Nu-Way NOL Скачать руководство пользователя страница 16

NOL Compact Modulating

Page 16

Control Program Under Fault Conditions

And Lockout Indication

In  the  event  of  fault  conditions  the  sequence

switch stops and simultaneously the lockout indi

cator.  The  symbol  appearing  above  the  reading

mark indicates the kind of fault encountered.

No start, 

because, e.g., the CLOSE signal has

not been supplied to control box terminal 8

by the servo motor limit or auxillary switch,

or  a  contact  has  not  been  closed  between

control box terminals 12 and 4 or 4 and 5.

Shut down of start up sequence, 

because

the  OPEN  signal  has  not  been  supplied  to

control  box  terminal  8  by  the  servo  motor

limit  switch.  Terminals  6,7  and  15  remain

under voltage until the fault is corrected.

Lockout 

due to a fault in the flame supervi

sion circuit.

Shut down of start up sequence, 

because

the signal for the low flame position has not

been supplied to control box terminal 8 by

the  servo  motor  auxillary  switch.  Terminals

6,7 and 15 remain under voltage until the

fault is corrected.

Lockout, 

because no flame signal has been

received on completion of the safety time.

Lockout, 

because the flame signal has been

lost during burner operation or an air pres

sure failure has occured.

Lockout on completion or after completion

of the control program sequence 

due to ex

traneous  light  (e.g.  flame  not  extinguished,

leaking fuel valves) or due to a faulty flame

signal (e.g. fault in the flame supervision cir

cuit or similar).

a - b

Start up sequence.

b - b’

idle steps up to the self shut down of

the sequence switch.

b(b’) - a

Post purge sequence.

When  lockout  occurs,  the  control  can  be  reset

immediately. After the resetting (and also after the

correction of a fault which resulted in a controlled

shut down,  or  after  each  mains  failure)  the  se

quence  switch  always  runs  through  to  the  start

position,  whereby 

only 

terminals  7,9,10  and  11

receive voltage in accordance with the control pro

gram. It is only then that the control unit programs

a fresh burner start up.

Note: 

Do  not  press  the  lockout  reset  button  (or

remote reset switch) for more than 10 seconds.

RWF40  M

ODULATING

  C

ONTROL

Basic display

The  diagram  below  opposite  shows  the  RWF40

after  switching  on  the  supply  voltage.    This

condition is called the basic display.  The actual

operating value and the currently active set point

will  be  shown.    Manual  operation,  self

optimization,  the  operating  parameter  and  the

configuration  levels  can  be  activated  from  this

display.

To change the working set point.

The  basic  display  shows  the  actual  pressure/

temperature of the boiler in red and the required

set point pressure/temperature beneath in smaller

green digits.
One quick press of the PGM button, the display

changes  to  show  the  set  point  as  the  larger  red

digits and the SPI in the lower small green digits.
Alter  the  red  display  using  the  up/down  buttons

to show the new required set point, press exit or

let the unit time out to return to the basic display

which should be the new set point figure.

To enter a new parameter

The parameters dictate the way in which the burner

firing  rate  alters  in  response  to  changes  in  the

pressure/temperature of the boiler.
A major factor that determines the need to change

the parameters is if the burner is fitted to a steam

or hot water boiler.  The table below indicates the

parameter and its setting for steam and hot water

boilers.  It must be emphasised that it is only an

indication and any departure from these settings

should  be  made  in  small  increments,  with  time

given  to  see  how  the  burner  is  reacting  to  the

changed parameter.

1

a

b

1

Landis & Staefa
LAL1. Program
Sequence Disk.

I

Содержание NOL

Страница 1: ...Page 1 NOL Compact Modulating HANDBOOK Series NOL fully automatic oil burner Models NOL Compact Modulating Class D Oil ...

Страница 2: ...ents 6 Plant Room Ventilation 6 Existing Appliances 7 Combustion Chamber Conditions 7 INSTALLATION 7 General 7 Fitting to the Appliance 7 Oil Supply Connections 7 Electrical Power Connection 7 BURNER AIR CONTROLS 7 Air Diffuser 7 BURNER OIL CONTROLS 7 Oil Nozzle 7 Oil Control Train 7 Modulating Unit 7 BURNER OIL SYSTEM 8 ELECTRICAL CONNECTIONS 9 OPERATION 10 COMMISSIONING 10 IMPORTANT SAFETY 10 EM...

Страница 3: ...res average water temperature and CO2 or O2 concentration ROUTINE MAINTENANCE OF NOL MODULATING BURNERS 13 General 13 Daily Checks 14 Photoelectric Cell 14 Replenishing the Fuel Supply 14 Boiler Combustion Surface 14 FAULT FINDING 14 If the Burner Fails to Start 14 If the burner is found at lockout red lockout lamp illuminated 14 Flame Occurs Followed by Immediate Lockout 14 The Burner Starts With...

Страница 4: ...NOL Compact Modulating Page 4 BURNER COMPONENT IDENTIFICATION Standard Burner Arrangement Shown All dimensions are mm 851 5 352 7 21 ...

Страница 5: ... 4 7 6 0 3 4 7 5 4 7 5 4 7 8 3 0 4 4 4 5 2 5 0 3 8 3 0 5 L O N 5 6 4 1 2 7 0 3 4 0 8 4 0 8 4 0 8 4 4 5 2 5 0 3 8 2 0 6 L O N 0 4 4 4 7 6 0 3 4 7 5 4 7 5 4 7 8 3 0 4 4 4 5 2 5 0 3 4 3 0 6 L O N 0 4 4 4 7 6 0 3 4 0 8 4 0 8 4 7 8 3 0 4 4 4 5 2 5 0 3 8 3 0 6 L O N 5 6 4 1 2 7 0 3 4 0 8 4 0 8 4 0 8 4 4 5 2 5 0 3 8 3 5 8 L O N 5 6 4 1 2 7 0 3 4 7 3 5 0 8 4 0 8 4 0 8 2 5 0 3 M E T I N O I T P I R C S E D...

Страница 6: ... complete the manual Literature on proprietary components is available on request SITE CONDITIONS AND SERVICES Fuel Storage and Handling The requirements of BS2869 will ensure that the fuel is suitable Under sustained cold and exposed conditions class D grade of fuel should be stored and supplied to the burner at a minimum temperature of 5 C 41 F Fuel Supply The oil line should consist of metallic...

Страница 7: ...facturers instructions BURNER AIR CONTROLS A motorised cable driven air flap controls the air for combustion It is located inside the air inlet Air Diffuser The air diffuser creates a pressure drop to ensure good fuel air mixing and flame stability BURNER OIL CONTROLS Oil Nozzle The oil nozzle is of the spill back type and is fitted to the front end of the inner assembly and located in the flame t...

Страница 8: ... 77 M E T I N O I T P I R C S E D 1 h c t i w S e r u s s e r P 2 e v l a V l o r t n o C l l i p S 3 e v l a v k c e h c n r u t e R n o N 4 e g u a G e r u s s e r P d e e F 5 e g u a G e r u s s e r P l l i p S 6 e v l a V f f O t u h S e g u a G 7 k c o l B d l o f i n a M r e n r u B 8 d e e F e v l a V y t e f a S C N 9 n r u t e R e v l a V y t e f a S C N 0 1 p m u P l i O 1 1 e l z z o N ...

Страница 9: ...6833 1 3 6 86 62 7 6833 7 7 K 7 7 7 7 3 1 32 5 7 51 211 7 216 9 3 1 3 8 6 32 5 7 51 211 7 216 9 851 5 7 50 1 675 3 237 21 5 029 3 1 3 8 6 ELECTRICAL CONNECTIONS M E T I N O I T P I R C S E D 2 F t n e m u r t s n I t i m i L e c n a i l p p A 1 H l a n g i S t l u a F r e n r u B 2 H l a n g i S g n i t a r e p O r e n r u B 1 N t n e m u r t s n I f f O n O e c n a i l p p A 1 P n u R s r u o H g...

Страница 10: ...l burner commissioning Nu way can accept no responsibility for consequential loss damage or personal injury which results from a failure to follow the commissioning instructions provided or from commissioning procedures being undertaken by unqualified personnel EMERGENCY INSTRUCTIONS NOL Modulating burners are designed and constructed to meet current legislation When used in accordance with the in...

Страница 11: ...id on the modulating cam box unit Switch on the burner at the control panel The modulating unit camshaft should now rotate to the high flame setting and the combustion air motor will start the air pre purge phase Allow the fan motor to run up to speed switch off the burner and check the fan rotation Anti clockwise as viewed from the motor side as the fan slows down Remove and cover the photoelectr...

Страница 12: ... Plunger Locking Screws Profile Band Cam Lever Operating Cable Adjuster Locking Screws Profile Adjuster Retaining Saddle Cable Adjuster Oil Cam A Air Cam B Oil Cam View On A Air Cam View On B View of Servomotor from underside cover removed showing position of disengagement lever Rotation for High Flame position Cams shown in the Low Flame Position Fig 1 Fig 2 Spill Pressure Reduce Increase ...

Страница 13: ...oil flow Continue to repeat a to d until the high flame oil rate is correct When a satisfactory flame is achieved again check the line and spill pressures Inch the camshaft back to the low flame position The oil consumption rate should now be between 35 and 50 of the rated maximum Measure the flue gas composition and adjust the combustion air volume as necessary Check the burner performance throug...

Страница 14: ...d before proceeding further On steam boilers check that the water level interlocks are in the made position If the burner is found at lockout red lockout lamp illuminated Reset the burner and observe the starting sequence Make reference to the Sequence Diagram and Timing Charts for the Flame Failure controls on page 15 for further information Check the fan motor overload and reset if necessary Fla...

