11.0 MAINTENANCE

11.2 Bearings

11.1 Fans

11.1.1 General Fan Maintenance

11.3 Filters

It is the owner’s responsibility to ensure that the air handling equipment is 
maintained accordingly. In doing so, regular and scheduled checks will decrease 
the possibility of unforeseen and possibly costly repairs. Maintenance tasks 
should be taken care of by a competent person, if system failure occurs due to 
improper maintenance, Nuaire will not be held liable for the costs of restoring a 
unit to its previous working condition.

It is recommended that PPE is always used during the maintenance of Air
Handling Equipment – gloves, eye shields and respiratory mask.

The bearings that are fitted will be (unless otherwise specified) “sealed for life”, 
therefore consequence maintenance is not required.  

Fan bearings are lifelong; up to 40,000 hours of operation. In cases of heavy 
duty operation, maintenance intervals are to be established by the operator.

Please refer to general arrangement drawings for details of the type of fan and 
drive that is fitted. Maintenance guidelines for all fans are beyond this manual, 
please contact Nuaire for specific documents.

Before any work is carried out, please ensure that:

The power supply to the motor is switched off.

The fan impeller is at rest.

Measures are taken to ensure that the accidental, uncontrolled run-
ning of the fan is prevented during maintenance work. 

In general, fans should be inspected twice a year, and care should be taken to    
ensure that any unusual vibration or sound is investigated as an urgent matter.

Access to the fan section is via hinged or lift-off panels. Cable entry must be 
made through the apertures provided. Screwed glands with cable restraint 
devices should be used.

Access to the fan is normally gained by opening the hinged  access 
doors.

Care should be taken to remove any build up of dust (a light vacuum 
or light brushing will normally take care of this) Do not use a steam 
or any other high pressure cleaners.

Inspect the connection between the fan and unit for any damage or    
wear and tear.

When removing the filter access panels, pay attention to the airflow direction 
marked on the panel, this must be replaced to the exact position prior to being 
removed. Disposable filters should be checked, and changed when they become 
fully laden with dust. Washable filters should be removed and washed in a mild 
detergent, flushed with clean water and allowed to dry before refitting.

IMPORTANT

Isolation - Before commencing work make sure that the unit 

is electrically isolated from the mains unit and sufficient time has 

passed to allow the fans to run down (5 minutes minimum).

11.4 Heating & Cooling Coils

11.5 Plate Heat Exchanger

Coils should be connected to ensure that full counter flow exists i.e. - the 

entering airflow meets the return connection.

All coils should be connected with the flow at the bottom and the return at the 

top unless otherwise advised. Drain and bleed valves are located on the coil, 

others may be required in the system pipe-work depending on the installation.

Frost protection must be incorporated on shut down and fresh air conditions 

to avoid coil freezing. Ideally, where the system is at risk of frost damage, the 

addition of a proprietary antifreeze solution to the water is recommended.

Pipe-work connections should be made to the unit using appropriate techniques, 

and must be independently supported. The connections should be pressure 

tested. 

All coils sit in a common drip tray connected to the pre-fitted

condensate pump.

The coil panel has been pre-drilled and fitted with appropriate

grommets for pipe connections. Do not drill or cut the unit casing for

this purpose. 

Coils should have their finned surface examined for accumulation of dirt, lint
and biological contaminants or similar. If necessary, wash down affected areas 
with a mild detergent solution and a soft brush. Care should be taken not to 
damage the finned surface, and any cleaning fluids should be rinsed away with 
water.

A compressed air line may be used to blow out any solids between fins. Do
not probe the coil fin block with metal objects as damage may cause leaks.
Drain lines should be checked to ensure that they are unobstructed and free
draining. Drain pans should be flushed out periodically to remove 
contamination.

Note: The unit application may require particular attention to this item –
Check with Building Management personnel for details.

The recuperator block is normally protected from dust and contamination by 
upstream pre-filters. It is possible to clean the unit with compressed air in the 
case of dust deposits or by spraying with a mild detergent solution for grease 
deposits.

Solvents, strong alkaline, acidic or any products that may be aggressive to 
aluminium or plastics should not be used. Do not use cleaning water over         
50 deg C.

Drain lines should be checked to ensure that they are unobstructed and free 
draining. Traps should be checked that they are fully primed and functioning.

Drain pans should be flushed out periodically to remove contamination, and 
chemical treatments may be used to provide protection between service visits.

Note: The unit application may require particular attention to this item –
Check with Building Management personnel for details.

IMPORTANT

Isolation - Before commencing work make sure that the unit 

is electrically isolated from the mains unit and sufficient time has 

passed to allow the fans to run down (5 minutes minimum).

IMPORTANT

If the unit contains a thermal wheel heat exchanger, please 

ensure that the rotation sensor is aligned with the sensing studs, as 

this can become misaligned during

transport/installation thus causing a fault signal.

Содержание ecosmart CONNECT BPS

Страница 1: ...828 nuaire co uk 029 2085 8200 Horizontal BPS with INSTALLATION MAINTENANCE INSTRUCTIONS Control 2016 ErP COMPLIANT LEAKAGE CLA SS T H E R MAL RID G I N G CLA SS TB1 D EFLECTIO N CL A SS D1 FOR THE CO...

Страница 2: ...Reverse Cycle coil is supplied as standard with Mitsubishi Mr Slim Condenser s and inbuilt PAC Control Note control wiring and piping by others thermistor wiring included Installation must be carried...

Страница 3: ...ontal PHX Units Frost Coil LPHW 3 B AH FL R BPS size Frost Coil LPHW Right Handed for Horizontal PHX Units B AH FL L BPS size Frost Coil LPHW Left Handed for Horizontal PHX Units Recirculation Module...

Страница 4: ...During installation commissioning operation and maintenance of an air handling unit operatives may be exposed to hazards including rotating components refrigerants and high voltage electricity If misu...

Страница 5: ...isplayed on the packaging Some of the modules have an uneven weight distribution and this will be indicated by labelling where appropriate Offloading and positioning of the equipment is the responsibi...

Страница 6: ...covered fork lifting channels are located across the width of the base frame if the module length is sufficient to allow this For shorter modules the fork lifting points will be along the length of t...

Страница 7: ...e 7 Air leakage air blow marks to the unit casings and unacceptable noise levels could result if the correct installation procedures are not employed The equipment must be stored in a dry internal loc...

Страница 8: ...be removed prior to operation of the thermal wheel module IMPORTANT If a frost coil is not fitted then appropriate control methods must be taken to prevent the coils filters and other equipment from...

Страница 9: ...32 and 42 the pre assembled dampers and terminals are provided with lifting eyes for on site hoisting into position see Figure 11 below Thoroughly inspect the unit after installation is complete The i...

Страница 10: ...nit filters may be changed and the fans coils heat exchanger and condensate tray may be inspected and cleaned if necessary 3 The LPHW and Electrical heater settings coil bleed and drain and all other...

Страница 11: ...ed Extract Supply Intake Exhaust Model shown is right handed Figure 14 Access for horizontal plate heat exchanger units Right and Left handed EXTRACT SUPPLY INTAKE DISCHARGE Access Shown from top Left...

Страница 12: ...se ensure that the condensate hose is connected between modules Care must be taken to ensure a constant fall in gradient is maintained and the hose is kept taught see Figure 15 Access is available in...

Страница 13: ...upply contactor Denotes any character These values do NOT include the condenser units which are powered by a separate supply See the table below or condenser manual Single heater models require a sepa...

Страница 14: ...Heat demand the relay is powered when heating is selected Cool demand the relay is powered when cooling is selected A fan start delay can be imposed to allow the damper time to open This is adjustabl...

Страница 15: ...TERMINAL BLOCKS The earth terminal block green yellow has a direct electrical connection to the DIN rail with the earthing foot earth connection only TERMINATION OF FINE STANDED CONDUCTORS Open the cl...

Страница 16: ...Figure 19 Main wiring points for the customer is to the isolators situated on the sides of the units as shown below Note Cable glands for additional ancillary cabling ISOLATOR POSITIONED ON ELECTRIC H...

Страница 17: ...ed to reference the required connection and wiring diagrams Example Unit onsite has code B815H ER CO L This indicates a size 15 unit with electric heating and reverse cycle cooling Section 9 4 and 9 1...

Страница 18: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART CONNECT CONTROL CO 8 2 Basic Connection Diagram BPS Sizes 05 10 15 20 No Condenser Control Figure 20...

Страница 19: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 19...

Страница 20: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART CONNECT CONTROL CO 8 3 Basic Connection Diagram BPS RC Sizes 05 10 with Mitsubishi Reverse Cycle DX Control Figure 21...

Страница 21: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 21...

Страница 22: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART CONNECT CONTROL CO 8 4 Basic Connection Diagram BPS RC Sizes 15 20 with Mitsubishi Reverse Cycle DX Control Figure 22...

Страница 23: ...28 BOXER BPS ECOSMART CONNECT CONTROL CO 23 F Engineering Projects Project Data Platinum I Ms EcoSmart Connect Drawings Connect Connection Diagrams Connect Connection Diagrams dwg 07 11 2017 09 45 43...

Страница 24: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART CONNECT CONTROL CO 8 5 1 BPS Internal Wiring Sizes 05 20 No Heating or LPHW Sheet 1 8 5 BPS Internal Wiring Sizes 05 20 No Heating or LPHW Figure 23...

Страница 25: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 25...

Страница 26: ...085 8200 BOXER BPS ECOSMART CONNECT CONTROL CO F Engineering Projects Project Data Platinum I Ms EcoSmart Connect Drawings Connect Control Sch 8 5 2 BPS Internal Wiring Sizes 05 20 No Heating or LPHW...

Страница 27: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 27 hematics Connect Control Diagrams dwg 07 11 2017 09 42 47 AutoCAD PDF Smallest File pc3...

Страница 28: ...ONTROL CO F Engineering Projects Project Data Platinum I Ms EcoSmart Connect Drawings Connect Control Schematics Connect Control 8 6 BPS Internal Wiring Sizes 05 20 Electric Heating 8 6 1 BPS Internal...

Страница 29: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 29 Diagrams dwg 07 11 2017 09 42 49 AutoCAD PDF Smallest File pc3...

Страница 30: ...085 8200 BOXER BPS ECOSMART CONNECT CONTROL CO F Engineering Projects Project Data Platinum I Ms EcoSmart Connect Drawings Connect Control Schema 8 6 2 BPS Internal Wiring Sizes 05 20 Electric Heating...

Страница 31: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 31 atics Connect Control Diagrams dwg 07 11 2017 09 42 51 AutoCAD PDF Smallest File pc3...

Страница 32: ...ER BPS ECOSMART CONNECT CONTROL CO 8 7 BPS Internal Wiring Sizes 05 10 No Heating or LPHW with Mitsubishi Reverse Cycle DX 8 7 1 BPS Internal Wiring Sizes 05 10 No Heating or LPHW with Mitsubishi Reve...

Страница 33: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 33...

Страница 34: ...NNECT CONTROL CO F Engineering Projects Project Data Platinum I Ms EcoSmart Connect Drawings Connect Control Schematics Connect Control Diag 8 7 2 BPS Internal Wiring Sizes 05 10 No Heating or LPHW wi...

Страница 35: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 35 grams dwg 07 11 2017 09 42 57 AutoCAD PDF Smallest File pc3...

Страница 36: ...ject Data Platinum I Ms EcoSmart Connect Drawings Connect Control Schematics Connect Control Di 8 8 BPS Internal Wiring Sizes 15 20 No Heating or LPHW with Mitsubishi Reverse Cycle DX 8 8 1 BPS Intern...

Страница 37: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 37 iagrams dwg 07 11 2017 09 42 58 AutoCAD PDF Smallest File pc3...

Страница 38: ...NNECT CONTROL CO F Engineering Projects Project Data Platinum I Ms EcoSmart Connect Drawings Connect Control Schematics Connect Control Diag 8 8 2 BPS Internal Wiring Sizes 15 20 No Heating or LPHW wi...

Страница 39: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 39 grams dwg 07 11 2017 09 43 00 AutoCAD PDF Smallest File pc3...

Страница 40: ...oject Data Platinum I Ms EcoSmart Connect Drawings Connect Control Schematics Connect Control Diag 8 9 BPS Internal Wiring Sizes 05 10 Electric Heating with Mitsubishi Reverse Cycle DX 8 9 1 BPS Inter...

Страница 41: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 41 grams dwg 07 11 2017 09 43 05 AutoCAD PDF Smallest File pc3...

Страница 42: ...ONNECT CONTROL CO F Engineering Projects Project Data Platinum I Ms EcoSmart Connect Drawings Connect Control Schematics Connect Control Diag 8 9 2 BPS INTERNAL WIRING Sizes 05 10 Electric Heating wit...

Страница 43: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 43 grams dwg 07 11 2017 09 43 07 AutoCAD PDF Smallest File pc3...

Страница 44: ...XER BPS ECOSMART CONNECT CONTROL CO 8 10 1 BPS Internal Wiring Sizes 15 20 Electric Heating with Mitsubishi Reverse Cycle DX Sheet 1 8 10 BPS Internal Wiring Sizes 15 20 Electric Heating with Mitsubis...

Страница 45: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 45...

Страница 46: ...NNECT CONTROL CO F Engineering Projects Project Data Platinum I Ms EcoSmart Connect Drawings Connect Control Schematics Connect Control Diag 8 10 2 BPS Internal Wiring Sizes 15 20 Electric Heating wit...

Страница 47: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 47 grams dwg 07 11 2017 09 43 10 AutoCAD PDF Smallest File pc3...

Страница 48: ...the heater supply contactor The frost coil is fitted with a burst fired controller with integral setpoint air off thermistor air in frost stat thermal cut out and contactor The burst fired controller...

Страница 49: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 49 9 4 Electric Heater Frost Coil Wiring BPS Sizes 05 10 15 20 Figure 36...

Страница 50: ...off temperature is set by the end user via the adjustment dial Eg ESCO TDS If no display room modules are fitted the controller setpoint can be adjusted by changing the BACnet Software Setpoint objec...

Страница 51: ...ld be connected to ensure that full counter flow exists i e the entering airflow meets the return connection All coils should be connected with the flow at the bottom and the return at the top unless...

Страница 52: ...e Function of slide seal Function of transverse seal Condition of casing Condition of wheel Remove dust and fibres with a soft brush or vacuum cleaner Use caution when blowing dirt out with compressed...

Страница 53: ...e is modified or removed Nuaire will accept warranty on the hardware unit provided the replacement does not control the unit beyond its specified limits refer to Nuaire testing standards and Applicati...

Страница 54: ...Equipment stored on site prior to installation should be protected from the weather and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified op...

Страница 55: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 55 NOTES...

Страница 56: ...strial Estate Caerphilly CF83 1NA t 44 0 29 2085 8200 f 44 0 29 2085 8222 e info nuaire co uk www nuaire co uk 05 11 20 Leaflet Number 671828 As part of our policy of continuous product development Nu...

Отзывы: