Lx – WH Series Installation and Operation Instructions
│
Trinity Lx
9
Figure 3-1(c) Closet Installation, Minimum Clearances (Lx500WH-Lx800WH)
Table 3-1 Minimum Clearances for Installation and Service
Model No.
Clearances
Dimensions - inches
Front
Top
Left Side Right Side
Rear
Flue Pipe
Lx200WH
Minimum
36
1
12
12
4
0
4
1
Recommended
36
24
24
2
4
0
4
1
Lx300WH & Lx400WH
Minimum
36
1
12
12
12
0
4
1
Recommended
36
24
24
2
12
0
4
1
Lx500WH-Lx800WH
3
Minimum
36
1
12
24
4
14
1
Recommended
36
24
30
24
18
1
Notes:
1
6” if surface is removable allowing 36” clearance (i.e. closet installation). See Ventilation Air Opening dimensions in
Figure 3-1.
2
Clearances can be as low as 12” if the right side has a clearance of 24”.
3
For models Lx500WH-Lx800WH, ensure rear of unit is accessible for wiring and flue gas testing.
4
Code requires all wall mounted instantaneous water heaters to be installed with suitable wall protection extending the full
length and width of the water heater. Check with local authorities regarding acceptable protection materials.
Piping
must be
CPVC
Front 24
” [610 mm]
Left Side 24
”
[610 mm]
Right Side
4
” [102 mm]
6” [152 mm]
max. below
vent opening
Top
12”
[305 mm]
1” [25 mm]
clearance for
hot water and
vent pipes
6” [152 mm]
max. above
vent opening
Removable Surface
or Closet Door
Ventilation Air Opening
1 in
2
per 1000 Btu/hr,
min. 100 in
2
Ventilation Air Opening
1 in
2
per 1000 Btu/hr,
min. 100 in
2
Ventilation Air Openings
-
Openings are not required if
the appliance area meets the
Recommended Clearances in
Table 3-1.
Rear 14
”
[356 mm]
Access
- Ensure rear of unit is
accessible for wiring and flue
gas testing. See Table 3-1.
Model Lx800
shown