6
Installation- ENVIROMUX-16D / -5D / -2D
Using RJ45 Sensor Socket
If an RJ45 Sensor socket is available, a contact sensor can be connected to it using a CAT5 cable. Connect the CAT5 cable as
indicated in the image below. Connect the white/orange and orange (ALARM) wires to the contact terminals of the sensor.
If the sensor does not have a tamper feature, or you do not wish to use it, simply omit the connection to pin 5.
APPLICATION NOTE: The wire gauge specified for connection is 16-26 awg. This will support a connection up to 1000
feet between the sensor and the ENVIROMUX.
Using DIGITAL IN Terminals
The ENVIROMUX-16D has 8 sets of terminals for connecting contact sensors. The ENVIROMUX-5D / 2D have 5 sets.
1.
Connect two 16-26 awg wires (not supplied) to the “
+
” and “
-
“ (“
+
” and “ “ on the ENVIROMUX-5D / 2D) of any set of “Digital
In“ terminals (see next page) on the ENVIROMUX.
2.
Connect the other end of those two wires to the contact terminals “N.C”
o
n the sensor. (Apply one wire to each terminal, it
doesn’t matter which wire goes on which terminal.)