Tft285 NG-LP Conversion Instructions

 

 

Trinity Tft285  

NATURAL TO LP CONVERSION INSTRUCTIONS:  

Version Date:  2018-06-07 
Kit Number: 

85802-1 

 

 

NTI  boilers  are  factory  set  to  operate  with  Natural  Gas. 

BEFORE  OPERATING  WITH  PROPANE

  the  specified 

LP-orifice must be installed. The orifice size is stamped into orifice; ensure the orifice being used corresponds to the 
boiler model being converted.  Use the procedures outlined in these instructions to fully complete the Natural Gas to 
LP conversion for Trinity boiler model Tft285. 
 

 

Kit Contents: 

 

Natural to LP Conversion Instructions (p/n 85800) 

 

Natural to LP Conversion Decal (p/n 85802) 

 

5.2 mm LP-orifice (p/n 85798) 

 
This conversion kit 

CANNOT

 be used to convert NTI appliance models not referenced in these 

instructions.  Contact  NTI  for  the  Natural  Gas  to  LP  conversion  kit  and  instructions  for  other 
models.  

 

Failure  to  apply  these  instructions  properly  may  result  in  dangerous  Carbon  Monoxide  levels, 
fire or explosion leading to property damage, personal injury or death. 

 

 

 

 

ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE 

 

Liquefied Petroleum (LP) propane gas is heavier than air; therefore, it is imperative that your  boiler is not 
installed in a pit or similar location that will permit heavier than air gas to collect. Local Codes may require 
appliances fueled with LP gas be provided with an approved means of removing unburned gases from the 
room. Check your local codes for this requirement. 

 

 
 
 

 
 
 
 
 
 
 
 
 
 

NTI # 85800 

 

This conversion kit shall be installed by a qualified service agency in accordance with 
the manufacturer’s instructions and all applicable codes and requirements of the 
authority having jurisdiction.  If the information in these instructions is not followed 
exactly, a fire, an explosion or production of carbon monoxide may result causing 
property damage, personal injury or loss of life.  The qualified service agency is 

responsible for the proper installation of this kit.  The installation is not proper and 
complete until the operation of the converted appliance is checked as specified in the 
manufacturer’s instructions supplied with the kit, which necessitates the use of a 
calibrated CO

2

/O

2

 and CO combustion analyzer. 