27 Troubleshooting
Defect determined:
Cause:
Remedy:
Fault code
Burner motor does not start
up
Electric supply lead faulty
Rectify faults in electrical installation
Fuse faulty
Replace
Safety thermostat locked
Unlock
42 h
Temperature of controller setting is
exceeded
Renewed start attempt after temperature
drop
MPA 22 faulty
Replace
04 h
Leak
Rectify leak
44H / 43H
No gas
Safeguard gas supply
Gas pressure monitor faulty
Replace gas train
22 h
Filter in gas train dirty
Clean or replace
Air pressure switch not in idle position
Check air pressure switch (see page 7)
20 h
Burner motor faulty
Replace
No load at terminal 5
Check plug connection and current path of
solenoid valve
Mains voltage
<
187 V
Rectify faults in electrical
installation
Burner starts up and swit-
ches to fault mode before or
after expiry of safety period
Air pressure monitor does not switch
through during pre-ventilation
See Page 7
21 h
Ignition influencing of ionization monitor See Page 8
26 h
Gas solenoid valve does not open
Replace gas train
Starting gas quantity set too low
Increase starting gas quantity
No ignition
Check ignition electrode and setting, igni-
tion transformer and cable
Phase and zero mixed up
Connect connector unit in correct phase
sequence
Flame control faulty
Check according to Page 8
2BH
Air pressure switch opens during opera-
tion
See Page 7
21 h
Gas nozzle dirty or faulty
Replace gas nozzle
Flame extinguishes
during operation
No gas
Safeguard gas supply
Filter in gas train
dirty
Clean or replace
Flame blow-off
Incorrect burner setting
27 h
Air pressure monitor contact opens
Check/replace air pressure switch
21 h
Flame signal too weak
Measure flame signal, check ionisation
electrode
27 h