#84034 - 

Trinity Lx Commercial Controller Replacement Instructions 

 

2/3 

 

S:\NTI2001_N_Drive (1-20-09)\R&D\PARTS - ENGINEERING\Parts Department Stickers and Instructions\Current Parts Instructions (doc)\84034 instructions - 
Trinity Lx Commercial Controller.doc 

Control Settings Verification and Adjustments: 

1)

 

Control Configuration  Verification

 – From the “Configuration” menu, select “System  Identification and Access”.  

Check  to  ensure  the  control  is  equipped  with  the  correct  configuration  –  see  illustration  below.    Replacement 
controllers  intended  for  use  on  Lx  Commercial-series  boilers  will  begin  with  “NTI  LxCGen”.    At  this  time  the 
installer may choose to modify the “Boiler name” to reflect the boiler model the control is installed on, i.e. Lx500. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
2)

 

Modulation Rate Adjustments

 – Since the replacement control is generic to all Lx Commercial boiler models, the 

minimum  and  maximum  modulation  rates  must  be  set  to  the  applicable  values.  Select  “Modulation  Configuration” 
from the “Configuration” menu and adjust the settings according to the following table: 

 

Parameter 

Description 

Settings 

CH max. modulation 
rate 

Maximum  permissible  blower  speed  during  CH  demand.    Setting 
is model dependent. 

Lx500 = 6400 rpm 
Lx600 = 4350 rpm 
Lx700 = 4300 rpm 
Lx800 = 5300 rpm 

DHW max.  
modulation rate 

Maximum  permissible  blower  speed  during  DHW  demand.  
Setting is model dependent. 

Minimum modulation 
rate 

Minimum permissible blower speed. Setting is model dependent. 

Lx500 = 1400 rpm 
Lx600 = 1050 rpm 
Lx700 = 1250 rpm 
Lx800 = 1250 rpm 
 

 
Failure  to  set  the  modulation  rates  appropriate  to  your  specific  boiler  model  according  the 
table above may result in fire, explosion, property damage or loss of life. 

Configuration Identification 

Must begin with “NTI LxCGen” 