Nuaire Group MRXBOX95B-LOFT Скачать руководство пользователя страница 5

5

Leaflet Number 671453 January 2011

Installation and Maintenance

MRXBOX95B-LOFT Mechanical Ventilation with Heat Recovery & Summer Bypass

Optional Connections

Ecosmart control 

(see figure 5a)

(a) J11/12/13

The IDC plug-in connectors are provided for the connection of

compatible sensors. 

NOTE: Do not run the data cable in the same conduit as the

mains cable and leave a 50mm separation with any power

cables.

(b) Volt Free Relay Contacts 

Note that the volt free contacts are not fused. If these are used

to power any external equipment, the installer must provide

adequate fusing or other protections. These contacts are rated

at 5A resistive, 0.5A inductive.

Run connections (J5)

- These contacts are closed when the

fan is running.

Fault connections (J7)

- No fault = the contacts are closed.

Fault

= the contacts are opened (this includes no power supply

at the unit).

(c) Data Cable installation

A 4-core data cable is used to connect devices such as sensors

to the fan and for interconnecting multiple fan units.

Do not run data cable in the same conduit as the mains cables

and ensure there is a 50mm separation between the data cable

and other cables. The maximum cable run between any two

devices is 300m when it is installed in accordance with the

instructions.

Please note that the total data cable length used in any system

must be less than 1000m. Keep the number of cable joints to a

minimum to ensure the best data transmission efficiency

between devices.

LED Indication

PWR GREEN: 

Power on and OK,

RED: 

Standby LED on when fan is not running. 

As the unit runs continuously this LED should 

be off. If it is illuminated locate the trickle 

switch and change its position.

Fan 1 GREEN:

Fan 1 is running, 

RED:

Fan 1 faulty.

Fan 2 GREEN: 

Fan 2 is running, 

RED:

Fan 2 faulty.

5.0  Ancillaries

Passive Infra red detector

MRXBOX95-PIR

External Humidity sensor

MRXBOX95-HUM

Remote Fail Indicator

MRXBOX95-RFI

Electrical connection cont.

Содержание MRXBOX95B-LOFT

Страница 1: ...t the four L shape fixing brackets to the unit with the M4 screws provided they can be attached to the long or short sides of the unit depending on requirements Each pair of brackets should be mounted...

Страница 2: ...of 90 Deg bends be kept to a minimum 5 Ducting joints must be sealed with duct tape and or silicone sealant For further information refer to Building Regulations Part F and BRE appendix Q website Any...

Страница 3: ...n alternative position 125mm dia spigot Alternative 150mm dia spigot 3 alternative 150mm dia spigots on back of unit 3 0 Dimensions mm Figure 4 Main unit components shown with front and lid removed G4...

Страница 4: ...other cables 4 0 Electrical Connection Please note the electrical connection of the unit must be be carried out by a qualified electrician The unit is supplied with a flexible cord for connection to t...

Страница 5: ...ata Cable installation A 4 core data cable is used to connect devices such as sensors to the fan and for interconnecting multiple fan units Do not run data cable in the same conduit as the mains cable...

Страница 6: ...years Generally check for damage and security of components Refit top cover 3 Inspecting motors Motors can be accessed through removal side panels 8 0 Replacement of Parts Should any component need r...

Страница 7: ...hange speed This is normal and will have no adverse effect on the fan The speed will return to normal once the interference has subsided 5 0 INSTALLATION REQUIREMENTS In addition to the particular req...

Страница 8: ...estern Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2088 5911 F 029 2088 7033 E info nuaire co uk W www nuaire co uk Technical or commercial considerations may from time to time make it...

Отзывы: