Nuaire Group MRXBOX95B-LOFT Скачать руководство пользователя страница 4

4

Leaflet Number 671453 January 2011

Installation and Maintenance

MRXBOX95B-LOFT Mechanical Ventilation with Heat Recovery & Summer Bypass

Fuse 2A

MAINS
230V
50Hz

Room
light

Light 

switch 

(Double 

Pole)

N

L

3 Pole
isolator

Kitchen switch

Green/yellow

Blue

Brown

Black

Summer
bypass
switch

Grey (only used
on bypass unit)

Supply cord
from unit

Unit serving kitchen and bathroom

Unit serving kitchen and two bathrooms

Fuse 2A

MAINS
230V
50Hz

Room
lights

Light 

switches 

(Double 

Pole)

N

L

3 Pole
isolator

Kitchen switch

Green/yellow

Blue

Brown

Black

Summer
bypass
switch

Grey (only used
on bypass unit)

Supply cord
from unit

Figure 6. 

Figure 7. 

For good EMC engineering practice, any sensor cables 

or switched live cables should not be 

placed within 50mm of other cables or on the same 

metal cable tray as other cables.

4.0  Electrical Connection

Please note: the electrical connection of the unit must be be carried
out by a qualified electrician.

The unit is supplied with a flexible cord for connection to the mains
supply.

Electrical details:-

Voltage:

240V  1ph  50Hz

Consumption:

75W (max) 0.6 amps

Fuse rating: 

3 Amp

NOTE This unit must be earthed

The three core cable from the mains power supply should be 
connected to a fixed wiring installation, via a fused isolator, in
accordance with current IEE wiring regulations.

SWL   N       L

Connections for 
optional controls

Volt free relay 
contacts.

 

Run

Switch to deactivate 
continuous trickle

Fan connections

230V IN
50Hz
Mains

Fault

Internal wiring

Connection to supply cord

Earth point

Bypass

SWL

(Grey)

Internal
wiring to
Bypass
Damper

2 Way
Terminal
Block

Figure 5a. Power supply PCB.

230V in, 24V dc out.

Figure 5b. 

Control PCB.

24V 

Note: Wiring is for reference purposes only as the 

connections above are factory fitted. 

The unit is pre-wired with a 2 metre fly lead.

Содержание MRXBOX95B-LOFT

Страница 1: ...t the four L shape fixing brackets to the unit with the M4 screws provided they can be attached to the long or short sides of the unit depending on requirements Each pair of brackets should be mounted...

Страница 2: ...of 90 Deg bends be kept to a minimum 5 Ducting joints must be sealed with duct tape and or silicone sealant For further information refer to Building Regulations Part F and BRE appendix Q website Any...

Страница 3: ...n alternative position 125mm dia spigot Alternative 150mm dia spigot 3 alternative 150mm dia spigots on back of unit 3 0 Dimensions mm Figure 4 Main unit components shown with front and lid removed G4...

Страница 4: ...other cables 4 0 Electrical Connection Please note the electrical connection of the unit must be be carried out by a qualified electrician The unit is supplied with a flexible cord for connection to t...

Страница 5: ...ata Cable installation A 4 core data cable is used to connect devices such as sensors to the fan and for interconnecting multiple fan units Do not run data cable in the same conduit as the mains cable...

Страница 6: ...years Generally check for damage and security of components Refit top cover 3 Inspecting motors Motors can be accessed through removal side panels 8 0 Replacement of Parts Should any component need r...

Страница 7: ...hange speed This is normal and will have no adverse effect on the fan The speed will return to normal once the interference has subsided 5 0 INSTALLATION REQUIREMENTS In addition to the particular req...

Страница 8: ...estern Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2088 5911 F 029 2088 7033 E info nuaire co uk W www nuaire co uk Technical or commercial considerations may from time to time make it...