1.0 Introduction

The WM1 wall mounted range of units is designed to provide
mechanical supply and extract ventilation with heat recovery.

The unit is fitted with two independent fans. Each fan has full speed
control for background and boost ventilation rates. 
To recover heat from the extract air the heat exchanger block is
utilised. The heat exchanger can recover up to 95% of the normally
wasted heat.

If the unit has integral automatic summer bypass (AB models
only) 

The bypass damper shall open automatically via a wax 

actuator allowing the air to bypass the heat exchanger to deliver
fresh filtered air during the warmer months.

2.0 Installation

Installation must be carried out by competent personnel in 
accordance with the appropriate authority and conforming 
to all statutory governing regulations. All mains wiring must be in
accordance with the current I.E.E. Regulations, or the appropriate
standards. Ensure that the mains supply (Voltage, Frequency and
Phase) complies with the rating label. 

Please note a clear working space is required around the installed
unit to allow the cover to be removed and provide sufficient access
for maintenance such as filter change.
Please allow a minimum of 280mm in front of the unit.

The fan must be installed indoors, on a suitable wall away from
direct sources of frost, heat, water spray or moisture generation. 
For a vibration-free result the unit must be mounted to a solid wall.

2.1 Wall Mounting the MVHR Unit

The unit is designed for wall mounting, only on a solid wall. 
A gypsum block or stud/plasterboard wall will not suffice.

1. One part of the mounting bracket (supplied) should be offered up
to the wall, ensuring it’s located horizontally. Mark the fixing points
through the pre drilled holes in the bracket and install with screws
(by others), ensuring the interlock side is at the top, (fig. 3). 

Figure 3. Fixing the mounting bracket to the wall.

2. Install the unit on the wall by ensuring the bracket fixed to the
rear of the unit interlocks over the wall mounted bracket (fig. 4).

Figure 4. Mounting the unit on the wall mounted bracket.

Note: Care must be taken to ensure the unit is installed true in 
all 3 dimensions. Failure to do so may result in overflow from the
internal condensation drip tray.

(See overleaf for wall mounting option details).
Note: the unit is not recommended for loft mounting.

The unit must remain switched on at all times to maintain 
ventilation within the dwelling. Turning the unit off will cause
long term damage to the unit and building fabric.

This appliance is not intended for use by persons (including 
children) with reduced physical, sensory or mental capabilities,
or lack of experience and knowledge, unless they have been
given supervision or instruction concerning the use of the 
appliance by a person for their safety. Children should be 
supervised so that they do not play with the appliance.

Installation and Maintenance

MRXBOX95-WM1 (Standard Unit)
MRXBOX95-WM1-OH (Opposite hand Unit)
MRXBOX95AB-WM1 (Standard Unit)
MRXBOX95AB-WM1-OH (Opposite hand Unit)

Mechanical Ventilation Units with Heat Recovery for Wall Mounting

Nuaire Limited

Western Industrial Estate  Caerphilly  United Kingdom  CF83 1NA 

T: 029 2085 8400  F: 029 2085 8444  E: [email protected]  W: www.nuaire.co.uk

1

09. 06. 16. Leaflet Number 671684

Extract air 
from house

Intake air 
from outside

Exhaust air 
from house
to outside

Supply air 
to house

Figure 1. Airflow through unit (Standard unit).

Figure 2. Airflow through OH unit (Opposite hand unit).

Intake air 
from outside

Extract air 
from house

Supply air 
to house

Exhaust air 
from house
to outside

The EMC Directive 
2014/30/EU  
The Low Voltage 
Directive 
2014/35/EU

Содержание BPC MRXBOX95-WM1

Страница 1: ... the pre drilled holes in the bracket and install with screws by others ensuring the interlock side is at the top fig 3 Figure 3 Fixing the mounting bracket to the wall 2 Install the unit on the wall by ensuring the bracket fixed to the rear of the unit interlocks over the wall mounted bracket fig 4 Figure 4 Mounting the unit on the wall mounted bracket Note Care must be taken to ensure the unit i...

Страница 2: ...Figure 5 Typical example of a cupboard mounted unit Standard unit fixed to a block work wall Option 2 Wall Mounting If it is not practical to use a solid wall the MVHR unit should be fixed to a stud partition with a 25mm minimum thickness MDF panel solidly fixed behind the plasterboard If fixing to a stud wall the MDF panel should extend width wise over a minimum of 3 vertical studs with centres o...

Страница 3: ...pt to a minimum A minimum distance of 300mm between the appliance and any bends in ductwork is recommended Ideally 150mm diameter or 204 x 60mm rectangular ducting should be used Refer to dwelling design drawing figure 9a and 9b on page 5 for further information Ducting joints must be sealed with silicone type sealant and shall be adequately and reliably fixed to the appliance 2 6 Ventilation flow...

Страница 4: ...ly as an alternative the purge ventilation provisions given in ADF 2010 can be used where security is not an issue In this case minimum high extract rate for the sanitary accommodation should be omitted from the step 2 calculation Step 3 The required airflow rates are as follows n the maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note...

Страница 5: ...upply duct Air supply to lounge via Air Valve in ceilings Extract air from kitchen bathroom via Air Valve in ceilings Air supply to bedrooms via Air Valve in ceilings Top of ceiling void Top of ceiling void Nuaire wall mounted unit Air supply to bedrooms via Air Valve in ceilings Nuaire wall mounted unit MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall running to SVP MVHR DRAIN ...

Страница 6: ...ure 10 The IDC plug in connectors are provided for the connection of compatible sensors NOTE Do not run the data cable in the same conduit as the mains cable and leave a 50mm separation with any power cables Fuse 2A MAINS 230V 50Hz Room light Light switch Double Pole N L Fuse 2A MAINS 230V 50Hz Room lights Light switches Double Pole N L 3 Pole isolator 3 Pole isolator Kitchen switch Kitchen switch...

Страница 7: ...ngportal gov uk building regulations approved documents partf associated A calibrated moving vane anemometer and hood will be required to carry out commissioning 5 Adjustment valves should be locked in place to prevent further adjustment 6 Once commissioned the home owner tenant should be informed that the unit should not be adjusted as it will have a detrimental effect on the indoor air quality a...

Страница 8: ...ectrically competent person When ordering spare parts please quote the serial number of the unit and the ARC number of the purchase if possible This information will be available on the fan label 11 0 Warranty The 5 year warranty starts from the day of delivery and includes parts and labour for the first year and parts only for the remaining 4 years This warranty is conditional on planned maintena...

Страница 9: ...lings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SAP 2005 Customer Details Customer Name Address Telephone Number Date of Installation Name of Lead Contractor Design Project Number It should be noted that this guidance is not intended to replace product manufactur...

Страница 10: ...or to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequate air flow and least resistance Bends should have a minimum radius at least the same as the diameter of the ducting used Refer to Figure 1 if using flexible ducting Have the fans and ducting placed in unheated vo...

Страница 11: ...ry unit been fixed to a stable element of the building fabric e g wall or floor using manufacturer recommended supplied fixing brackets Has the condensation drain been fitted and the pipe insulated Have approved acoustic anti vibration mountings been used Note Special attention is needed to avoid transmission and stress to duct joints Has the unit been installed in a position that will permit acce...

Страница 12: ... or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product status Has a local isolator been provided to enable the unit to be isolated for maintenance purposes Has the unit been fused in accordance with its power rating SECTION 2 COMMISSIONING GUIDANCE ...

Страница 13: ...ution grilles been locked where possible to minimise unapproved occupant adjustment Figure 3 Ensure all external and internal windows and doors are closed Set fan speed using manufacturer data table Set normal daytime air flow on extract points starting at location furthest from unit Set normal daytime air flow on input points starting at location furthest from unit Step 1 Step 2 Step 3 Step 4 Ste...

Страница 14: ...he customer been advised that opening windows is not recommended during normal use in order to ensure the energy efficient operation and performance of the balanced system Has the customer been advised not to seal natural air flows from room to room e g avoid door seals and thick pile carpets Has the customer been advised not to alter settings post commissioning Has the customer been advised to cl...

Отзывы: