NuAire MRXBOXAB-ECO-LP2-C Скачать руководство пользователя страница 4

4

nuaire.co.uk 

029 2085 8400

20. 08. 19. Document Number  671887

I

nstallation and Maintenance

MRXBOXAB-ECO-LP2-C Remote Commissioning MVHR 

Table 1. ADF 2010 - Extract ventilation rates.

Table 2. Whole dwelling ventilation rates.

Notes:

1. In addition, the minimum ventilation rate should be no less than 
0.3 l/s per m2 of internal floor area.  (This includes all floors, e.g. 
for a two-story building add the ground and first floor areas).

2. This is based on two occupants in the main bedroom and a single 
occupant in all other bedrooms. This should be used as the default 
value. If a greater level of occupancy is expected add 4 l/s per 
occupant.

Room

Min high rate

Min low rate

Kitchen

13 l/s

Total extract rate 

should be at least 

the whole dwelling 

ventilation rate given 

in Table 2.

Utility Room

8 l/s

Bathroom

8 l/s

Sanitary 

Accommodation

6 l/s

Number of bedrooms in dwelling

1

2

3

4

5

Whole dwelling 
ventilation rate 
(l/s)

1,2

13

17

21

25

29

3.4 Ventilation Flow Rates

3.5 ADF 2010 Ventilation Calculations Design of MVHR 
Systems

The MVHR system has been sized for the winter period. Additional 
ventilation may be required during the warmer months and it has 
been assumed that the provisions for purge ventilation (e.g. open-able 
windows) could be used.

Step 1:

 For any design air permeability, determine the whole dwelling 

ventilation supply rate from

 Table 2.

As an alternative where the design air permeability is intended to be 
leakier than (>) 5m3/(h.m2) 50 Pa, allow for infiltration for all dwelling 
types by subtracting from the whole dwelling ventilation supply rate 
from Table 2; 0.04 x gross internal volume of the dwelling heated space 
(m3).

Step 2:

 Calculate the whole dwelling extract ventilation rate by 

summing the individual room rates for ‘minimum high rate’ from 

Table 

1.  

(For sanitary accommodation only, as an alternative, the purge 
ventilation provisions given in ADF 2010 can be used where security is 
not an issue. In this case ‘minimum high extract rate’ for the sanitary 
accommodation should be omitted from the step 2 calculation).

Step 3: 

The required airflow rates are as follows: 

The maximum whole dwelling extract ventilation rate (e.g. boost) 
should be at least the greater of step 1 and step 2.

Note that the maximum individual room extract rate should be at least 
those given in

 table 1 

for minimum high rate.

The minimum air supply rate should be at least the whole building 
ventilation rate found in step 1.

For Scotland refer to BRE Digest 398.

For further information refer to the “Domestic Ventilation Compliance 
Guide”.

IMPORTANT

Any air intake terminal MUST be installed in accordance with the 

appropriate regulation.

As a guide, the BS5440 series of British Standards deals with this 

issue and currently states that an air intake must be at a minimum 

distance of 300mm from a gas boiler balanced flue.

Installers are advised to be aware of the requirements of this 

standard when installing ‘through the wall’ supply air ducting.

Pre Commissioning MRXBOXAB MVHR Units

MRXBOXAB units are designed to ventilate the whole dwelling 
and must not be used during site construction or the clean-up 
period. Cement and plaster dust can be abrasive and can affect 
fan performance and reliability. Please ensure that the filters are 
checked prior to commissioning to ensure there is no build-up of 
dust or debris.

While the property is drying out, very high moisture levels are likely 
to occur. Therefore it is advisable that if the installation and building 
works are complete the unit is left running. If the building works are 
not complete please close the air valves or cover up the air valves to 
prevent condensation forming in the ductwork and the MRXBOXAB 
unit due to natural migration of warm air.

Содержание MRXBOXAB-ECO-LP2-C

Страница 1: ...mum contact separation of 3mm in accordance with latest edition of the wiring regulations This unit must be earthed Ducting must be securely fixed with screws to the spigot to prevent access to live p...

Страница 2: ...all statutory governing regulations Beware of sharp edges on unit when handling ensure appropriate PPE is used All mains wiring must be in accordance with the current I E E Regulations or the appropri...

Страница 3: ...epth on the pipe and check that the pipe section to be jointed is free of any surface damage which may affect the joint seal 3 Unscrew the cap from the MVHR DRAIN outlet and slide the cap and rubber s...

Страница 4: ...rate from Table 1 For sanitary accommodation only as an alternative the purge ventilation provisions given in ADF 2010 can be used where security is not an issue In this case minimum high extract rat...

Страница 5: ...2 3 735 Filter access distance Removable access filter Removable access filter 69 97 342 Access Requirements Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in ceilings Ai...

Страница 6: ...3 735 Filter access distance Removable access filter Removable access filter 69 97 342 Access Requirements Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in ceilings Air V...

Страница 7: ...oses only as the connections above are factory fitted Connection to Remote Fail Indicator Ref MRXBOX95 RFI optional Fuse 2A MAINS 230V 50Hz light Room Light switch Double Pole N L 3 Pole isolator Kitc...

Страница 8: ...N The status of the unit is indicated by a series of LED s on the control box cover The variants are listed below 10 1 Integral automatic HX bypass AB units only Intake and extract temperatures are mo...

Страница 9: ...only for the remaining 4 years This warranty is conditional on planned maintenance being undertaken This warranty is void if the equipment is modified without authorisation is incorrectly applied misu...

Отзывы: