes

IO Damper

AHU’6Outpts’11IODmp

11IODmp

C

5.6

BO

Q250

Close, Open

Содержание XBC75

Страница 1: ...PARTS This unit contains fast moving rotational parts which may start automatically It is the sole responsibility of the installer to adequately guard these components REFER TO INSTRUCTION MANUAL Rea...

Страница 2: ...ttenuator Length 900 900mm 6 Unit Roof No Suffix Standard Unit No Roof WP Twin Pitched Roof Factory Fitted 3 0 DELIVERY 3 1 Receiving Equipment All equipment is inspected prior to despatch and leaves...

Страница 3: ...ensions mm and Weights kg Includes unit and 76mm high base frame Unit Code Unit Dimensions mm Control Dimensions mm Unit Weight kg Packed Weight kg A B C J K M E F G XBC75 H 2800 2126 876 940 740 940...

Страница 4: ...ion Dimensions mm Weight kg Width Height Length 4 XBC75 H MD24V Motorised dampers 24V for Horizontal XBC75 Adapt Siemens AS control units 620 560 165 14 4 XBC85 H MD24V Motorised dampers 24V for Horiz...

Страница 5: ...and Weights kg Unit Code Unit Dimensions mm Control Dimensions mm Unit Weights Packed Weights A B C J F H W D kg kg XBC75 H 2500 954 1416 610 894 60 954 2500 630 730 XBC85 H 3000 1000 1676 940 740 65...

Страница 6: ...Weight kg Width Height Length 4 XBC75 V MD24V Motorised dampers 24V for Vertical XBC75 units with Adapt Siemens AS control 620 560 165 14 4 XBC85 V MD24V Motorised dampers 24V for Vertical XBC85 unit...

Страница 7: ...ttery 5 2 Vertical Units e g XBC75 V XBC85 V 8 Vertical Unit Access All access panels are located on one side of the fan unit Note Unit must be isolated before panels are removed 9 Vertical Unit Overv...

Страница 8: ...ndition Observe and record filter pressure drops after performance commissioning Typically filter dirty condition occurs when the initial filter clean readings have been increased by 125Pa If filter m...

Страница 9: ...XBC75 H MD24V Vertical XBC75 V MD24V needs to be fitted after the silencer This ensures that breakout noise levels are kept to a minimum Fully interlocking parallel blades half inch diameter electrop...

Страница 10: ...h the switch will trip When the pressure falls below this set value the switch returns to its resting position 6 4 2 Switch Wiring The cable gland is designed for cables with alternative sheath diamet...

Страница 11: ...Air Temperature Sensor D Thermal Trip Electric Heater Only E LPHW Heater LPHW Models Only F Bypass Damper Drive G Condensate Pump Alarm H Fresh Air Temperature I Extract Fan Drive Health 6 5 2 Horizo...

Страница 12: ...mer will produce an unpredictable result and is not recommended Volt free versions of the switched live signals are also available at terminals T33 T34 T35 T36 Link two contacts to activate the signal...

Страница 13: ...MP terminals blocks 19 Removing Terminal Connections 7 7 4 Fitting Jumpers Terminal blocks can be connected together to increase the number of terminals at the same potential using push in jumpers In...

Страница 14: ...cument Number 671786 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC75 85 AS Control Installation Manual 7 8 Physical Layout Diagrams 7 8 1 Horizontal Units 25 Physical Layout Ho...

Страница 15: ...15 09 06 21 Document Number 671786 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC75 85 AS Control Installation Manual 7 8 2 Vertical Units 26 Physical Layout Vertical Units...

Страница 16: ...ly CF83 1NA nuaire co uk XBC75 85 AS Control Installation Manual 7 9 Wiring Diagrams All inter connections between circuit boards blowers and sensors are made at the factory This diagram only shows th...

Страница 17: ...17 09 06 21 Document Number 671786 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC75 85 AS Control Installation Manual 28 Wiring Diagram Electric Heater...

Страница 18: ...clockwise or anticlockwise It is recommended that the frost condition temperature is set at 4 C 8 2 Electric Frost Coils 8 2 1 Wiring The heater requires two connections the relay link up and the 400V...

Страница 19: ...or cooling options 9 8 Frost Protection Should the internal temperature of the unit fall below a value defined in the commissioning variables the control will override all heating cooling logic to ope...

Страница 20: ...ean with a soft brush or vacuum Check for signs of contamination 10 3 Annually Thoroughly inspect the unit and its components for corrosion acting immediately to treat restore any damaged areas All el...

Страница 21: ...on plate attached to the unit casing Part Number Description XBC75 V FILTERKIT XBC75 Replacement G4 Panel Filters x4 776187 XBC75 Replacement Blower Assembly x1 18kg XBC75 H FILTERKIT XBC85 Replacemen...

Страница 22: ...er and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature...

Страница 23: ...23 09 06 21 Document Number 671786 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC75 85 AS Control Installation Manual NOTES...

Страница 24: ...24 09 06 21 Document Number 671786 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC75 85 AS Control Installation Manual NOTES...

Отзывы: