#84034 Trinity Lx Commercial Controller 

Issue date: 2012-Jan-11 

Replacement Instructions 

Revision date: 2012-Jan-11 

1/3

 

 

S:\NTI2001_N_Drive (1-20-09)\R&D\PARTS - ENGINEERING\Parts Department Stickers and Instructions\Current Parts Instructions (doc)\84034 instructions - 
Trinity Lx Commercial Controller.doc 

#84034 - 

Trinity Lx Commercial Controller Replacement Instructions 

 
The commercial controller (part number 84034) is configured specifically for use with Trinity Lx 
Commercial  series  boilers  only,  Lx500-800  inclusive.    This  controller  shall  NOT  be  used  with 

non Lx Commercial-series boilers.  Use of this controller on boiler models other than Trinity Lx Commercial-series will 
override some saftey features and may lead to unsafe operation resulting in fire, explosion, property damage or death. 

 
Check  the  contents  of  the  parts  received  to  ensure  the  controller  is  labeled  “

84034  Sola,Lx 

Comm.  Cfg.

”,  signifying  that  it  is  for  use  with  Lx  Commercial-series  Trinity  boilers;  see 

illustration below.   If the controller is not labeled, or has a different label, it is not intended for use with a Trinity  Lx 
Commercial-series boiler. Note: all commercial Sola controllers have a blue case, if the controller case is not blue return 
to NTI. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Controller Replacement Instructions 

 

The  instuctions  provided  in  this  document  are  a  supplement  to  the  Installation  and  Operating 
Instructions originally provided with the boiler.  Failure to follow the Installation and Operating 

Instructions may result in fire, explosion, property damage or loss of life. 
 
These  instructions  describe  the  steps  necessary  to  replace  a  controller  from  any  model  of  the  Trinity  Lx  Commercial 
series,  sizes  500  to  800  inclusive,  with  a  “generic”  controller.  Be  sure  to  thoroughly  read  and  understand  these 
instructions before attempting a controller replacement.  
 
Note: Before replacing an existing controller, record (if possible) the settings specific to the particular installation from 
the old controller, so they may be transferred to the new replacement controller. 
 

Replace the Trinity Lx Commercial controller: 

1)

 

Turn off power to the appliance via the circuit breaker, remote switch or local On/Off switch. 

2)

 

For Lx500-600 units remove the top panel. For Lx700-800 units, remove the top rear panel. 

3)

 

Remove the control panel cover. 

4)

 

Unplug all electrical connections from the controller. All wiring is connected to the controller by means of quick-
connect plugs, each of which is uniquely keyed to its mating receptacle to prevent incorrect electrical connections. 

5)

 

Remove the old controller from the panel. The controller is secured to the panel by four screws, #8 w/  ¼” hex drive. 

6)

 

Installation procedure is in reverse order. 

7)

 

Use  the  display  to  adjust  the  control parameter settings  to  the  values specific  to  the  boiler  model (see instructions 
below). 

 

 

Contact NTI if the replacement 
controller does not have this 
exact decal on the Controller. 