32 

 

ASO 

Indicates that 

the Air 

Switch is 

Open 

Fault 

 

“Air Switch Open” 

 

This is displayed when 

the boiler is expecting the 

air switch to be closed by 

a differential pressure 

generated when the 

combustion blower turns 

on. 

 
 
 1 – Are the vinyl tubes connected between the air switch and the ports on the inlet 
pipe?  Negative side of switch connects to the port on the 1-1/2” PVC elbow (2” elbow 
on Ti400). 
 2 – Check for blockage on the intake and exhaust vents. 
 3 – If fan is running the air switch may be faulty, ensure it is set at 0.2”wc. (Note: 
switch on Ti400 condensate drain must be set at 3”wc.) 
 4 – If fan is not running, check 120V wiring to blower, if ok remove low voltage 
harness from blower, if blower fails to start, replace blower, if blower does start 
problem may be with blower or Sentry control. 

 

ASC 

Indicates that 

the Air 

Switch is 

Closed

 

 

“Air Switch Closed” 

 

This is displayed when 

the boiler has turned the 

blower off and is 

expecting the air switch to 

be open.   

 1 – Is the fan running. If so check for 24V between B and D terminals (see wiring 
diagram).  If 24V is not present replace transformer.   
 2 – Check venting termination with required venting described in manual. 
 

Two Flashes 

on Fenwal 

“Flame Fault” 

 

The Fenwal controller 

senses flame prior to 

ignition sequence. 

If the combustion sequence is normal, and there is no flame prior to ignition, the Fenwal 
control is defective, and must be replaced. 

If the condensate drain gets blocked, the boiler will become flooded and terminate 
operation as the flame rod becomes immersed. This will damage the flame probe. To 
correct, free the drain blockage, and permanently prevent it from reoccurring. Remove 
and dry off the probe. Reinstall the probe and try for ignition, if it fails to stay lit, leave 
the fan run for up to three hours to dry out the insulation and probe. 

Three Flashes 

on Fenwal 

“Ignition Lockout” 

Reset Boiler so it will attempt to ignite. 
Check for proper operation of ignition components.  Make sure igniter glows and gas 
valve opens. 
Check for proper line pressure at gas valve when it opens.   
If boiler lights check for flame signal between FC1 And FC2 on Fenwal control (If 
lower then 1.2 DC µAmps see “

Boiler will not stay lit

”). 

Check combustion properties. 

Boiler will not 

stay lit

Indicates lack of a flame 

signal.  In order to stay 

running the flame signal 

must be at least 0.7 

µAmps 

If the Burner light on the Sentry is going out, go to “

Burner shutting off

”. 

Check condensate drain for blockage and check the inlet piping for ingested snow or 
water (if the flame rod gets wet, it may need to be replaced).  Check for resistance from 
flame rod to ground, must be an open circuit (O.L), if not, remove rod and bent it away 
from the burner slightly. 
Check for proper polarity of line and neutral wiring to the boiler. 

Boiler bangs 

or hisses 

Bangs or sounds like a 

kettle while burner is 

running indicates 

insufficient flow 

1 - Ensure the plumbing is as shown in manual.  Check to see if pumps are operating 
properly and water pressure is above 15psi.  

This problem can lead to boiler 

overheating! 

2 - Boiler may be plugging-up with scale or magnetite, clean with Fernox DS-40 
Descaler and Cleanser (NTI PN: 83450). 
3 - If glycol is being used the concentration may be to high, recommend using a 
concentration lower then 35%. 

Sentry 

Controller 

Locks-up 

Excessive noise, current, 

or voltage spikes in the 

120V power supply. 

Check for voltage at the wires going to the A-C-T-O-D terminals of the Boiler. 
Check the magnitude of the line voltage power supply. 
Check the Amp draw of output C1 and Ap (max 3 Amp). 
Check the Amp draw of control on start-up (max 6 Amps)

 

Display Goes 

Blank 

No power to control or 

control failure 

Check for 120V between terminals L1 and L2 at Sentry. 

 

If 120V exists turn power off and remove line voltage harness from Sentry. Then 
check for resistance between L1 and L2 of control, if the circuit is open (O.L) the 
internal fuse has blown.  Check for shorts in wires leading to circulators prior to 
replacing the internal fuse.  To access the internal fuse, remove the front decal to 
reveal the screws securing the face plate cover.   