Страница 15: ...he lockout window should also be noted prior to resetting the burner Refer to theSequence Diagram and Timing Chart below PLEASE NOTE When the control box goes to lockout it is generally performing the function it is designed for Burner Control Program Burner operational sequence based on the Landis staefa LAL1 25 Control box Note Timings are for operation on a 50 hz electrical supply only D O I R ...

Страница 16: ...lled shut down or after each mains failure the se quence switch always runs through to the start position whereby only terminals 7 9 10 and 11 receive voltage in accordance with the control pro gram It is only then that the control unit programs a fresh burner start up Note Do not press the lockout reset button or remote reset switch for more than 10 seconds RWF40 MODULATING CONTROL Basic display ...

Страница 17: ...ted range of that parameter All other parametrs must remain as supplied Note The detector range parameters SCL SCH are given as C for Hot Water temperature and bar for Steam pressure F W R 0 4 RECOMMENDED SETTINGS r e t e m a r a P y a l p s i D t o H r e t a W m a e t S l a n o i t r o p o r P d n a b 1 b P 0 1 1 e v i t a v i r e D e m i t t D 0 1 5 e m i t t e s e R t R 0 5 0 2 r o t a u t c A ...

Страница 18: ...handbook Should it become necessary to order replacement parts it is important to quote the burner model specification and serial numbers to ensure correct expedition of your order Nu way Ltd is able to offer on site Commissioning Service and Repair through its wordwide network of authorised distributors and sales offices Please contact the Nu way Service Department for further information BURNER ...

Страница 19: ...TPUT Kg h 0 5 10 15 20 TOTAL RESISTANCE mbar 50 100 150 200 240 NOL18 38 NOL18 34 NOL35 34 NOL35 38 NOL30 25 NOL50 38 NOL60 38 NOL85 38 NOL100 38 NOL50 28 NOL50 34 NOL60 34 NOL60 NOL35 25 28 Burner outputs are based on a gross calorific value of class D fuel of 12 66 kW Kg Graphs produced in accordance with BS EN 267 ...

Страница 20: ...R r o t c i r t s e R 1 1 e l z z o N l i O R E N R U B A Ø B Ø C Ø D Ø R E N R U B A Ø B Ø C Ø D Ø 4 3 8 1 L O N 8 7 1 5 6 1 2 5 1 5 6 1 8 2 0 5 L O N 0 2 2 7 9 1 8 7 1 6 0 2 8 3 8 1 L O N 8 7 1 5 6 1 2 5 1 5 6 1 4 3 0 5 L O N 0 2 2 7 9 1 8 7 1 6 0 2 5 2 0 3 L O N 8 7 1 5 6 1 2 5 1 E N O N 8 3 0 5 L O N 0 2 2 7 9 1 8 7 1 6 0 2 5 2 5 3 L O N 8 7 1 5 6 1 0 4 1 E N O N 8 2 0 6 L O N 0 2 2 7 9 1 8 7 ...

Страница 21: ...8 2 0 3 5 3 6 6 0 2 5 1 5 2 0 3 L O N 0 0 8 2 5 1 7 1 6 3 6 1 5 1 5 2 5 3 L O N 0 0 8 2 5 1 7 1 6 3 6 1 5 1 4 3 5 3 L O N 0 0 8 2 0 3 5 3 6 6 0 2 5 2 8 3 5 3 L O N 0 0 8 2 0 4 5 4 5 8 5 2 5 2 8 2 0 5 L O N 0 0 8 2 0 3 5 3 6 6 0 2 5 2 4 3 0 5 L O N 0 0 8 2 0 4 5 4 5 8 5 2 5 2 8 3 0 5 L O N 0 0 8 2 5 5 7 5 3 1 1 2 3 5 2 8 2 0 6 L O N 0 0 8 2 0 4 5 4 5 8 5 2 5 2 4 3 0 6 L O N 0 0 8 2 0 4 5 4 5 8 5 2 ...

Страница 22: ...__________ Rating ________________ Spec No ______________ Serial No _______________ Nozzles ______________ Oil Pump _____________ Commissioning date __________________ Guarantee Expiry Date ________________________ Oil type ____________________________ s l i a t e D n o i t s u b m o C w o L e m a l F t n i o P 2 t n i o P 3 t n i o P 4 t n i o P 5 h g i H e m a l F O C 2 N e k o m S O C p m e T t...

Страница 23: ... g n i c i v r e S e h t y b d e t e l p m o c e b o t e r a w o l e b s l i a t e d e h T t n e m t s u j d a e c i v r e s h c a e g n i w o l l o f d e n g i s d n a d e t e l p m o c e b o t t e e h s s i h T e t a D e c i v r e S f O s l i a t e D e r u t a n g i S ...

Страница 24: ... WAY LIMITED P O Box 1 Vines Lane Droitwich Worc WR9 8NA England Telephone 01905 794331 e mail info nu way co uk Fax Office 01905 794017 Parts Components 01905 795829 NOL Modulating PM65 Revision 101201B BS EN ISO 9001 CERT No FM00921 ...

Отзывы: