                                                                                                                                                                          Tft285 NG-LP Conversion Instructions

 

Adjustments to the 

Throttle/Input Adjustment Screw

 may only be made by a qualified gas 

technician, while using a calibrated combustion analyzer capable of measuring  CO

2

 and CO. 

Adjustments  may  only  be  performed  if  the  gas  line  pressure  is  maintained  above  minimum  
levels throughout the duration of the test, see  Table 2-1. Failure to follow these instructions 
may result in serious injury or death. 

 

Adjustment 

Throttle / Input Screw Adjustments - 

The boiler is equipped with a Throttle/Input Adjustment Screw, located on the 

Gas Valve. It is used to adjust the flow of gas leaving the gas valve entering the Venturi and then the combustion 
air stream. Turn the adjustment screw in (clockwise) to reduce gas flow, make combustion leaner, and reduce the 
CO

2

 concentration in the flue gases. To increase the CO

2

 level and gas flow in the combustion air stream, adjust 

the Throttle screw out (counterclockwise).  Typical adjustment for LP Gas is 0-1/4 turns in or out from the factory 
setting upon inserting the LP orifice as per these conversion instructions. See Figure 1-1 for throttle screw location. 

 
 

 

 
 

 

Combustion  Calibration

  -  To  calibrate  burner  operation,  perform  the  following  procedure  using  a  calibrated 

combustion analyzer capable of measuring CO

2

 and CO from Natural and Propane Gas burning boilers: 

1.

 

Operate the unit at the maximum modulation rate, see Table 2-2.  

2.

 

Ensure the gas line pressure is maintained within tolerance, see Table 2-1. 

3.

 

While  at  the  maximum  modulation  rate,  measure  the  CO

2

  and  CO;  adjust  as  necessary,  using  the  Throttle 

Screw, to be within the limits listed in Table 2-1. 

4.

 

Operate the unit at the minimum modulation rate (see Table 2-2). Ensure the combustion remains smooth and 
CO

2

 and CO values are lower than the values obtained during maximum modulation as per notes in Table 2-1. 

If not, do not adjust further, contact NTI for assistance. 

 

Failure to perform the flue gas analysis and adjustment as detailed in this section may result in 
erratic  and  unreliable  burner  operation,  leading  to  reduced  efficiency,  increased  fuel 
consumption,  reduced  component  life,  heat  exchanger  combustion  deposits,  and  general 
unsafe operation. Failure to follow these instructions may result in serious injury or death.  

3.0 Labeling 

As  the  certified  installer  of  the  Natural  Gas  to  LP  Conversion  Kit,  you  must  indicate  on  the  boiler  that  it  has  been 
converted for use with Propane (LP) Gas: 

 
 

1.

 

Update Rating Plate Decal

 – Locate the rating plate decal on the side of the appliance, using a regular ink pen, 

check the box next to “Field converted to Propane Gas” and fill in the date; depress hard enough to permanently 
etch the decal (see Figure 3-1). 

2.

 

Conversion Decal

 - Fill out the required information on the Conversion Decal (included in this kit) and affix it to 

the boiler cabinet adjacent to the rating plate decal, and in a location where it can be easily seen (see Figure 3-2). 

 

Figure 3-1 Update the Rating Plate Decal 
 

 

 
 
 
 
 
 
 

 

Figure 3-2 Conversion Decal 
 
 
 

 
 
 
 
 
 

      Throttle/Input Adjustment Screw

 

 

 

  

 

Increase gas 
Turn Counter Clockwise 

 

Decrease gas 
Turn Clockwise 