NSI LUMA-NET 400CP Скачать руководство пользователя страница 9

Network ID number.

Since the Luma-net System is a digital network, all panels and devices attached (except dimmers) must have a
unique network ID number.  

If two panels have the same network ID number, the entire network will stop functioning.

Panels without a dipswitch must follow this procedure otherwise simply set the dipswitch as per the chart on the
following page.

To set Network ID number (units without dipswitch):

1.

Make sure that the 400CP is in the program mode as discussed.

2.

Press the zone 1,2,3,4 increase buttons at the same time and the BUSY LED will stop flashing

3.

Look up the necessary sequence of 1’s and 0’ for the ID number on the chart at the end of this section.

4.

Using the two buttons indicated below, enter the eight number sequence of 1’s and 0’s.

5.

The unit will exit this program mode at the release of the eighth press, and the BUSY LED will start flashing
again.

400CP REMOTE CONTROL PANEL

PROGRAMMING

Software Revision 3.00, Version C

Network ID number.

NSI CORPORATION

9

Содержание LUMA-NET 400CP

Страница 1: ...fade times Remote lockout capability is also included Installation is a snap with the simple 4 wire digital connection required IMPORTANT Programming differs from older 400CP panels prior to release 3...

Страница 2: ...or components MOUNTING The 400CP will mount in any standard double gang electrical box with the 4 screws provided See below paragraph on system turn on before final mounting of panels SYSTEM TURN ON...

Страница 3: ...re bad ID While programming the following actions are normal Quickly flashing Programming mode no mode selected Off Programming mode mode selected LOCKOUT Any 400CP may be disabled from operation with...

Страница 4: ...down all ZONE 1 4 LOWER buttons while connecting terminal block Full Memory Clear Normally the 400CP will not require memory clearing Once the memory is cleared all parameters including fade rate must...

Страница 5: ...e zone 1 increase button and the BUSY led will quit flashing 3 Press button representing desired number of dimmers as shown in the diagram 4 If more than 256 dimmers are required then press a second b...

Страница 6: ...red zone to be programmed At this point all currently assigned dimmers will come on The current dimmer selector will be set to one 4 Use the buttons marked as UP and DOWN in diagram to increment or de...

Страница 7: ...pressed If the factory default setting of 5 seconds is desired for each zone then this step may be ignored To program zone fade time 1 Make sure that the 400CP is in the program select mode as discus...

Страница 8: ...m mode as discussed 2 Press the zone 4 increase button and the BUSY LED will stop flashing 3 Look up the necessary sequence of 1 s and 0 for the ID number on the chart at the end of this section 4 Usi...

Страница 9: ...s without dipswitch 1 Make sure that the 400CP is in the program mode as discussed 2 Press the zone 1 2 3 4 increase buttons at the same time and the BUSY LED will stop flashing 3 Look up the necessar...

Страница 10: ...1100 62 01111100 63 11111100 64 00000010 65 10000010 66 01000010 67 11000010 68 00100010 69 10100010 70 01100010 71 11100010 72 00010010 73 10010010 74 01010010 75 11010010 76 00110010 77 10110010 78...

Страница 11: ...hannels assigned to the selected zone and decrease lighting levels at the programmed fade rate Release button when correct lighting levels are attained To restore control from a console Simply perform...

Страница 12: ...r or replace at its option defective materials provided you have identified yourself as the original owner of the product to NSI or any authorized NSI dealer Transportation charges to and from an auth...

Отзывы: