MRXBOXAB-ECO-LP2-C Remote Commissioning MVHR 

8.0 ELECTRICAL CONNECTION

IMPORTANT

For good EMC engineering practice, any sensor cables or switched 

live cables should not be placed within 50mm of other cables or 

on the same metal cable tray as other cables.

EXTRA

EXTRA

CT F

CT F

AN

 

LI

AF

 

   

 

Supply  Extract  Supply  Extract  Supply  Extract

SPEED 1 

SPEED 2  

SPEED 3

3

2

Please note: the electrical connection of the unit must be carried out by 
a qualified electrician. 
The unit is supplied with a flexible cord for connection to the mains 
supply.

Electrical details:- 
Voltage: 240V 1ph 50Hz 
Consumption: LP2 - 1.3 Amps 
Fuse rating: 3 Amps

NOTE: This unit must be earthed. 
The cable from the mains power supply should be connected to a 
fixed wiring installation, via a fused isolator, in accordance with 
current IEE wiring regulations.

If more than one Ecosmart 
sensor is required please 
use MRXBOX-JB and refer 
to leaflet No. 671700 for 
installation instructions.

Note: Wiring is for reference 
purposes only as the 
connections above are 
factory fitted. 

Connection to Remote Fail 
Indicator Ref: MRXBOX95-RFI 
(optional).

Fuse 2A

MAINS

230V

50Hz

light

Room

Light

switch

(Double

Pole)

N

L

3 Pole

isolator

Kitchen switch

Blue

Brown

Black

Optional speed 3 switch

Supply cord

from unit

Grey

Green/yellow

Fuse 2A

MAINS

230V

50Hz

Room

lights

Light

switches

(Double

Pole)

N

L

3 Pole

isolator

Kitchen switch

Blue

Green/yellow

Brown

Black

Supply cord

from unit

Optional speed 3 switch

Grey

Unit Serving Kitchen and Bathroom

Unit Serving Kitchen and Two Bathrooms

Figure 11. PCB Details

Figure 12.  

Figure 13.  

Disconnection from the 
supply mains must be 
incorporated within the fixed 
wiring in accordance with the 
wiring regulations and shall 
have a minimum contact 
separation of 3mm.

Disconnection from the 
supply mains must be 
incorporated within the fixed 
wiring in accordance with the 
wiring regulations and shall 
have a minimum contact 
separation of 3mm.

8.1 OPTIONAL CONTROLS 

For Further Information Contact Nuaire on 02920 858 400.

Note: for Ecosmart sensors/controls cut a 
slit in the grommet and feed the Ecosmart 
connector through to retain sufficient 
protection against water ingress. Ensure 
Ecosmart cabling is secured with P-clips 
supplied to provide suitable cable retention. 

Содержание MRXBOXAB-ECO-LP2-C

Страница 1: ...mum contact separation of 3mm in accordance with latest edition of the wiring regulations This unit must be earthed Ducting must be securely fixed with screws to the spigot to prevent access to live p...

Страница 2: ...all statutory governing regulations Beware of sharp edges on unit when handling ensure appropriate PPE is used All mains wiring must be in accordance with the current I E E Regulations or the appropri...

Страница 3: ...epth on the pipe and check that the pipe section to be jointed is free of any surface damage which may affect the joint seal 3 Unscrew the cap from the MVHR DRAIN outlet and slide the cap and rubber s...

Страница 4: ...rate from Table 1 For sanitary accommodation only as an alternative the purge ventilation provisions given in ADF 2010 can be used where security is not an issue In this case minimum high extract rat...

Страница 5: ...2 3 735 Filter access distance Removable access filter Removable access filter 69 97 342 Access Requirements Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in ceilings Ai...

Страница 6: ...3 735 Filter access distance Removable access filter Removable access filter 69 97 342 Access Requirements Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in ceilings Air V...

Страница 7: ...oses only as the connections above are factory fitted Connection to Remote Fail Indicator Ref MRXBOX95 RFI optional Fuse 2A MAINS 230V 50Hz light Room Light switch Double Pole N L 3 Pole isolator Kitc...

Страница 8: ...N The status of the unit is indicated by a series of LED s on the control box cover The variants are listed below 10 1 Integral automatic HX bypass AB units only Intake and extract temperatures are mo...

Страница 9: ...only for the remaining 4 years This warranty is conditional on planned maintenance being undertaken This warranty is void if the equipment is modified without authorisation is incorrectly applied misu...

Отзывы: