Trinity
│
Installation and Operation Instructions
Tft Series
82
Table 16-4 Alert Codes
Code
Description
301
Abnormal Recycle: Interrupted air flow switch was off during Main Flame Establishing Period
302
Abnormal Recycle: Ignition failed due to interrupted air flow switch was off
303
Abnormal Recycle: ILK off during Drive to Purge Rate
304
Abnormal Recycle: ILK off during Measured Purge Time
305
Abnormal Recycle: ILK off during Drive to Light off Rate
306
Abnormal Recycle: ILK off during Pre-Ignition test
307
Abnormal Recycle: ILK off during Pre-Ignition time
308
Abnormal Recycle: ILK off during Main Flame Establishing Period
309
Abnormal Recycle: ILK off during Ignition period
310
Run was terminated due to ILK was off
311
Run was terminated due to interrupted air flow switch was off
312
Stuck reset switch
313
Run was terminated due to fan failure
314
Abnormal Recycle: Fan failed during Drive to Purge Rate
315
Abnormal Recycle: Fan failed during Measured Purge Time
316
Abnormal Recycle: Fan failed during Drive to Light off Rate
317
Abnormal Recycle: Fan failed during Pre-Ignition test
318
Abnormal Recycle: Fan failed during Pre-Ignition time
319
Abnormal Recycle: Fan failed during Ignition period
320
Abnormal Recycle: Fan failed during Main Flame Establishing Period
321
Abnormal Recycle: Main Valve off after 10 seconds of RUN
322
Abnormal Recycle: Pilot Valve off after 10 seconds of RUN
323
Abnormal Recycle: Safety Relay off after 10 seconds of RUN
324
Abnormal Recycle: Hardware flame bias
325
Abnormal Recycle: Hardware static flame
326
Abnormal Recycle: Hardware flame current invalid
327
Abnormal Recycle: Hardware flame rod short
328
Abnormal Recycle: Hardware invalid power
329
Abnormal Recycle: Hardware invalid AC line
330
Abnormal Recycle: Hardware SLO flame ripple
331
Abnormal Recycle: Hardware SLO flame sample
332
Abnormal Recycle: Hardware SLO flame bias range
333
Abnormal Recycle: Hardware SLO flame bias heat
334
Abnormal Recycle: Hardware SLO spark stuck
335
Abnormal Recycle: Hardware SLO spark changed
336
Abnormal Recycle: Hardware SLO static flame
337
Abnormal Recycle: Hardware SLO rod shorted
338
Abnormal Recycle: Hardware SLO AD linearity
339
Abnormal Recycle: Hardware SLO bias not set
340
Abnormal Recycle: Hardware SLO bias shorted
341
Abnormal Recycle: Hardware SLO electronics
342
Abnormal Recycle: Hardware processor clock
343
Abnormal Recycle: Hardware AC phase
344
Abnormal Recycle: Hardware A2D mismatch
345
Abnormal Recycle: Hardware VSNSR A2D
346
Abnormal Recycle: Hardware 28V A2D
347
Abnormal Recycle: Hardware HFS IAS shorted
348
Abnormal Recycle: Hardware PII INTLK shorted
349
Abnormal Recycle: Hardware HFS LCI shorted