VS80-130
Introduction - Installation & Operation Instructions
│
Triton
5
2.0 SPECIFICATIONS
Draft Settings –
The Triton is designed to operate with -0.04” w.c. draft in the flue
breaching. For proper operation, there must be enough natural or mechanical draft. Due to
the design of the Triton, it may operate at a positive over fire pressure up to +0.03” at -
0.02” draft. Due to installation and equipment variations, recommended air settings are a
guideline and will require alteration. See Tables 2-1 and 2-2.
Table 2-1 Riello Burners with Triton Boilers (Natural Draft)
Boiler
Model
Input
GPH (US)
Heating
Capacity
MBH
Net I=B=R
Rating Water
MBH
AFUE
Efficiency
%
Pump
PSIG
Delevan
Nozzle
Recommended Burner Settings
Burner
Air
Turbulator
VS80
0.65
79
69
86.8%
115
0.60 60
o
B
F3
4.0
0.0
VS90
0.75
91
79
86.3%
155
0.60 60
o
B
F3
6.0
0.0
VS100
0.85
103
90
85.7%
130
0.75 60
o
B
F3
6.0
0.5
VS120
1.00
120
104
85.0%
180
0.75 60
o
B
F5
3.5
1.0
VS130
1.10
131
114
84.4%
120
1.00 60
o
B
F5
4.0
1.5
General Notes:
1
Energy ratings have been confirmed by AHRI.
2
Models VS80-100 - F3 burners have an insertion depth of 2.375”.
3
Models VS120-130 - F5 burners come assembled with an insertion depth of 2.375”.
Table 2-2 Beckett Burners with Triton Boilers
Boiler
Model
Input
GPH (US)
Heating
Capacity
MBH
Net I=B=R
Rating Water
MBH
AFUE
Efficiency
%
Pump
PSIG
Delevan
Nozzle
Recommended
Burner Settings
Burner Head Shutter Band
VS80
0.65
79
69
86.8%
140
0.55 60
o
B
MBL1
(LFB)
-
7
0
VS90
0.75
91
79
86.3%
133
0.65 60
o
B
MBL1
-
6
0
VS100
0.85
103
90
85.7%
128
0.75 60
o
B
MBL1
-
10
1
VS120
1.00
120
104
85.0%
138
0.85 60
o
B
MDV1
0
7
0
VS130
1.10
131
114
84.4%
167
0.85 60
o
B
MDV1
0
8
0
General Notes:
1
Models C95-180 use Beckett AFG50 series burners.
2
“LFB” indicates the boiler must use a Low Fire Baffle (i.e. VS80).
3
Energy ratings have been confirmed by AHRI.
4
Beckett burners have an insertion depth of 3.75”.
Boiler Characteristics
Table 2-5 Triton Boiler Characteristics
Boiler Shell Weight [lbs]
310
Fuel Type
No. 2 Oil
Water Connections – NPT [in.]
1.25
Stack [in.]
6
Dimensions H x W x D [in.]
34 x 21 x 21
Approx. Boiler Weight with Water [lbs]
385
Approx. Boiler Water Content [usg]
9
Standard Coil
S-4
Electrical Rating
120V / 1Ph / 60Hz / < 12A