 

If 120V not present, check wiring and for 120V at source. 

Содержание Trinity Ti 100

Страница 1: ...ne Valves 22 7 2 2 Multiple Zones with Taco Valve controller 23 7 2 3 Multiple Zones Pump controller 24 7 2 4 Multiple Temperature Zones with Injection Pumps 25 8 0 SENTRY 2100 CONTROLLER 26 9 0 LIGHT...

Страница 2: ...1 Venting material CPVC PVC See Section 3 1 Max Vent lengths Natural Gas 3 105 Equivalent Max Vent lengths Propane 3 105 Equivalent 3 50 Equivalent 4 30 Equivalent 6 65 Equivalent Weight 80 lbs 80 lb...

Страница 3: ...less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Plate include with boiler 4 INSPECTION The state or local gas inspector of the side wall horizontally vented...

Страница 4: ...amp Only approved CPVC can be inserted into the Ti400 exhaust connection Note a 4 long piece of 4 CPVC is provided with the Ti400 Check the flue outlet gasket for proper insertion and sealing prior to...

Страница 5: ...Snow allowance Example 12 19 31 Coupling and elbow to be against wall play is acceptable 18 Min The vertical portion of the exhaust termination does not require insulation if less than 5 feet in total...

Страница 6: ...rmissible to run vent pipe through an existing chimney as long as 1 The chimney is not being used by any other appliance 2 Flue gases don t enter the vacant chimney 3 Only Trinity certified venting ma...

Страница 7: ...exhaust piping must be on a slope back to the boiler a minimum of per linear foot of vent For applications where excessive condensation is possible per linear foot is recommended 9 Exhaust vent pipe...

Страница 8: ...nstalled with 105 equivalent feet of intake venting and 105 equivalent feet of exhaust venting IMPORTANT The length of one vent pipe intake or exhaust may not exceed the length of the other vent pipe...

Страница 9: ...condition as the unit will shut down and damage to the flame sensor and components can occur NEVER use copper steel or galvanized piping in the construction of the condensate system condensate is ver...

Страница 10: ...t two threads from the end Over doping or applying dope to the female end can result in a blocked gas line DO NOT TIGHTEN FITTINGS WITHOUT SUPPORTING THE GAS VALVE as damage to the valve or motor can...

Страница 11: ...be reduced until the CO is less than 140 PPM or the CO2 is reduced to 8 9 for LP Gas If the CO is over 140 PPM and the CO2 is less than 8 9 for LP Gas contact NTI for assistance CO At minimum fan spe...

Страница 12: ...t apply torque to the boiler fittings Hold the fitting when installing otherwise damage to the unit will occur 6 0 HEATING SYSTEM PIPING Caution This boiler is designed to operate in residential and c...

Страница 13: ...13 57 F PL 36 UP 26 99 0011 Notes Must use at least minimum pump size specified for Ti150 if installation requires the use of a flow switch The Taco 009 circulator will flow more through the Ti100 15...

Страница 14: ...between the LWCO and the boiler Use the normally open contacts of the LWCO to break line voltage before being supplied to the boiler Circuit is 120 Volts 12 Amps Contact NTI for proper installation an...

Страница 15: ...ASME N O F Relief valve location All other piping is same as Ti150 Quantity and location of shutoff valves and drains are at the discretion of the installer Primary Loop For Heating Model Quantity and...

Страница 16: ...ltiple Zones using Zone Valves 6 2 2 Multiple Zones using Pumps Primary Loop Max 12 apart See figure 7 2 1 Multiple 4 wire Zone Valves for wiring 7 2 2 Multiple Zones with Taco Valve controller See fi...

Страница 17: ...ements Boiler sensor 2 Lo Temp Boiler sensor 1 Hi Temp Mix sensor 1 Hi Temp Mix sensor 2 Lo Temp See figure 7 2 3 Multiple Zones using pumps and pump controller By setting the tempering valves to diff...

Страница 18: ...The boiler is immediately energized if not already on the 3 way diverting valve moves to the domestic hot water position A and the circulator is energized Hot water is circulated through the plate hea...

Страница 19: ...the responsibility of NY Thermal Inc and suitable steps shall be taken to avoid it Cleaning Secespol brazed plate heat exchangers operate with high turbulence flow even at low flow rates This high tu...

Страница 20: ...t off valve fully 2 Turn the dial on the mixing valve to the desired setting being careful not to exceed 120 F or a dial setting greater then 2 and adjust LO setting accordingly 3 Create the maximum a...

Страница 21: ...inuity check between all wires and ground to make sure that there are no electrical leaks that could damage the board Before providing 120 Volts to the boiler do a polarity check of the line and neutr...

Страница 22: ...ostat closes circuit to zone valve motor thus opening the valve When the valve is opened the end switch closes the circuit between terminals T C on the Sentry control The Sentry 2100 provides power to...

Страница 23: ...es Operation Room thermostat closes circuit to TT terminals Taco ZVC403 to ZVC 406 zone controller The controller energizes the appropriate zone valve and closes the circuit between terminals T C on t...

Страница 24: ...e pump controller The controller energizes the appropriate circulating pump and closes the circuit between terminals T C on the Sentry control The Sentry 2100 provides power to the primary pump C1 onc...

Страница 25: ...to the injection pump through the 356 Tekmar controller 3 Closes the circuit between terminals T C on the Sentry control The Sentry 2100 provides power to the primary pump via C1 once the pump is on...

Страница 26: ...the Sentry 2100 detects the presence of the outdoor sensor the controller will operate in Reset Mode If the outdoor sensor is not installed the controller will operate in Conventional Mode If outdoor...

Страница 27: ...ntrol Function and To enter the programming mode press the function key once To scroll through the various menu options depress until the menu is displayed To alter the value press Function once and t...

Страница 28: ...comes 70 when it is 70 F outdoors or higher Only used if outdoor sensor is connected 85 SFS 75 100 Starting Gas Input Value Settable from 45 90 on Ti400 models 80 for Ti100 200 50 for Ti400 HFS 100 24...

Страница 29: ...vent outlet or other sources of heat The outdoor sensor connects to the top of the boiler on terminals O and D terminals are located at the top of the left side panel on Ti400 models Formula Operatin...

Страница 30: ...a pilot It is equipped with an ignition device that automatically lights the burner Do not try to light the burner by hand B BEFORE OPERATING check all around the appliance area for gas Be sure to che...

Страница 31: ...outlet prior to the primary circulator ensure the boiler is plumbed in primary secondary fashion Replace water pressure switch if plumbing and pressure is correct and if it measures an open circuit 3...

Страница 32: ...d gas valve opens Check for proper line pressure at gas valve when it opens If boiler lights check for flame signal between FC1 And FC2 on Fenwal control If lower then 1 2 DC Amps see Boiler will not...

Страница 33: ...issue If gas valve is not held when the gas nipple is connected the force of tightening the fitting can damage the valve and warp the fan housing If pipe is used the gas line must not create any force...

Страница 34: ...ter Energizes Indirect Pump Ap turns off C1 Combi Model Sentry 2100 Call for Ignition Air Switches Sentry 2100 Open Error A S C Closed Sentry 2100 Fan to SFS 75 24 Vlot signal to blower Sentry 2100 Er...

Страница 35: ...35 12 0 WIRING SCHEMATIC...

Страница 36: ...ng 14 0 ANNUAL MAINTENANCE AND INSPECTION This unit requires very little maintenance however a Qualified Technician should inspect it at the beginning of every heating season Inspection Check list 1 L...

Страница 37: ...Drain 18A 82913 Siphon Condensate Trap 19 82767 Cast aluminum Burner door 19A 82769 Ti Ceramic burner door disc 19B 82770 Ti Burner door gasket 20 82768 Ti Igniter gasket 21 82228 Tempering valve AM1...

Страница 38: ...ensate Tee 3 4 HB to 3 4 17A 83038 Adapter 3 4 x 1 4 18 82913 SIPHON CONDENSATE TRAP 19A 82769 Burner Door Ceramic Disc 19B 82770 Burner Door Viton Gasket 20 82768 Igniter Gasket Ti Series 21 83034 Ex...

Отзывы: