7.0 DESCRIPTION OF CONTROL - SOFTWARE STRATEGY

A comprehensive unit

control specification -

factory fitted and tested

to provide guaranteed

operation from a

single supplier – one who

will take responsibility.

7.1 GENERAL

The system incorporates a web enabled Trend iQ4E/96/LAN/BAC/230 
controller with iQ4/IO/8DO relay expansion module. 

7.2 UNIT CONTAINS THE FOLLOWING CONTROLLABLE ITEMS:

7.3 ENABLE SIGNAL

 Supply fan.

 Extract fan.

 Heat recovery bypass damper (If applicable).

 Thermal wheel (if applicable).

 Heating coil (if fitted).

 Cooling coil (if fitted).

DX coil (if fitted).

Inlet damper (if fitted).

Exhaust Damper (if fitted).

Recirculation damper (if fitted).

 The unit can be enabled via the following methods:

 Software switch (ENABLE) via SDU, IQView4, IQView8 or network.

 Switched live (230VAC) input, PIR etc.

 Extra Low voltage contacts.

 Night cooling / summer free-cooling strategy.

 Scheduled via weekly calendar.

When the enable signal is removed, the unit will run on for a time defined by the 
run-on setpoint. If an electric heater is fitted, the fans will automatically run-on 
for an extra 2 minutes, without heating, in order to dissipate residual heat. 
For DX units the fans will run-on for an extra 5 minutes, this is to allow for the 
ramp down of the reverse cycle compressor. 

7.4 OCCUPANCY CONTROL

7.5 BOOST

7.10 INLET / OUTLET (OPTIONAL)

7.7 PRESSURE SENSOR

7.8 FILTER DP SWITCH

7.9 THERMAL WHEEL / PLATE HEAT EXCHANGER BYPASS

7.6 TRICKLE MODE

When a Trend occupancy sensor is selected via UI4 & 5 software module, the 
control will look for a Trend OCC-U sensor in the appropriate input.
An occupied signal will give an enable signal.
0V = Occupied
14V = Unoccupied

When the control receives a boost signal the fans will run at boost speed. Once 
the signal is removed the fans will run on for a time defined by the boost run-on 
setpoint.

Inlet and outlet dampers are 24vac and controlled by the iQ4-8DO relay 7. 
When energised it gives a 24vac signal to both I/O dampers to open.

When installed, there is the option of connecting the internal damper close 
switch to the fault circuit alarm circuit 2 (orange wires). 

When IO dampers are fitted the strategy Switch “IO Damper Fitted” must be set 
to “On”. This will cause the software to delay the fans starting for the IO Damper 
delay period. It will also ignore faults on Alarm Circuit 2 if the fans are stopped 
and the dampers are closed intentionally.

See Internal connection section for physical damper connections.

An extract air pressure sensor is fitted as standard. This is disabled in the Trend 
strategy by default but can be enabled by the software switch “Enable Constant 
Pressure”. 
When enabled, the unit will increase the fans speeds as required until the 
pressure differential between the extract air and atmosphere reaches the 
constant pressure setpoint. The pressure sensor is a 0-10v 0-1000Pa sensor on 
the iQ4E input 6.

3 filter differential pressure switches are fitted as standard. These monitor the 
Extract filter, and Supply filter and Supply pre-filters.
These are connected in series with Alarm Circuit 2 (orange wires) and will break 
the circuit on overpressure. The adjustable range is 0.5 to 4 mbar and is set by 
default to 2mbar.

The plate heat exchanger bypass damper and thermal wheel both run on the 
same iQ4-8DO Relay 1. Energised = Bypass.
The bypass strategy is as follows.
If the fresh air temperature is equal to the setpoint within the deadband, then 
the heat exchanger will be forced into bypass mode.
The 24vac bypass signal from the Trend relay is converted by relay logic for each 
of the following options:

Thermal Wheel 
Runs on a volt free enable signal, which is produced using a combination 
of the HX bypass relay and fan run relay to close the circuit if fans are 
running and the unit is not in bypass.

Plate Heat Exchanger 
The HX bypass damper opens on a 24 Vac signal which is produce from the 
bypass damper relay.

When trickle mode is active, the fans will run at their minimum speed even when 
there is no enable signal. Heating and cooling will also function in this mode if 
available.

Содержание B815H/ER/AT-L

Страница 1: ...r 671761 Horizontal BPS with INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS Trend Control 2016 ErP COMPLIANT LEAKAGE CLA SS T H E R MAL RID G I N G CLA SS TB1 D EFLECTIO N CL A SS D1 FOR THE COMPLETE...

Страница 2: ...1 0 UNIT INTRODUCTION 3 2 0 HEALTH SAFETY 5 3 0 DELIVERY RECIEPT OF EQUIPMENT 6 4 0 ERECTION ASSEMBLY 8 5 0 ACCESS TO UNITS 11 6 0 INTERNAL CONNECTIONS 13 7 0 CONTROL STRATEGY 14 8 0 ELECTRICAL DETAIL...

Страница 3: ...verse Cycle coil is supplied as standard with Mitsubishi Mr Slim Condenser s and inbuilt PAC Control Note control wiring and piping by others thermistor wiring included Installation must be carried ou...

Страница 4: ...d for Horizontal PHX Units Frost Coil LPHW 3 B AH FL R BPS size Frost Coil LPHW Right Handed for Horizontal PHX Units B AH FL L BPS size Frost Coil LPHW Left Handed for Horizontal PHX Units Recirculat...

Страница 5: ...d to During installation commissioning operation and maintenance of an air handling unit operatives may be exposed to hazards including rotating components refrigerants and high voltage electricity If...

Страница 6: ...he packaging Some of the modules have an uneven weight distribution and this will be indicated by labelling where appropriate Offloading and positioning of the equipment is the responsibility of the p...

Страница 7: ...this covered fork lifting channels are located across the width of the base frame if the module length is sufficient to allow this For shorter modules the fork lifting points will be along the length...

Страница 8: ...5 Air leakage air blow marks to the unit casings and unacceptable noise levels could result if the correct installation procedures are not employed The equipment must be stored in a dry internal loca...

Страница 9: ...with the requirements of BS EN 378 Units must be fitted with gas detection systems or deploy other suitable control method to ensure that in the event of a refrigerant leak the Lower Flammability Limi...

Страница 10: ...gs The inlet outlet dampers and roof terminals are pre assembled on a single skinned panel The panel is easily fitted to the unit with a series of quarter turns provided with a locking key See fig 8a...

Страница 11: ...enience it is preferred that wherever possible this minimum access provision is not adopted and it is recommended that a minimum of around 600mm clearance as stated in ADF 2010 is allowed 6 Where thes...

Страница 12: ...s left handed Extract Supply Intake Exhaust Model shown is right handed Figure 11 Access for horizontal plate heat exchanger units Right and Left handed EXTRACT SUPPLY INTAKE DISCHARGE Access Shown fr...

Страница 13: ...en the Supply Module and the Heat exchanger module The recirculation section is pre fitted with all the relevant looms and is plug and play into the standard Supply and HX sections Each section must b...

Страница 14: ...hen energised it gives a 24vac signal to both I O dampers to open When installed there is the option of connecting the internal damper close switch to the fault circuit alarm circuit 2 orange wires Wh...

Страница 15: ...units for use with Mitsubishi reverse cycle condenser units one or more PACIF012B E Interface boards are fitted inside the control panel The controller interacts with this board in the following ways...

Страница 16: ...rce Recirc damper to recirc mode On Off Off 52 Damper NoRecirc Force Recirc damper out of recirc mode On Off Off Knob No Name Description Range Default 2 Run on Time Run on timer value 0 3600 Sec 0 se...

Страница 17: ...10 v 10 v 32 Extract Fan Voltage Limit The maximum voltage to be supplied to the fan motor 6 10 v 10 v 41 CP Loop Gain Constant Pressure Loop Gain 0 50 0 5 42 IO Damper Delay Delay to allow inlet outl...

Страница 18: ...elease lid duct sensor Two part terminals to facilitate wiring 24 Vac dc supply Adjustable depth duct mounting flange option FEATURES Pre calibrated for ease of commissioning IP65 Operates over 10 to...

Страница 19: ...ter supply contactor Denotes any character These values do NOT include the condenser units which are powered by a seperate supply See the table below or condenser manual Single heater models require a...

Страница 20: ...at the volt free contacts are not fused If these are used to power any external equipment the installer must provide adequate fusing or other protections Trend 8D relays are rated at 5A 240Vac resisti...

Страница 21: ...rminals EARTH TERMINAL BLOCKS The earth terminal block green yellow has a direct electrical connection to the DIN rail with the earthing foot earth connection only TERMINATION OF FINE STANDED CONDUCTO...

Страница 22: ...L DETAILS Figure 9 Main wiring points for the customer is to the isolators situated on the sides of the units as shown below Note Cable glands for additional ancillary cabling ISOLATOR POSITIONED ON E...

Страница 23: ...cooling is present The below tables can then be used to reference the required connection and wiring diagrams Example Unit onsite has code B815H ER AT L This indicates a size 15 unit with electric hea...

Страница 24: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 CONNECTION WIRING DIAGRAMS 9 2 BASIC CONNECTION DIAGRAM BPS Sizes 05 10 15 20 No Condenser Control...

Страница 25: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 25 Figure 10...

Страница 26: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 4 BASIC CONNECTION DIAGRAM BPS RC Sizes 05 10 with Mitsubishi Reverse Cycle DX Control...

Страница 27: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 27 Figure 11...

Страница 28: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 5 BASIC CONNECTION DIAGRAM BPS RC Sizes 15 20 with Mitsubishi Reverse Cycle DX Control...

Страница 29: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 29 Figure 12...

Страница 30: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 7 BPS INTERNAL WIRING Sizes 05 20 No Heating or LPHW Sheet 1...

Страница 31: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 31 Figure 13...

Страница 32: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 7 BPS INTERNAL WIRING Sizes 05 20 No Heating or LPHW Sheet 2...

Страница 33: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 33 Figure 14...

Страница 34: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 8 BPS INTERNAL WIRING Sizes 05 20 Electric Heating Sheet 1...

Страница 35: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 35 Figure 15...

Страница 36: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 8 BPS INTERNAL WIRING Sizes 05 20 Electric Heating Sheet 2...

Страница 37: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 37 Figure 16...

Страница 38: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 10 BPS INTERNAL WIRING Sizes 05 10 No Heating or LPHW with Mitsubishi Reverse Cycle DX Sheet 1...

Страница 39: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 39 Figure 17...

Страница 40: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 10 BPS INTERNAL WIRING Sizes 05 10 No Heating or LPHW with Mitsubishi Reverse Cycle DX Sheet 2...

Страница 41: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 41 Figure 18...

Страница 42: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 11 BPS INTERNAL WIRING Sizes 15 20 No Heating or LPHW with Mitsubishi Reverse Cycle DX Sheet 1...

Страница 43: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 43 Figure 19...

Страница 44: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 11 BPS TREND INTERNAL WIRING Sizes 15 20 No Heating or LPHW with Mitsubishi Reverse Cycle DX Sheet 2...

Страница 45: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 45 Figure 20...

Страница 46: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 13 BPS INTERNAL WIRING Sizes 05 10 Electric Heating with Mitsubishi Reverse Cycle DX Sheet 1...

Страница 47: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 47 Figure 21...

Страница 48: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 13 BPS INTERNAL WIRING Sizes 05 10 Electric Heating with Mitsubishi Reverse Cycle DX Sheet 2...

Страница 49: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 49 Figure 22...

Страница 50: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 14 BPS INTERNAL WIRING Sizes 15 20 Electric Heating with Mitsubishi Reverse Cycle DX Sheet 1...

Страница 51: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 51 Figure 23...

Страница 52: ...nuaire co uk 029 2085 8200 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 9 0 DIAGRAMS 9 14 BPS INTERNAL WIRING Sizes 15 20 Electric Heating with Mitsubishi Reverse Cycle DX Sheet 2...

Страница 53: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 53 Figure 24...

Страница 54: ...re fitted with its own internal control panel The control is powered by a 400Vac 50Hz 3 phase Neutral supply This must be isolated local to the unit and fitted with appropriate overcurrent and fault p...

Страница 55: ...05 11 20 Leaflet Number 671829 BOXER BPS ECOSMART ADAPT TREND CONTROL AT 55 Figure 26 10 2 1 ELECTRIC HEATER FROST COIL WIRING BPS Sizes 05 10 15 20...

Страница 56: ...fan section is via hinged or lift off panels Cable entry must be made through the apertures provided Screwed glands with cable restraint devices should be used Access to the fan is normally gained by...

Страница 57: ...RTANT If the unit contains a thermal wheel heat exchanger please ensure that the rotation sensor is aligned with the sensing studs as this can become misaligned during transport installation thus caus...

Страница 58: ...dust removed Thoroughly inspect the unit and its components for corrosion acting immediately to treat restore any damaged areas Check all earth connections Check thermal wheel belt motor bearings seal...

Страница 59: ...quipment stored on site prior to installation should be protected from the weather and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified oper...

Страница 60: ...strial Estate Caerphilly CF83 1NA t 44 0 29 2085 8200 f 44 0 29 2085 8222 e info nuaire co uk www nuaire co uk 05 11 20 Leaflet Number 671829 As part of our policy of continuous product development Nu...

Отзывы: