26. 01. 17. Leaflet Number 671340

Installation and Maintenance

SQURBO XBOX

4.0 Wiring - for units supplied 
without Ecosmart Control

The wiring illustrations below are for the fans, bypass damper

and electric heater for units without control. 

All wiring is terminated in junction boxes fitted to the specified

side of the unit.

It is the installer’s responsibility to select and fit the appropriate

control equipment to produce the desired output.

Note that any heating/cooling coils fitted are supplied 

without control valve and actuator.

Electrical Details

Fan motor  

Electric heater 

ratings

ratings (if fitted)

Unit size  flc 

sc 

kW 

flc

S1-XB

2x 0.65A 

2x 0.65A 

N/A 

N/A

S2-XB

2x 0.75A 

2x 3A 

4.5kW 

18.7A

S3-XB

2x 0.75A 

2x 3A 

4.5kW 

18.7A

S4-XB

2x 1.2A 

2x 4.8A 

4.5kW 

18.7A

S5-XB

2x 1.2A 

2x 4.8A 

4.5kW 

18.7A

S6-XB

2x 3A 

2x 3A 

6.0kW 

25A

Bypass damper rated at 3W, 13mA for all unit sizes.

Isolator 
by others

N L

N L

230V-50Hz

Speed control signal
<1V = fan off
Alternatively connect link
from +V to SIG for 
max speed

1 - 10V

0V

+V

SIG

0V

(Unit size S1-XB) Fan wiring. 

Two per unit and one per blower.

Isolator 
by others

N L

N L

230V-50Hz

N L

230V-50Hz

N L

Isolator 
by others

Bypass Damper

P

ower t

o open

A

ut

o Close

Electr

ic Heat

er

Ther

mal Ov

er

load

Connection t

Electr

ic Elements

(Unit sizes S2-6-XB) with electric heater 

bypass damper and electric heater wiring.

(Unit sizes S1-6-XB) Fan only or with 

LPHW coil bypass damper wiring.

N L

230V-50Hz

Isolator 
by others

Bypass Damper

P

ower t

o open

A

ut

o Close

N L

Figure 10.

Figure 13.

Figure 14.

EARTH

NEUTRAL

LIVE

Isolator 
by others

N L

N L

230V-50Hz

Fuse

3A  (T)

(Unit size S2-5-XB) Fan wiring. 

Two per unit and one per blower.

Figure 11.

Isolator 
by others

N     L

N L

230V-50Hz

Speed control signal
<1V = fan off
Alternatively connect link
from +V to SIG for 
max speed

1 - 10V

0V

+V

SIG

0V

Note: Do not wire the power supply to motor 
via motor thermal overload as these are only 
closed after the motor is energised.
Thermal overload contact rating is 
2A max resistive.

Mo

tor Ther

mal

Ov

er

load

TK   TK

(Unit size S6-XB) Fan wiring. 

Two per unit and one per blower.

Figure 12.

Содержание SQURBO XBOX

Страница 1: ...cluding all external services and controls should be installed in accordance with the appropriate authority and must conform to all governing regulations e g CDM CIBSE IEE and in strict accordance wit...

Страница 2: ...ual controls and for linking the fans together under a common control If more than 4 connections are required the junction box product code ES JB should be used see data cable installation Switch Live...

Страница 3: ...ith the instructions Please note that the total data cable length used in any system must be less than 1000m Keep the number of cable joints to a minimum to ensure the best data transmission efficienc...

Страница 4: ...ract N E L SL DP CL N RET Heat Demand Run Fault NET connections for Ecosmart devices Min Max SL run on Trickle Test 0 1 Link wire see note ES CO2 Connection BMS Input Signal 0 10V 0V Ecosmart Pwr Stan...

Страница 5: ...ted in the system The voltage tolerance is _ 125mV and is measured at the fans terminal Ventilation Cooling Heating mode mode mode Local control 0 00 OFF trickle 0 25 Speed 1 0 50 0 75 1 00 Speed 2 1...

Страница 6: ...1V fan off Alternatively connect link from V to SIG for max speed 1 10V 0V V SIG 0V Unit size S1 XB Fan wiring Two per unit and one per blower Isolator by others N L N L 230V 50Hz N L 230V 50Hz N L Is...

Страница 7: ...move covers and carefully clean out interiors as necessary Check for damage and security of components Refit covers 6 0 Replacement of Parts Should any component need replacing Nuaire keep extensive s...

Страница 8: ...to the appropriate standard must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations 5 3 For EMC all contro...

Отзывы: