NuAire MRXBOXAB-ECO-LP2-C Скачать руководство пользователя страница 8

8

nuaire.co.uk 

029 2085 8400

20. 08. 19. Document Number  671887

I

nstallation and Maintenance

MRXBOXAB-ECO-LP2-C Remote Commissioning MVHR 

1. For the required air flow rates please refer to the design specification 

for the property, follow 2.4, or refer to building regulations ADF 
2010.

2. The unit is supplied with independent control for both normal and 

boost airflows (Figure 14).

3. Correct commissioning is essential to ensure the ventilation air 

flowrates are met. It also ensures the unit is not over ventilating and 
causing excessive power consumption.

4. Commissioning should be carried out in accordance with building 

regulations document “Domestic ventilation compliance guide”. 
 
A calibrated moving vane anemometer and hood will be required to 
carry out commissioning.

5. Adjustment valves should be locked in place to prevent further 

adjustment.

6. Once commissioned the home owner / tenant should be informed 

that the unit should not be adjusted as it will have a detrimental 
effect on the indoor air quality and could result in condensation and 
mould growth. The label covering the control has an adhesive panel 
which should be removed post commissioning to prevent tampering.

+

-

-

+

- +

-

+

- +

Power

Post commissioning remove

adhesive backing under 

this section

060905

Ventilation Controls

For commissioning: 

refer to user manual

+

-

Control module

9.0 COMMISSIONING

IMPORTANT

The filters fitted inside the unit are protected with a plastic film. 

Prior to commissioning remove the covers (Figure 15), take off the 

film and replace.

Figure 14.  PCB Inside Enclosure

HX Bypass

(AB units only)

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

10.0 STATUS INDICATION

The status of the unit is indicated by a series of LED’s on the control box 
cover. The variants are listed below.

10.1 Integral automatic HX bypass (AB units only)

Intake and extract temperatures are monitored at the point the 
airflows enter the unit, if the range falls within the set parameters the 
bypass damper is opened automatically to target an indoor comfort 
temperature all year round.

Note:  The extract temperature is an average from all wet rooms. If 
this exceeds 25°C the unit may go into bypass depending on outside 
temperatures.

10.2 Frost Protection

In the event of the intake air temperature at the unit dropping below 
the predetermined set point (-5°C as standard) the supply fan will 
reduce to minimum speed, once the temperature rises above the set 
point the fan will return to its commissioned speed.

Please note this mode will only activate after ten days of continuous 
run time. If commissioning of the unit is outside of this time frame 
please notify the after sales department prior to site visit.

11.0 MAINTENANCE/CLEANING

Nuaire recommend that filters are inspected every 6 months and 
replaced every 12 months. A flashing LED (section 10.0) will indicate 
that a filter change is required. This indication repeats every 12 months 
and will turn off automatically after 5 Days.

Remove the filter covers on the front panel of the unit by gripping the 
two circular tabs either end of the filter covers and pulling away from 
the unit. The filter can now be extracted by pulling the removal loop on 
the front edge of the filter. Once the filters have been inspected return 
or replace them as necessary. 

Inspect the heat exchanger every 5 years. Generally check for damage 
and security of components. Refit cover.

Note: The display on the unit control panel will not indicate when a 
higher speed setting has been triggered by an external source, such 
as an ES-PIR2 etc.

Содержание MRXBOXAB-ECO-LP2-C

Страница 1: ...mum contact separation of 3mm in accordance with latest edition of the wiring regulations This unit must be earthed Ducting must be securely fixed with screws to the spigot to prevent access to live p...

Страница 2: ...all statutory governing regulations Beware of sharp edges on unit when handling ensure appropriate PPE is used All mains wiring must be in accordance with the current I E E Regulations or the appropri...

Страница 3: ...epth on the pipe and check that the pipe section to be jointed is free of any surface damage which may affect the joint seal 3 Unscrew the cap from the MVHR DRAIN outlet and slide the cap and rubber s...

Страница 4: ...rate from Table 1 For sanitary accommodation only as an alternative the purge ventilation provisions given in ADF 2010 can be used where security is not an issue In this case minimum high extract rat...

Страница 5: ...2 3 735 Filter access distance Removable access filter Removable access filter 69 97 342 Access Requirements Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in ceilings Ai...

Страница 6: ...3 735 Filter access distance Removable access filter Removable access filter 69 97 342 Access Requirements Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in ceilings Air V...

Страница 7: ...oses only as the connections above are factory fitted Connection to Remote Fail Indicator Ref MRXBOX95 RFI optional Fuse 2A MAINS 230V 50Hz light Room Light switch Double Pole N L 3 Pole isolator Kitc...

Страница 8: ...N The status of the unit is indicated by a series of LED s on the control box cover The variants are listed below 10 1 Integral automatic HX bypass AB units only Intake and extract temperatures are mo...

Страница 9: ...only for the remaining 4 years This warranty is conditional on planned maintenance being undertaken This warranty is void if the equipment is modified without authorisation is incorrectly applied misu...

Отзывы: