background image

2.4 Ventilation flow rates

Table 1.

ADF 2010  – Extract ventilation rates

Room

Min high rate

Min low rate

Kitchen

13 l/s

Utility room

8 l/s

Bathroom

8 l/s

Sanitary 

accommodation

6 l/s

Table 2.

Whole dwelling ventilation rates

Number of bedrooms in dwelling

1

2

3

4

5

Whole

13

17

21

25

29

dwelling 

ventilation 

rate l/s

1, 2

Notes:

1, In addition, the minimum ventilation rate should be not less than 0.3 l/s

per m2 of internal floor area. 

(This includes all floors, e.g. for a two-story building add the ground and

first floor areas).

2, This is based on two occupants in the main bedroom and a single occu-

pant in all other bedrooms. This should be used as the default value. If a

greater level of occupancy is expected add 4 l/s per occupant. 

2.5 ADF 2010 Ventilation calculations

Design of MVHR systems

The MVHR system has been sized for the winter period.

Additional ventilation may be required during the warmer

months and it has been assumed that the provisions for purge

ventilation (e.g. openable windows) could be used.

Step 1:

For any design air permeability, determine the whole

dwelling ventilation supply rate 

from Table 2.

As an alternative where the design air permeability is intended

to be leakier than (>) 5m

3

/(h.m

2

) 50 Pa, allow for infiltration

for all dwelling types by subtracting from the whole dwelling

ventilation supply rate 

from Table 2

; 0.04 x gross internal 

volume of the dwelling heated space (m

3

).

Step 2:

Calculate the whole dwelling extract ventilation rate by

summing the individual room rates for ‘minimum high rate’ 

from

Table 1.

(For sanitary accommmodation only, as an alternative, the

purge ventilation provisions given in ADF 2010 can be used

where security is not an issue. In this case ‘minimum high

extract rate’ for the sanitary accommodation should be omitted

from the step 2 calculation).

Step 3: 

The required airflow rates are as follows:

n

the maximum whole dwelling extract ventilation rate 

(e.g. boost) should be at least the greater of step 1 and 

step 2. 

Note that the maximum individual room extract rate should 

be at least those given

in table 1.

for minimum high rate.

n

the minimum air supply rate should be at least the whole 

building ventilation rate found in step 1.

For Scotland refer to BRE Digest 398.

For further information refer to “Domestic Ventilation Compliance
Guide” www.planningportal.gov.uk/buildingregulations/approved
documents/partl/compliance

3

27. 11. 17. Leaflet Number 671582

Installation and Maintenance

MRXBOX95B-LP1 Mechanical Ventilation with Heat Recovery & Summer Bypass

Any air intake terminal MUST be installed in accordance with the 
appropriate regulation. 
As a guide, the BS5440 series of British Standards deals with this 
issue and currently states that an air intake must be at a minimum 
distance of 300mm from a gas boiler balanced flue.

Installers are advised to be aware of the requirements of this 
standard when installing ‘through the wall’ supply air ducting.

Pre Commissioning MRXBOX95

MVHR Units

MRXBOX95 units are designed to ventilate the whole

dwelling and must not be used during site construction 

or the clean-up period. Cement and plaster dust can be

abrasive and can affect fan performance and reliability. 

Please ensure that the filters are checked prior to 

commissioning to ensure there is no build-up of dust or

debris.

While the property is drying out, very high moisture levels

are likely to occur.  Therefore it is advisable that if the 

installation and building works are complete the unit is

left running. If the building works are not complete please

close the air valves or cover up the air valves to prevent

condensation forming in the ductwork and the

MRXBOX95 unit due to natural migration of warm air.  

Total extract rate should

be at least the whole

dwelling ventilation rate

given in table 2.

Содержание Ecosmart MRXBOX95B-LP1

Страница 1: ...Voltage Frequency and Phase complies with the rating label Please note a clear working space is required around the installed unit to allow the cover to be removed and provide sufficient access for ma...

Страница 2: ...ad Hand tight should be adequate to form a proper seal 2 2 Extract input areas The unit is designed to extract air from all wet rooms e g bathroom kitchen en suite utility room with sink WC s do not n...

Страница 3: ...step 2 calculation Step 3 The required airflow rates are as follows n the maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note that the ma...

Страница 4: ...oom to outside via air brick Supply and extract ducts from external air bricks to the unit needs to be insulated Minimum distance as specified in Building Regulations Top of ceiling void Intake air fr...

Страница 5: ...ir Spigot 4 Air Exhaust Spigot 1 Air 250 Intake Heat exchanger Bypass chamber Supply fan Extract fan 21 5mm condensate pipe Drip tray Wire frame lter Wire frame lter Bypass 4 damper 1 2 3 735 Filter a...

Страница 6: ...al cable tray as other cables Figure 9 7 0 Electrical Connection Please note the electrical connection of the unit must be be carried out by a qualified electrician The unit is supplied with a flexibl...

Страница 7: ...al gov uk building regulations approved documents partf associated A calibrated moving vane anemometer and hood will be required to carry out commissioning 5 Adjustment valves should be locked in plac...

Страница 8: ...ty is conditional on planned maintenance being undertaken This warranty is void if the equipment is modified without authorisation is incorrectly applied misused disassembled or not installed commissi...

Отзывы: